Loading...
HomeMy WebLinkAboutCorrespondence - 544 FOSTER STREET 9/11/2009 Al-w fe ,lw C/��77LPi�lit G/�P//il�iGG'P4� .yGCa. 44 Commercial Street Raynham,MA 02767 Tel: (508)880-0233 Fax: (508)880-7232 October 19, 2009 North Andover Board of Health 1600 Osgood Street North Andover, MA 01845 °''°" °'" Attention: Health Agent Reference: FAST° Wastewater Treatment System - Serial Number: 2N281 Attached please find the Field Inspection & Service Report with held test results for services performed on 09/11/2009 at the property of Karen O'Keefe located at 544 Foster Street -North Andover, MA. Please call if you have any questions or require additional information. Sincerely, Wastewater Treatment Services, Inc. Service Department Enclosures Copy to: Karen O'Keefe Massachusetts DEP Massachusetts Department of Environmental Protection Li Bureau of Resource Protection - Title 5 DP Approved Inspection and O&M Form for Title 5 I/A Treatment and Disposal Systems 12661 A. Installation Important: Karen O'Keefe When filling out Owner forms on the computer, use 544 Foster Street only the tab key Facility Street Address to move your North Andover 01845 cursor-do not — --- use the return City Zip key. Mailing address of owner, if different: S21=i 544 Foster Street Street Address/PO Box: North Andover MA 01845 'edi1 City State Zip 978-689 7,3599 ext. Telephone Number B. Authorized Service Provider Wastewater Treatment Services, Inc. O&M Firm 44 Commercial Street Street Address Raynham MA 02767 City State Zip 508-880-0223 ext. Telephone Number David Koshiol 2976 Certified Operator Name Certification Number C. Facility/System Information 2N281 Bio-Microbics, Inc. MicroFAST .5 DEP ID Manufacturer ID Model Number 05/29/2002 Installation Date Start of Operation Approval Type: 0 General 0 Provisional 0 Piloting ®Remedial Seasonal Residence —used less than 6 mo./year: 0 Yes ® No D. Operating Information 09/11/2009 Inspection Date Previous Inspection Date 8 Pumping Recommended Q Yes ®No Sludge Level DEPMicroFASTnew.doc• lor19/o9 Pagel of3 Massachusetts Department of Environmental Protection Bureau of Resource Protection - Title 5 DEP Approved Inspection and OM Form for Title 5 I/A Treatment and Disposal Systems 12661 E. Field Testing Field Inspection Color: 0 gray 0 brown ©clear Q turbid 0 other (specify): Odor: 0 musty ©earthy 0 moldy 0 offensive 0 turbid Effluent Solids: ©no Q some pH 7.0 SU DO 7.3 mg/L. Turbidity 2.8 NTU '6 to 9 2 or greater 40 or less Should a Remedial or General Use system fail the Field Testing, effluent samples shall be collected per Standard Methods and analyzed for BOD and TSS. F. Sampling Information Samples Taken Q Influent Q Effluent Commercial systems or systems with a design flow of 2000 gpd and greater, and General Use nitrogen reducing systems: 440 gpd Parameters sampled: 0 pH 0 BOD Q CBOD 0 TSS Q TN 0 Other(list below) Other 1 Other 2 Other 3 G. Inspection and Maintenance Description of any maintenance performed since previous inspection and during this inspection Cleaned Filter, , , Checked Splash Recycle, Notes and Comments: DEPMicroFASTnew.doc• 10/19/09 Page 2 of 3 Massachusetts Department of Environmental Protection Bureau of Resource Protection - Title 5 DEP Approved Inspection and ® M Form for Title 5 I/A Treatment and Disposal Systems 12661 H. Certification I certify:'1 have inspected the sewage treatment and disposal system at the address above, have conducted the required Field Testing and/or sample collection in accordance with Standard Methods, have completed this report and the attached technology operation and maintenance checklist, and the information reported is true, accurate, and complete as of the time of the inspection. I am a Massachusetts certified operator in accordance with 257 CMR 2.00. David Koshiol 09/11/2009 Operator Signature Date System pwner must submit this report, technology O&M checklist, and any required sampling results to the local board of health and DEP as follows for each inspection performed: Remedial Use—by January 31 st of each year for the previous calendar year Piloting Use—within 45 days of inspection date Provisional Use—by March 315`of each year for the previous 12 months General Use—by September 30th of each year for the previous 12 months Send to: Department of Environmental Protection Attention: Title 5 Program One Winter Street, 6th Floor Boston,:MA 02108 i DEPMicroFASTnew.doc• 10/19/09 Page 3 of 3 r IN C0 R P 0 R A T E 0 8450 Cole Parkway 6 Shawnee, KS 66227 w Phone 913-422-0707 B Fax: 912-422-0808 12661 e-mail: onsite(cDbiomicrobics.com n www.biomicrobics.com a 800-753-FAST(3278) FIELD INSPECTION & SERVICE REPORT For Bio-Microbics Single Home FASTO System INSTALLATION AUTHORIZED SERVICE PROVIDER 544 Foster Street Installation Address: North Andover,MA 01845 Name: Wastewater Treatment Services, Inc. Owner Name: Karen O'Keefe Mail Address: Mail Address: 44 Commercial Street 544 Foster Street Raynham, MA 02767 North Andover,MA 01845 City State Zip 508-880-0233 508-880-7232 Phone: 978-689-3599 Fax e-mail Phone Fax e-mail INSTALLATION INFORMATION Model No. Serial No. Date of Installation Date of last pump out MicroFAST .5 2N281 05/29/2002 8/l/2008.12:00:00 AM EQUIPMENT YES NO MAINTENANCE PERFORMED AND COMMENTS Electrical Panel(s) Visual Alarm Operating X Audio Alarm Operating X if resent Blower(s) Air Inlet Filter Clean X Blower Hood Vents Clear X Excessive Noise X } Excessive Vibration X I Treatment unit(s) Unusual Odor Pum out Required: X Primary Settling Zone 8" Aerobic Treatment Zone 12" EFFLUENT(option a1l LIMIT RESULT Estimated Daily Flow 440 gpd. H Standard Units) Color Clear Temperature 67.3 Odor Earth Comments: TECHNICIAN SERVICE DATE David Koshiol 09/11/2009