Loading...
HomeMy WebLinkAboutPlans - 34 SAW MILL ROAD 1/28/2016 SCOPE OF WORE{ GENERAL NOTES LEGEND AND ABBREVIATIONS TABLE OF CONTENTS PAGER DESCRIPTION SOLAR MODULES PV-1.0 COVER SHEET • SYSTEM SIZE:780OW DC,760OW AC ALL WORK SHALL COMPLY WITH 2014 NEC,2009 IBC,MUNICIPAL CODE,AND ALL SE SERVICE ENTRANCE —RAIL MODULES:(30)REC SOLAR:REC260PE(BLK) MANUFACTURERS'LISTINGS AND INSTALLATION INSTRUCTIONS. ! PV-2.0 SITE PLAN • INVERTER(S): • PHOTOVOLTAIC SYSTEM WILL COMPLY WITH 2014 NEC. —F� i (1)SOLAREOGE TECHNOLOGIES:SE 760OA-US(240V) • ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH 2014 NEC. Mp MAIN PANEL PV-3.0 LAYOUT • RACKING:SNAPNRACK SERIES 100 UL;FLASHED L FOOT. o PHOTOVOLTAIC SYSTEM IS UNGROUNDED.NO CONDUCTORS ARE SOLIDLY - I PV-4.0 ELECTRICAL SEE PEN D01. GROUNDED IN THE INVERTER.SYSTEM COMPLIES WITH 690.35. e MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. SP SUB-PANEL =STANDOFFS& PV-5.0 SIGNAGE • INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741. ❑ FOOTINGS e RACKING CONFORMS TO AND IS LISTED UNDER UL 2703. • CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31{E}AND 2012 LC IFC 605.11' ' PV LOAD CENTER CHIMNEY o ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT. e 9.01 AMPS MODULE SHORT CIRCUIT CURRENT, SM SUNRUN METER ATTIC VENT 0 14.07 AMPS DERATED SHORT CIRCUIT CIRCUIT(690.8(a)&690.8(tr)}. • SOLAREDGE RAPID SHUTDOWN KIT REQUIRED FLUSH ATTIC VENT PM DEDICATED PV METER PVC PIPE VENT INVERTERS)WITH METAL PIPE VENT INV INTEGRATED DC DISCONNECT AND RFCI T-VENT FA—C-1AC DISCONNECT(S) � SATELLITE DISH DC DISCONNECTS) '.. FIRE SETBACKS COMBINER BOX HARDSCAPE INTERIOR EQUIPMENT —PL— PROPERTY LINE L J SHOWN AS DASHED SCALE:NTS sunrun A AMPERE AC ALTERNATING CURRENT AFCI ARC FAULT CIRCUIT INTERRUPTER LICENSE NO.750184 AZIM VICINITY MAP COMP COMPOSITION DC DIRECT CURRENT ��;_s.,• (E) EXISTING EXTEXTERIOR CUSTOMER RESIDENCE: FIRM FRAMING YASMIN HIRJI INT INTERIOR 34 SAWMILL RD,NORTH LBW LOAD BEARING WALL ANDOVER,MA,01845 NAG MAGNETIC MSP MAIN SERVICE PANEL rEi.lsie}aeaaxu raN a:ioa.noae? (N) NEW _ NTS NOT TO SCALE PROJECTNUMBER: OC ON CENTER 221R-034HIRJ PRE-FAB PRE-FABRICATED DESIGNER PSF POUNDS PER SQUARE FOOT PV PHOTOVOLTAIC M.PARADIS TL TRANSFORMERLESS DRAFTER: TYP TYPICAL Y VOLTS C.MORGAN - W WATTS SHEET REV NAME DATE COMMENTS COVER SHEET A REV:A 8(2512015 PAGE PV-1.O PITCH TRUE MAG PV AREA SITE PLAN-SCALE=1132"=1'-6" AZIM AZIM (SQFT) pt AR-0115° 177 (N)ARRAY AR-02 ° 163° 195.d AR-02 15° 267° 253° 337.5 — r (E)RESIDENCE MPC p` SE SM INV r=-Y- J {N)ARRAY AR-01 sunrun LICENSE NO.750184 CUSTOMER RESIDENCE: _ YASMIN HIRJI - 34 SAWMILL RD,NORTH