Re: Lot 13A Equestrian Drive
Dear Sandy:
Please find enclosed a sketch showing the revised septic design for the above
mentioned lot. We were concerned with the grading that was being done on the
site so at the time the foundation was being located a topography of the site was
conducted. Due to the location and elevation of the stone retaining wall and the
grades, the breakout criteria could not be met for the original design.
The enclosed sketch shows the existing site conditions, the approved septic
location and the new proposed septic location. The original septic design, revised
to June 1, 1995, was for the installation of 2 trenches: 79' long, 4' wide, 12" deep.
Total system area was 948 s.f. and system capacity was 663.6 gallons.
In order to meet breakout, according to existing conditions, the septic system was
redesigned to 2 trenches: 54' long, 4' wide, 24" deep. Total system area is 864 s.f.
and system capacity is 669.6 gallons. All system design calculations and invert
information are shown on the sketch. These trenches are designed in the same
location as the original design, starting at the end of the original trench locations
and then running 54' along the same line as the original design. The system does
not require any fill requirement.
We ask that you accept this sketch as the revised septic design for this lot and we
will reflect these changes on the "as-built".
ENGINEERS ® ® LAND SURVEYORS ® ® LAND USE PLANNERS
447 Old Boston Road U.S. Route #1 Topsfield, MA 01983
(508) 887-8586 FAX (508) 887-3480
Sandy Starr Page 2
October 25, 1995
Thank you for your time and effort in resolving this matter.
If you have any questions or concerns please do not hesitate to call.
Very truly yours,
THOMAS E. NEVE ASSOCIATES, INC.
r � e
John Morin, EIT Thomas E. Neve
Civil Engineering Consultant President, CEO
Enclosure
JM/ec
41478 Johnston.wps '......
j
SCALE : 1 4-0
O c.+ . Z4 1 �
3
5YS TSrat L-O(.A-rl(!Nrya
-- ��/ ll'�� �,E��►w � /1 , I I I I I
°T"P1AJ1(
0 F3 Ox vi
r ( I 1
ti I 1 I
w
♦ � 4d
�o�tcr�+ AttEA 0-5S c.AL/sp
lobl tr
-ro`PAL ->-J-,
w rod GAP A<. Al_
C�EEp
0 OF
THOM E.
�Trorn 'P2E"*lGt-1 = 13S.3C> ��R�+J
NEV
CIVIL
O
p,rJK OUT
et,l I-:,
NAL
THOMAS E. NEVE ASSOCIATES, INC. [�R L VM @ T, UMA 1"N1_NM L�U1A1
Engineers a Land Surveyors rh Land Use Planners
447 Boston Street US #1
TOPSHELD, MASSACHUSETTS 01983 DATE JOB NO.
FAX (508) 887-3480 FAX
7
� ` �
��l t
WE ARE SENDING YOU 17(Attached ❑ Un r e arate cover via the following items:
El Shop drawings ( Prints ❑ Plans Samples ❑ Specifications
❑ Copy of letter ❑ Change or
COPIES DATE NO. DESCRIPTION
i- -°
tt 1418'i A pf °°%M wr A a "ISM C=
THESE ARE TRANSMITTED as checked below:
• For approval ❑ Approved as submitted ( ,Resubmit "" copies for approval
• For your use ❑ Approved as noted ❑ Submit copies for distribution
❑ As requested ❑ Returned for corrections ❑ Return corrected prints
❑ For review and comment ❑
❑ FORBIDS DUE 19 ❑ PRINTS RETURNED AFTER LOAN TO US
REMARKS _ 1 G F' '1
COPY TO
RECYCLED PAPER: SIGNED
9�Contents:40%Pre�Consumer^10%Post-Consumer c
If enclosures are not as noted,kindly notify us at once.
PLAN REVIEW CHECKLIST
ADDRESS ,":°:' ° r �rr 's ENGINEERF.. m.
GENERAL
3 COPIES STAMP '",," LOCUS w - NORTH ARROW ~" SCALE mm ....
CONTOURS '"'°'µ " PROFILE "`" SECTION .- BENCHMARK S SOIL &
PERC INFO ELEVATIONS WETS . DISCLAIMER w" WELLS &
WETLANDS C r """" WATERSHED? , DRIVEWAY -," (Elev) WATER LINE —"
FDN DRAIN SCH40 "" TESTS CURRENT?
