HomeMy WebLinkAboutCertificate of Compliance - 54 STERLING LANE 11/27/2000 TOWN OF NORTH ANDOVER
BOARD OF HEALTH
CERTIFICATE OF COMPLIANCE
DATE OF COMPLIANCE
11/27/00
This is to certify that
the individual subsurface disposal system
constructed ( X) or repaired ( )
by
Dave Maynard
at
Lot 2 Sterling Lane
has been installed in accordance with the provisions of Title V of the State Sanitary Code
and with the North Andover Board of Health regulations.
The Issuance of this certificate shall not be construed as a guarantee that the system will
function satisfactorily.
,r
Board of Health Inspector
TOWN OF NORTH ANDOVER SEWAGE DISPOSAL SYSTEM
INSTALLATION CERTIFICATION
The undersigned hereby certify that the Sewage Disposal System(><5 constructed;
) repaired;
located at
Z
was installed in conformance with the North Andover Board of Health approved plan,
System Design Permit# dated 21,- o (,I with an approved design
flow ofd gallons per day. The materials used were in conformance with those
specified on the approved plan; the system was installed in accordance with the
provisions of 310 CMR 15.000, Title 5 and local regulations, and the final grading agrees
substantially with the approved plan. All work is accurately represented on the As-built
which has been submitted to the Board of Health.''
�Bed inspection date:
Z ingmeer,Representative
Final inspection date: -,//
agineer Representative
X,
Installer
Date:
:"141�k'�
Design En Date:
gineer:
I t
�
/
r �
INSPECTION CHECKLIST FOR SEPTIC SYSTEMS �
Yes NO loido|e
A. Bottom ofBed
1. Excavation to proper dcpdepth �
2. With trenches,sides ofexouvadoo are beneath 0borizon ----- �
3. Edge of excavation specified distance from foundation, etc.
Comments: �
B. l. V�l-heightandwidth as specified
2. Waterproofed
3. Wall minimum 1O`to leaching facility
4. Wall meets specifications*fplan
Comments:
C. Building Sewer
l. Pipe diameter minimum 4" L~/^
2. Schedule 40 pipe 41 ",_
]. Watertight joints
4. Inlet to tank cemented
5, Slope minimum 0.0i or |N"per foot minimum
6. Pipe properly set ou compact firm base
7. Pipe laid on continuous grade io straight line
8. C|cunoutm precede all change in alignment and grade
0. Manholes mt any yO"change
18. 10` minimum offset Lowater|ioe
Comments:
�
D. Septic Tank �
l. Level
l 1,500 gal
3. Ouo - on outlet
4. Manhole tugrade
j. Manholes over center and each tee
6. 3-20`,manholes
7. Inlet tee minimum i2`under invert
Q. Oui1ct tee minimum 14"under invert
9. Outlet line cemented
10. Air space 3`^above tees
i1. 2'`-3"drop from inlet[ooutlet
12. Pipe set
13. Compact base with R`ofl4"crushed stone under tank
14. Tank iowatertight
Comments:
]
�
Yes NO
E. Pump Chamber
1. If separate from tank,compact base with 6"of-1/4"stone underneath
2. Minimum 2 pipe to d-box if gravity system 1
3. 20"access manhole
4. Tank level ... �' �°
S. Watertight
6. Tank size agrees with plan specification
7. Manhole to grade
8. Check valve and bleeder hole present
9. Alarm in building on separate circuit
10. Alarm functions
11. Manual operating switch
12. Pump delivers liquid to d-box
Comments:
F. Distribution Box
I. D-box level _y
2. Minimum 0.17"(2")drop from inlet to outlet
3. Minimum 6"sump
4. Outlet pipes show equal distribution
5. Compact base with 6"of stone beneath box
6. Box is watertight 1"/
7. All lines cemented with hydraulic cement V
8. Schedule 40 pipe
Comments:
G. Soil Absorption system
1. All stone double-washed-'/,"- 1 ''/z"
-pea stone
Bucket test done?
2. Minimum 2".of pea stone above distribution lines
3. Minimum 6"stone beneath pipe
4. Distribution lines capped or connected together
5. Grading meets 3:1 slope
6. Minimum of 9"of fill graded over system
7. Toe of slope stops minimum 5' from edge of property; if not,then swale.
Comments:
H. Leach Trenches
1. Minimum 2 trenches �.
2. Length of trenches agree with plan. (Max. length 100')
3. Width of trenches agree with plan-Minimum 2';maximum-4'.
4. Vent present if j 50 feet or specified ✓
5. Distance between trenches minimum 4' and maximum of 6'
6. Minimum distance between trenches 10' ✓
7. Pipe slope minimum 0.005 or 6"per 100' ✓`
8. Depth of trenches below outlet invert minimum of 6".
Yes NO
9. Pipes set on stable base.
Comments:
1. Leach Field
1. Maximum length of field 14"
2. Pipe slope minimum 0.005 or 6'11�er 100'
3. Separation between pipe 6'maximum
4. Pipes connected at end \
5. Separation between adjacent fields 10'`tninimum
6. Pipes set on stable base
7. Maximum 4' separation from edge of field to first line
8. Minimum two distribution lines
9. Maximum perc rate 20 mpi
Comments:
J. Leaching Pits
1. Minimum inlet pipe 4"
2. Pits of concrete
3. Sidewall between 12"and 48"wide
4. Access manholes on each pits,
5. Pipes cemented with hydraulic cement
Comments:
K. Final Grade
1. Slope over soil absorption system minimum 0.02 ✓' ,��. ��L�
2. All system components covered by at least 9"soil
3. Cover soil free of stones larger than 6" o
4. Grading slopes away from dwelling
5. No areas over system that may pond
AS-BUILT CHECKLIST
LOT NUMBER, STREET NAME
ASSESSORS MAP & PARCEL NUMBER
LOT LINES & LOCATION OF DWELLINGS
LOCATIONS &DIMENSIONS OF SYSTEM,
INCLUDING RESERVE
TIES TO LOT LINES & DWELLING, WELLS
a. FROM SEPTIC TANK
b. FROM LEACH AREA
LOCATIONS OF DEEP HOLES &PERC
TESTS
ELEVATIONS OF DISPOSAL SYSTEM
TOP OF FDN ELEVATION
LOCATIONS OF WELLS, DRAINS, WATERCOURSES
WITHIN 150' OF SYSTEM
LOCATION OF WATER, GAS, ELECTRIC LINES, CABLE
DISTANCES FROM CORNERS OF HOUSE TO CENTER OF
TANK& D-BOX
ORIGINAL STAMP & SIGNATURE
IMPERVIOUS AREAS - DRIVEWAYS, ETC.
NORTH ARROW
LOCATION & ELEVATIONS OF BENCHMARK USED