Inspection - 445 BOSTON STREET 1/24/2007
44 Commercial Street Raynham,MA 02767 Tel: (508)880-0233 Fax; (508)880.7232 January 24, 2007 f North Andover Board or Health i,l 1600 Osgood Street t North Andover MA 01845 ' �r Attention: Health Agent Reference: FAST° Wastewater Treatment System Serial Number: 21762 Attached please find the Field Inspection& Service Report with field test results for services performed on 01/09/2007 at the property of Thomas Connolly located at 445 Boston Street -North Andover, MA. Please call if you have any questions or require additional information. Sincerely, Wastewater Treatment Services, Inc. Service Department Enclosures Copy to: Thomas Connolly Massachusetts DEP Massachusetts Department of Environmental Protection Bureau of Resource Protection - Title 5 DEP Approved Inspection and O&M Form for Title 5 I/ Treatment and Disposal Systems 8155 A. Installation Important: Thomas Connolly When filling out Owner forms on the computer,use 445 Boston Street only the tab key Facility Street Address to move your North Andover 01845 cursor-do not City Zip use the return key. Mailing address of owner, if different: 445 Boston Street Street Address/PO Box: North Andover MA 01845 City State Zip 978 975 7694 ext. Telephone Number B. Authorized Service Provider Wastewater Treatment Services, Inc. O&M Firm 44 Commercial Street Street Address Raynham MA 02767 City State Zip 508-880-0223 ext. Telephone Number Michael Dillen 11173 Certified Operator Name Certification Number C. Facility/System Information 21762 Bio-Microbics, Inc. MicroFAST .5 DEP ID Manufacturer ID Model Number 01/06/2003 Installation Date Start of Operation Approval Type: Q General Q Provisional Q Piloting ®Remedial Seasonal Residence—used less than 6 mo./year: Q Yes ®No D. Operating Information 01/09/2007 Inspection Date Previous Inspection Date 12" Pumping Recommended Q Yes ®No Sludge Level DEPMicroFASTnew.doc•1/24/07 Page 1 of 3 Massachusetts Department of Environmental Protection Bureau of Resource Protection - Title 5 DEP Approved Inspection and O&M Form for Title 5 II Treatment and Disposal Systems 8155 E. Field Testing Field Inspection Color: Q gray Q brown ®clear Q turbid Q other (specify): Odor: Q musty ®earthy Q moldy Q offensive Q turbid Effluent Solids: ©no Q some pH 7.0 SU DO 5.11 mg/L. Turbidity 8.42 NTU E to 9 2 or greater 40 or less Should a Remedial or General Use system fail the Field Testing, effluent samples shall be collected per Standard Methods and analyzed for BOD and TSS. F. Sampling Information Samples Taken Q Influent Q Effluent Commercial systems or systems with a design flow of 2000 gpd and greater, and General Use nitrogen reducing systems: 440 gpd Parameters sampled: Q pH Q BOD Q CBOD Q TSS Q TN Q Other(list below) Other 1 Other 2 Other 3 G. Inspection and Maintenance Description of any maintenance performed since previous inspection and during this inspection Cleaned Filter, , , Checked Splash Recycle, Notes and Comments: DEPMicroFASTnew.doc•1/24/07 Page 2 of 3 Massachusetts Department of Environmental Protection Bureau of Resource Protection - Title 5 DEP Approved Inspection and O&M Form for Title 5 I/A Treatment and Disposal Systems 8155 H. Certification I certify: I have inspected the sewage treatment and disposal system at the address above, have conducted the required Field Testing and/or sample collection in accordance with Standard Methods, have completed this report and the attached technology operation and maintenance checklist, and the information reported is true, accurate, and complete as of the time of the inspection. 1 am a Massachusetts certified operator in accordance with 257 CMR 2.00. Michael Dillen 01/09/2007 Operator Signature Date System owner must submit this report, technology O&M checklist, and any required sampling results to the local board of health and DEP as follows for each inspection performed: Remedial Use—by January 31 s`of each year for the previous calendar year Piloting Use—within 45 days of inspection date Provisional Use—by March 31 s`of each year for the previous 12 months General Use—by September 30th of each year for the previous 12 months Send to: Department of Environmental Protection Attention: Title 5 Program One Winter Street, 6'h Floor Boston, MA 02108 DEPMicroFASTnew.doc•1/24/07 Page 3 of 3 2il=PO RATEO 8450 Cole Parkway m Shawnee, KS 66227 m Phone 913-422-0707 m Fax: 912-422-0808 8155 e-mail: onsite(c)-biomicrobics.com m www.biomicrobics.com m 800-753-FAST(3278) FIELD INSPECTION & SERVICE REPORT For Bio-Microbics Single Home FASTO System INSTALLATION AUTHORIZED SERVICE PROVIDER 445 Boston Street Installation Address: North Andover,MA 01845 Name: Wastewater Treatment Services,Inc. Owner Name: Thomas Connolly Mail Address: Mail Address: 44 Commercial Street 445 Boston Street Raynham, MA 02767 North Andover,MA 01845 City State Zip 508-880-0233 508-880-7232 Phone: 978 975 7694 Fax e-mail Phone Fax e-mail INSTALLATION INFORMATION Model No. Serial No. Date of Installation Date of last pump out MicroFAST.5 21762 01/06/2003 1/1/2006 12:00:00 AM EQUIPMENT YES NO MAINTENANCE PERFORMED AND COMMENTS Electrical Panel(s) Visual Alarm Operating X Audio Alarm Operating X if resent Blower(s) Air Inlet Filter Clean X Blower Hood Vents Clear X Excessive Noise X Excessive Vibration X Treatment unit(s) Unusual Odor Pum out Required: X Primary Settling Zone 12" Aerobic Treatment Zone 12" EFFLUENT(optional) LIMIT RESULT Estimated Daily Flow 440 gpd. H Standard Units Color Temperature 56.4 Odor Earth Comments: TECHNICIAN SERVICE DATE Michael Dillen 01/09/2007