SEPTIC TANK
MIN 1500G '° 17 INVERT DROP ,,
��°"'"" GARB, GRINDER L(+200% EDF)
25 ' TO CELLAR �`'" MANHOLE TO GRADE ELEV GW
D-BOX
SIZE # LINES FIRST 2 ' LEVEL STATEMENT
INLET 1, ', - OUTLET �E � _ � (21' OR . 17 FT) TEE REQ' D?
LEACHING
MIN 660 GPD? ".._ ,,. RESERVE AREA 4 FROM PRIMARY? " W' ~ 24 SLOPEA1y',,
100 1 TO WETLANDS +-w 100 1 TO WELLS 41 TO S .H.GW
35 ' TO FND & INTRCPTR DRAINS '-' , 325 ' TO SURFACE H2O SUPP
r'
4 ' PERM. SOIL BELOW FACILITY, MIN 1211 COVER FILL? .,,,' ) (25 '
if above natural elev; 10 if below) BREAKOUT MET.
TRENCHES
..., ,t t ,,- ..".....,. ,,.,.
MIN 660 gpd SLOPE (min . 005 or 6 /100 ) >3 ' COVER?-VENT
SIDEWALL DIST. 2X EFF. W OR D (MIN 6 ' ) "°"`' IS RESERVE BETWEEN
TRENCHES? ' °`' IN FILL? MUST BE 10 ' MIN. "" 4" PEA STONE?
BOT .; '° '... , X LDNG 4 " = TOT r ��
....r . X LDNG ",,. + SIDE , ....
(L x W x #) (G/ft2) (DxLx2x#) (G/ft2)
Copyright Q 1993 by S.L.Starr
THOMAS NVE ASSOCIATES, INC. ������ 0� ��Q���D��Q�
Engineers - Land Surveyors - Land Use Planners
447 Boston Street US Route #1
TOPSFIELD, MASSACHUSETTS 01983
DATE JOB NO.
(508) 887-8586 Iv®v. 3 ►�J��l- 13�� - 13�
FAX (508) 887-3480 ATTENTION
SAa®y 5°rAr�P�
RE:
TO /,.,oi®y S�AR� SEP�ie, iZ(�v4Sio►.a5 ►.oT 13A
N130IR°rH APa®oyGR �.®. 11. EQ���-P-PZ ►,o,4.� bt�iv�
> WE ARE SENDING YOU ❑ Attached ❑ Under separate cover via the following items:
❑ Shop drawings ❑ Prints ❑ Plans ❑ Samples ❑ Specifications
❑ Copy of letter ❑ Change order ❑
COPIES DATE NO. DESCRIPTION
REV ,113194 )38Z-1 SA.J4°rArzy e'ifP>oSA" SYS-rMM LoT 13 A
E:Q06..-;-'rMtA.J -
THESE ARE TRANSMITTED as checked below:
)( For approval ❑ Approved as submitted ❑ Resubmit copies for approval
❑ For your use ❑ Approved as noted ❑ Submit copies for distribution
> ❑ As requested ❑ Returned for corrections ❑ Return corrected prints
❑ For review and comment ❑
❑ FOR BIDS DUE 19 ❑ PRINTS RETURNED AFTER LOAN TO US
REMARKS DP_AR P4_EA<,E rioJD 5-K.)c—L_o:SF.p 3 PKr "TS c>F -rr1E_
RF_V►SEfl SI✓.P-riC_ pESIGN FO LoT 1-3 EQJESTf21AnJ D rt.1yF.-
Riz.y% aloos HA\/E. 13GE+V MACE C>2DIrJCs TO Y®urL L®MMEN7-5
0,11 yoaK oc t— 3l 1 Q4- 1e_+tfc-. 10 gE5pc>o5e, To Ynv2 Lo"Im4ENJT !�
'rt-1E PEe-►Z G T' I ac>rror'-\ or= -r He
_17115 E�_-r.\/ATinrJ CE 11+E�_ P62C_ -TEST 1-5 14� or �'HE -PeP2c
wAS C_o"C>0c_TSC> °5Z" BF_L'0( .s CrfZADP_ 4.JHIC-1-1 Cr1v�5 Yoy A� E4_a,-/AT10i&J
DFC 134.3'. TN15 I j I If 6Et.aw Do71D/`^i of r/ZErjC.H EL = 135.3o'. !F
yav IAA V0 A^JY FL)f? rHEiz QvP-srI®,,3:f> I;::1c_c:A5E
1-1F_51 TAT-V C-Atj,_ iNJC_
COPY TO
SIGNED:
PRODUCT2402 � Inc,Groton,Mm 01471. If enclosures are not as noted, kindly notify us at ce.