ANDOVER,MA,01845 TEL I—)s55aiaa PROJECT NUMBER: / EGNER: I DESGNER: e M.PARADIS DRAFTER: C.MORGAN SHEET SITE PLAN REVA 8/2512015 PAGE PV-2.0 ROOF TYPE ATTACHMENT ROOF HEIGHT ROOF FRAME FRAME TYPE FRAME MAX FRAME OC ROOF EDGE MAX RAIL MAX RAIL DESIGN CRITERIA EXPOSURE MATERIAL SIZE SPAN SPACING ZONE SPAN OVERHANG MODULES: AR-01 COMP SHINGLE FLASHED L FOOT, SEE PEN D01. SINGLE STORY ATTIC WOOD RAFTER 2 X 8** 15'-2" 16" NO 4'-0" V-4" REC SOLAR:REC260PE(BLK) AR-02 COMP SHINGLE FLASHED L FOOT. SEE PEN D01. SINGLE STORY ATTIC WOOD RAFTER 2 X 8** 15'-2" 16" NO 4'-0" l'-4" MODULE DIMS: 65.55'x 39.02"x 1.5" D1-AR-01-SCALE:3116"=1'-0" PITCH:15" 1g'-8' MAX DISTRIBUTED LOAD:3 PSF A21M:177" SNOW LOAD:50 PSF WIND SPEED: i _ I 100 MPH 3-SEC GUST. 6, LAG SCREWS: 6/167x4A":2.5"MIN EMBEDMENT o PENETRATION SPACING: 4'TYP- STAGGERED **FRAME STRENGTHENING REQUIRED:SEE SRC-St W'-N" ___§--- STRENGTHENING DETAILS I r : Y I n :j D2-AR-02-SCALE:3/16"=1'-0" 6"-1( 39'-6" PITCH:15° -6" P u n r u n PITCH: 67" G- ;._. F ,.._. I _i i,, C _. G _ n _.. CENSE NO 750184 � T S i 4 YP + ' : 3 r I !.. .MA laazalGt Atac�2 LI e __ 1 RESIDENCE O 11" - - �T? CUSTOMER REST { I } 9.14„ t 13-2., p YASMIN HIRJI 34 SAWMILL RD,NORTH 3- --- - --- _^, cv ANDOVER,MA,01845 i TEL.{9]8!- APN#:10.1A{+pBT PROJECT NUMBER: 221R-034HIRJ DESIGNER: M.PARADIS DRAFTER: C.MORGAN SHEET LAYOUT REV:A 8125(2015 PAGE PV-3.0 f 120/240 VAC SINGLE PHASE SERVICE METER#: NATIONAL GRID UTILITY 13816983 GRID SUPPLY SIDE TAP 4 ( EXISTING (N)LOCKABLE 200A MAIN BLADE TYPE (N)LOCKABLE SOLAREDGE TECHNOLOGIES:SE T BREAKER FUSED BLADE TYPE (N)SUN RUN 760OA-US(240V) AC DISCONNECT AC DISCONNECT METER 7600 WATT INVERTER PV MODULES _ REG SOLAR:REC260PE(BLK) EXISTING T3 3 3 �, 2 r 1 /j (30)MODULES 200A MAIN �� orb (M j _ --a'�� �. tl}f OPTIMIZERS WIRED IN(1)SERIES FACILITY PANEL v �� �— `Y OF(19)OPTIMIZERS AND(1)SERIES LOADS 40A FUSES JUNCTION BOX OF(11)OPTIMIZERS SQUARE D SQUARED 250V METER SOCKET LOAD RATED DC MIN RATED NEMA3R SOLAREDGE POWER OPTIMIZER D222NRB DU222RB 125A CONTINUOUS& DISCONNECT&AFCI P300 3R,60A 3R,60A,2P 240V METER 1201240VAC 1201240VAC 200A,FORM 2S CONDUIT SCHEDULE NOTES TO INSTALLER: 1. 19 VDC EXPECTED OPEN CIRCUIT STRING VOLTAGE. # CONDUIT CONDUCTOR NEUTRAL GROUND 2, CONNECT SYSTEM VIA INSULATION PIERCING ON SUPPLY SIDE OF MAIN 1 NONE (4)10 AWG PV WIRE NONE (1)10 AWG BARE COPPER BREAKER IN MAIN PANEL ENCLOSURE.CONDUCTORS ARE FIELD INSTALLED. W 2 3/4"EMT OR EQUIV. (4)10 AWG THHNITHN-2 NONE (1)10 AWG THHNITHWN-2 3 314"EMT OR EQUIV. (2)8 AWG THHNITHWN-2 (1)10 AWG THHNITHWN-2 (1)8 AWG THHN7THWN-2 4 3/4"EMT OR EQUIV. (2)6 AWG THHN/THWN-2 (1)6 AWG THHNITHWN-2 (1)8 AWG THHNtTHWN-2 LICENSE NO.750184 MODULE CHARACTERISTICS OPTIMIZER CHARACTERISTICS CUSTOMER RESIDENCE: YASMIN HIRJI REC SOLAR:REC260PE(BLK) 260 W MIN INPUT VOLTAGE 8 VDC 34 SAWMILL RD,NORTH OPEN CIRCUIT VOLTAGE 37.8 V MAX INPUT VOLTAGE 48 VDC ANDOVER,MA,01845 MAX POWER VOLTAGE 30.7 V MAX INPUT ISC 101 ADC ei,teza}sasasca SHORT CIRCUIT CURRENT 9.01 A MAX OUTPUT CURRENT 15 ADC PROJECT NUMBER: 221R-034HIRJ SYSTEM CHARACTERISTICS-INVERTER 1 DESIGNER: M.PARADIS SYSTEM SIZE 7800 W SYSTEM OPEN CIRCUIT VOLTAGE 19V DRAFTER: C.MORGAN SYSTEM OPERATING VOLTAGE 350 V SHEET MAX ALLOWABLE DC VOLTAGE 500 V ELECTRICAL SYSTEM OPERATING CURRENT 22.3 A REV:A 8125[2015 SYSTEM SHORT CIRCUIT CURRENT 30A PER CODE:600.52 PAGE PV-4.0 Sam, �, -ABELL—TION. =i.; _ .. tGXG6) _ *-$--- M: PER COpE-.P.'EC690.13.G.3&NEC LABEL LOCATION: --- 696.13.6.4 + (ACj(POIj - - PER CODE: THIS EQUIPMENT FEV BY MULTIPLE SOURCE NEC69DA1B PER CODE:70512(D)(2) TOTAL OVER CURRENT DEVICES EXCLUDING MAIN SUPPLY OVERCURRENT VEVIGE SHALL NOTEXCEEV AMPACITY OF BUSBAR M 00 PER CODE:NEC690.56RU 8 p $ ;t-S - tABEL LOCATION: (UNDER ROOFING MATERIAL) - a PER CODE:NEOG0.13.G.1LAB'2 to LOCATION 'DC)UN : IaeEL LOCATION., 1 ELECTRIC SHOCK HAZARD (DCI,iv) (DO)(INV) LABEL LOCATION: PERCCDENEC69A.ST)TOBEUSED PER CODE NEC690.13.B ON POWERONE INVERTER THE PHOTOVOLTAIC CONDUCTORS OF THIS WHEN INVERTER IS UNGROUNDED PER CODE:NEC 690.15 AND NEC 690.13(6) UNGROUNDED AND MAY BE ENERGIZED LABEL LOCATION PER CODE:NEC69G.13.13 LABEL LOCATION: TURN OFF PHOTOVOLTAIC (DtTAC)ICE) W. ..8 $e a =-1 am B_$ LABEL LOCATION: PER CODE:NEC'10.27(C} - --- (-)(Pon AC DISCONNECT PRIOR TO PER Cone NE0690,16.8 WORKING INSIDE PANEL LABEL LOCATION: 6'B 0 i- 1I''3) T PLABEL LOCATION: (AC) TAC)(POI) Id PER GORE:NEG69033.E.2 PER PER CODE:1,4E0690.54 LABEL LOCATION: EL LAPEL LOCATION. DO NOT UfO TOUCH TERMINALSCK PER P'ER CODE:NEC 690.17E (INDIVIDUAL BREAKERS) TERMINALS ON BOTH LINE AND \ PER CODE NEC70>1203 4 LOAD SIDES MAY BE ENERGIZED sunrun IN THE OPEN POSITION DC VOLTAGE IS ALWAYS PRESENT l BEL LOCATION: WHEN SOLAR MODULES ARE (DC)(INV) EXPOSED TO SUNLIGHT LICENSE NO.750184 PER CODE:NEC690653 LABEL LOGATIQN: (DC)(INV) PERCODE IFC.60.1131FC605.IAA NEC69245,NEC69CI3(B)&NEC 690.14C.2. INVERTER OUTPUT CONNECTION LABEL1) LOCATIONP. : CUSTOMER RESIDENCE: DO NOT RELOCATE THIS PERI)CODE NEC 70512.D.2 YASMIN HIRJI - _-- OVERcuRRENT DEVICE 34 SAWMILL RD,NORTH '. ANDOVER,MA,01845 pffl -i - TEL(978)68 NA APN8'.104-7-- (AC)EPER CODE 69013.. ;. PROJECT NUMBER; LEGEND AA - - - -�� 221R-04HIRJ LABEL LOCATION., (AC):AC Disconnect ELECTRIC SHOCK HAZARD AC)(POI) (C):Conduit DO NOT TOUCH TERMINALS