._�1tz,'H��'i\�a2.\v7DSSA3a'SkiHHtY AAlliiili l9S�'FTS3r1�'bU.Liiu'TS>ASYS.Iii¢..�\o`;-0.SW!}3„AJ.iTYil.`:S.�mme�a.m.sm+ .i��.+o..a�.•+'�.r�. .._._......_ .--__
NORTN
BOAM OF HEALTH
a° .....: . ....: .. p
u
° 120 MAIN STREET TEL. 682-6483
CH NORTH ANDOVER, MASS. 01845 Ext23
SAUS
October 31, 1994
Thomas E. Neve Associates, Inc.
447 Oid Boston Road
Topsfield, MA 01983
RE: Lot 13A Equestrian Drive
Dear Tom:
This is to notify you that the proposed plans for Lot 13A
Equestrian Drive, North Andover, MA, dated August 5, 1994 have
been disapproved for the following reasons:
1 - Percolation test is not at the bottom of the system.
(r Distance from house to septic tank is missing. .
3 - Only 2" of pea stone is specified; must be either 4" of
Cfeastone or 2" peastone with filter fabric.
- The foundation drain is missing.
�)/C5 - Please add a note that all stone is to be double-washed.
6 - Septic tank has no manhole to grade.
i
� �
DATE Sheet of
BOARD OF HEALTH
TOWN OF NORTH ANDOVER
SUBSURFACE DISPOSAL DESIGN REVIEW /
o
FEE PERMIT # DATE RECEIVED% /�"
APPLICANT ��Nf�Lb ��j' / iG�?: ASSESSOR' S MAP
ADDRESS PARCEL #
LOT # /
/ STREET
ENGINEER t)6-U& /a J�
ADDRESS
PLAN DATE REVISION DATE
CONDITIONS OF APPROVAL:
APPROVED
DISAPPROVED -
7`0
PLAN REVIEW CHECKLIST
ADDRESS , �" °p" �/:rvc 71;�/ /�,� ENGINEER
GENERAL
3 COPIES °' STAMP LOCUS � ". NORTH ARROW SCALE .._
CONTOURS (....... w,,._ PROFILE(——- SECTION L, BENCHMARK SOIL &
PERC INFO ELEVATIONS WETS. DISCLAIMER WELLS &
WETLANDS l �' ' WATERSHED? ° DRIVEWAY (Elev) WATER LINE
FDN DRAIN ; SCH40 L .�"" TESTS CURRENT?
SEPTIC 'I ANK
MIN 1500G . 17 INVERT DROP GARB. GRINDER k',:) (+200p EDF)
25 ' TO CELLAR MANHOLE TO GRADE �" ELEV GW
D®BOX
SIZE # LINES FIRST 2 ' LEVEL STATEMENT , "
INLET �/ ° '� ; OUTLET O° y �� �. - 2 OR 17 FT TEE REQ D. �� c
® °� ( It ) t . fy
f>f�:
LEACHING
MIN 660 GPD? L,,,,- RESERVE AREA t.-. 4 ' FROM PRIMARY? L_'- 2% SLOPE
100 ' TO WETLANDS L 100 ' TO WELLS 1--"," 4 ' TO S.H.GW
35 ' TO FND & INTRCPTR DRAINS , 325 ' TO SURFACE H2O SUPP <..
4 ' PERM. SOIL BELOW FACILITY � MIN 12" COVER ( FILL?A)e) (25 '
if above natural elev; 101if below) BREAKOUT MET?
TRENCHES
MIN 660 gpd .,. "" SLOPE (min . 005 or 6"/1001 ) >3 ' COVER?-VENT el,,'s
SIDEWALL DIST. 2X EFF. W OR D (MIN 61 ) , IS RESERVE BETWEEN
TRENCHES? IN FILL?,I�L MUST BE 10 ' MIN. 4" PEA STONE?,L
BOT X LDNG ' + SIDE 'f .' X LDNG,,'�/4 = TO
(L x W x #) (G/ft2) (DxLx2x#) (G/ft2)
Copyright 0 1993 by S.L.Starr
May 16 , 1994
Town of North Andover
Board of Health
120 Main Street M �
North Andover, MA 01845
Subject: Lot 13A, 40 Equestrian Drive
Request for Percolation Testing
Dear Members of the Board:
On Thursday, May 5, 1994 , Thomas E. Neve Associates conducted deep
observation hole testing which was witnessed by Ms. Sandy Starr,
Health Agent. Due to scheduling time constraints, the percolation
tests could not be performed.
On May 12 , 1994 , we received a proposal for engineering services
from Mr. Neve which advised that percolation tests could not be
performed until July due to a scheduled vacation of the Health
Agent. Due to a pending offer from a buyer to purchase this lot,
we are unable to wait until July for percolation testing and
subsequent redesign. This offer has been made subject to
percolation test results. As you are probably aware, we are
absorbing significant additional costs to secure a new septic
system permit and, most likely, a new order of Conditions from -the
Conservation Commission.
We respectfully request an appointment as soon as possible with the
Board of Health, the Health Agent, or other representative -to
witness the required percolation testing in order for us to proceed
with design and the sale of this lot.
We have requested Mr. Thomas E. Neve, P.E. , to contact you to make
the necessary arrangements.
Sincere y yo rs,
William E.E. Goodrich and Rita Am lfitana
38 Terrace Park
Reading, MA 01867
(617) 944°-8961 (H)
( 617) 439®9351 (W)
cc: Mr, Thomas E. Neve
April 19, 1994
Town of North Andover
Board of Health
, , .,,
120 Main Street �. ��;������ .°
North Andover, MA 01845
Subject : Lot 13A, 40 Equestrian Drive
Request for Percolation and
Deep Observation Bole Tasting
Dear Members of the Board:
We have been the Owners of Lot 13A, Equestrian Estates, since
September, 1985 . A septic system was originally designed by the
Developer' s Engineer, Thomas E . Neve Associates, and approved by
the Board of Health on September 5, 1985, Permit No. 78 .
We are currently in the process of selling this lot to another
buyer. We requested Mr. Thomas E. Neve, P . E . , review the original
design and its compliance with current local and state
requirements . He has advised us that new testing is required for
a new design to comply with current requirements .
We request an appointment with the Board of Health or its agent to
perform and witness required percolation and deep observation hole
testing to the extent necessary.
Mr. Thomas E. Neve, P. E . , of Thomas E . Neve Associates is
authorized to act on our behalf in proceedings with the Board of
Health and its agents .
Sincerel f yours, ...
William E. Goodrich and Rita Amalfitano
38 Terrace Park
Reading, MA 01867
(617) 944-8961 (H)
(617) 439-9351 (W)
,aoRrN
O0L
O
BOARD OF HEALTH
120 MAIN STREET TEL. 682-6483
9'TS ACHUSEt NORTH ANDOVER, MASS. 01845 Ext23
April 1, 1994
Thomas E. Neve Associates, Inc.
447 Old Boston Road
Topsfield, MA
Re: Lot 13A Equestrian Drive
Dear Tom:
It is possible, of course, to use old tests and still design
a new system that this department will approve. However, were
the new design to place the leaching area in the same location as
that shown on the plan dated, August 7, 1985, it would not be
approved. New soil tests would definitely be required.
If you have any questions, please do not hesitate to call me
at the number above.
Sincerely, �--
Sandra Starr, R.S.
Health Administrator
SS/cjp
r1
r ,, I
�. .E
March 31, 1994
Ms. Sandy Starr
Health Agent
120 Main Street
North Andover, MA 01845
Re; Lot 13a Equestrian Drive,North Andover
Dear Sandy;
Enclosed please find a copy of the Sanitary Disposal System Design for the
above-referenced lot. This plan was previously approved and has expired. Our
client has asked that we update this plan so that it can be approved by your Board.
Will you accept a new design on the lot according to new regulations using old
test pits or do you want us to do new percolation tests and deep hole observation
test pits?
Please get back to us with your decision so that we can properly advise our client.
Very truly yours,
THOMAS E. NEVE ASSOCIATES, INC.
Thomas E. Neve, PE, PLS
President
TEN/krn
Enclosure 11354-13a EQUESTRIMPS
ENGINEERS ,,, LAND SURVEYORS LAND USE PLANNERS
447 Old Boston Road U.S. Route 01 'I"o1]sfield, MA 01983
(508) 887.8586 FAX (508) 887-3480