DESIGNER: TERMINALS ON 80TH LINE AND PER CODE NEC 690.11.E (CB)Combiner Box LOAD SIDES MAY BE ENERGIZED M.PARADIS (D)Distribution Panel IN THE OFEN POSITION DRAFTER: (DC):DC Disconnect O.MORGAN (IC):Interior Run Conduit (INV):Inverter With integrated DC disconnect SHEET (LC):Load Center SIGNAGE (M):Utility Meter (POI):Point of interconnection REV:A 8/2512015 PAGE PV-5.0 Installers to verify rafter size.spacing and sloped spans,and notify E.O.R.of any discrepancies before proceeding. RIDGE F S40Q�4$QPN 4 Ft, y I b I MAX VERAGE - -- ------- HORt.SPACING C OLLAR T3ES ' 4 P b ROOF SUPPORTS WHERE APPLIES st1 SLOPE (NO BEARING V!ZL BELOWI OI a o b o o @ o acs j: r2 as " �I O O- e5 O 6 INTERIOR WALLS 114 I t 1LOCATION MAY VARY) TYP RAIL SEE O3 OVERALL SPAN l RAFTER TRUSS CHORD SEE PORTRAIT ROOF STRUCTURAL INFO RS°FARCHS DETAIL 2 ROOF TYPE—COLLAR TIES DETAIL(l)STAGGERED ATTACHMENTS LAYOUT see RV d.awm9srorelsiaaw,o saga of roor. E EXISTING 4 STRUCTURAL INFORMATION �tiwsN��s.i SRC Job Id: 7441 "ss ESN SE,eGG RE°i �� Coiling Type: 112 gyp.Ed. `;�s otys`StP A t Collar Tic Space: 32 Coverage%: 23 Rv MoDILE Frame Size: 3-2x6@16 � Ground Snow f psf): 50 6 PLALENEW MEhiBEft AT MIDSP.IN OF St.Pefl ROOT Sfi'Qw Load{j}S SQ ROOF- - RAFTER _EMSTING CEILING Lag Screw DA3,Rtet.r i£€: Sit sHTG. �- C) MEP.1eER i Lag SctasV Embedment(ir,): €.5 Ce Overall Sao.^.(fti' 34 EXISTING I! PV Orientation: Portrait r --- INTERIOR YJALL Pt' e1�Slit(If: 3 TYPICAL 2RAIL SYSTEM RAFTER STRENGTHENING DETAIL Rafter Sloped Span IN): 45.967 V, OF =r,4* Rail System: 2Rad -PV MODULE {, Roofing Type_. Comp.Shingle STANRAIL I—RAiNDOFF t—. l,�STANDOFF J1if $ A, Roof dear;Height(ft): Is PV MODULE f I ROOF SHTO- 11DAM$ �, RooF SHTG. Rooi SiOpe,degrees); 95 ROOF SHTG. t p STRUCTURAL Roof Type CollarTies RAFTER- � F�-NEYY 21MER1eER SISTEREDSloped corliflg?: No ("1 I ( ` ALONGSIDE OF EXISTING RAFTER WHERE PV STANDOFFS OCCUR f,7f. IST ,ti Standoff M§X,Hort,Space(f2)' 4 _ J6RS// k�hA%.AYE RAGE Fla SASPACING HORIZ.SPA.CING� � --ADDITIONALZx EACH StONAL><t' Starx$o{`f Max.Vert.$}]aG8(its: 2,75 Ft. SIDEG—STING Somdof€Sf.ggered?: Yes SECTION A-A EXpir.R513Rt2016 Wind Exposure: C SK-1 RAFTER STRENGTHENING DETAIL D€guatly Signed by James A.Adams,S.E. Wind Speed(mph). 100 DETAILFLUSH MOUNT PROPERTY OF SOLAR-ROOF-CHECK.COM,JAMES A.ADAMS,P.E. Date:2045.06.2513:07:37.0740 This sheet not to be used without permission from SOLAR-ROOF-CHECK.COM sunrun Sunrun DESIGNER: SRC _Tr-BE Hirp.Yasmin Residence_ STRUCTURAL SHEET DATE 775 Fiero Lane DRAFTER: SRC 221 R-R'=IIRJ 34 Sawmill Rd DETAILS S'I R `25`2DS San Luis Obis o GA 33STr9 North Andover,MA G2645