DESIGN APPROVAL FOR
'SSA�N�SES� SOIL ABSORPTION SEWAGE DISPOSAL SYSTEM
Applicant owdrw Test No.
Site Location wr 4
• Reference Plans and Specs.
/f _
ENGINEER DESIGN DA
Permission is granted for an individual soil absorption sewage disposal systerrf to be ins tilled
in accordance with regulations of Board of Health. "—,-A
CHAIRMAN,BOARD OF HEALTH
: Fee _ Site System Permit No. ��
CHRISTIANSEN SERGI, INC.
PROFESSIONAL [ENGINEERS AND I AND SURVEYORS
G;: ilh7FR STW((1 —A\lL9@°916..1_, MAS(0wP6l➢S='9°"'i C '] 131 (5 8). 7E 0310 AX: (508) 377.1960
TO : Ms . Sandra Starr
Board of Health
North Andover
RE : Septic System Design Plans
Ili,° /"` l,, n�r a✓, a
Date :
Attached are plans for
This design is
a new submittal
a revision with the following changes
SEPTIC PLAN SUBMITTALS
LOCATION: `O
NEW PLANS: YES $60.00/Plan
REVISED PLANS: YES $25.00/Plan
ATE: 1
DESIGN ENGINEER:
When the submission is all in place, route to the Health Secretary
SEPTIC PLAN SUBMITTALS
LOCATION: l)T " -.
NEW PLANS: YES $60.00/Plan
REVISED PL YE� $25.00/Plan
DATE: � � I
DESIGN ENGINEER:
When the submission is all in place, route to the Health Secretary
x "
NORTH ANDOVER BOARD OF HEALTH
DESIGN REVIEW REPORT
FEE PERMIT �_. DATE RECEIVED l r
y
APPLICANT �-�x�J�:�s !_s�rrr�s �s�, ;)d�./°� MAP PARCEL
ADDRESS LOT # 2� °°,
ENG. STREET - � `" i"""
ADDRESS
PLAN DATE REV. DATE
CONDITIONS OF APPROVAL
APPROVED DISAPPROVED
REASONS FOR DISAPPROVAL:
zo
/ � 1
- a
u
a
/ � l
Town of Nerllh A n to`or o 7M
/01 o �,y
OFFICE OF d_,- °
ya O� 1
CO �,I IU Y V Vi i C�r T a: D SERVICES O
t4
146 Main S ircf t �`-
i`Ior'di Andovri MassachuseUs 01845
WILLIAM J. SCOTT �sacHU51'
Director
October 1, 1996
Christiansen & Sergi
160 Summer Street
Haverhill, NfA 01830
Lots 7 & 8 Long Pasture
Dear Phil:
This is to inform you that the proposed plans for the site referenced above have been
disapproved for the following reasons:
1. Lot 7 -No peres.
2. Lot 8 - Inadequate and out of date peres.
3. No further review.
If you have any questions, please do not hesitate to call the Board of Health Office at the
number below.
Sincerely,
Sandra Starr, R.S.
Health Administrator
BOARD OF APPEALS 688-9541 BUILDING 688-9545 CONSERVATION 688-9530 HEALTH 688-9540 PLANNING 688-9535
CHRISTIANSEN G I, INC.
PROFESSIONAL ENGlNl.:k-RS AND LAND SURVEYORS
1,60 SUMMER STREET 1-1AVF E�W
.. w ....
�Ml..V.., KV1FlS`EAt`;HIESE:,TfS 01830 (•
TO; Ms . Sandra Starr
Board of Health
North Andover
RE : Septic System Design Plans
Date : -/
a
Attached are plans for
:✓ Cl
This design is ;
a new submittal
a revision with the following changes
CS I, INC.
PROFESSIONAL SIC'}NAL ENGINECRS AND LAND SURVEYORS
].GEC)SUNIPv1ER STREET I-IAWURHILL, MAS4iACk°gLNSE R'S 01.830 (�08)373.0310 FAX: (508) 372 3960
October 10, 1996
Ms . Sandra Starr
North Andover Board of Health
146 Main St . r
North Andover, MA 01845 ,
RE : Lots 7 and 8, Long Pasture
Dear Ms . Starr:
Thank you for your October 1, 1996 commends regarding
the septic systems designs for the above referenced lots . I
have the following responses to your reasons for denial .
There are two passing perc tests on Lot 7 . Perc tests
31 and 32 were performed on July 15, 1987 by Christiansen &
Sergi, Inc . The tests were witnessed by Health Agent Michael
Graf . The pert rates for both were recorded as less than 2
minutes per inch. Although the locations of the tests were
indicated on the plans that were submitted to you, the test
results were inadvertently left off . These test results have
been added to the plan.
When Soil Evaluator Daniel O' Connell performed the test
pits on this lot on May 23 , 1996 , he determined that the
location of the proposed leaching facility should be located
in an area on the lot closer to Forest Street from where the
perc tests were performed. For this reason, the proposed
leaching facility and reserve area are located from 40 to 50
feet from the locations of Perc tests 31 and 32 . The test
pit results indicated that the soils in this area are
consistent in that they have a very rapid permeability, and a
field assumption was made by you and Daniel O' Connell that
the perc rate would be less than 2 minutes per inch. It was
obvious that the perc rate of the soils would not be greater
than five minutes per inch, which is the fastest effluent
loading design rate listed in Title 5 . Since the 2 minutes
per inch rate requires a five foot vertical separation from
groundwater, the use of this rate for design purposes results
in additional protection of the groundwater.
There are two passing perc tests located on Lot 8 . Perc
test 1 and 2 were performed on June 22 , 1987 by Christiansen
& Sergi, Inc . The tests were witnessed by Health Agent
Michael Graf . The perc rates for both tests were recorded as
3 minutes per inch. When Soil Evaluator, Daniel O' Connell
performed test pits on this lot on May 23 , 1996, he
determined that the location of the proposed leaching
facility should be located further back onto the lot from
Starr, October 10, 1996
page 2
where the perc tests were performed. The test pits were dug
in locations that would minimize the amount of fill that
would be required between the proposed house and the leaching
facility. The configuration currently proposed would also
allow for the construction of the reserve area without the
necessity of a reinforced concrete retaining wall along
Forest 'Street, which would be required if the locations of
the leaching area and reserve area were shifted so that Perc
test 2 would lie within the reserve area. This could save
the future homeowners a substantial amount of money at a time
when they will already face severe economic hardship. i
Perc Test 1 lies within the proposed reserve area and is
approximately 30 feet from the proposed leaching field. Perc
Test 2 lies approximately 40 feet from the reserve area. The
test pit results indicated that the soils in this area are
consistent in that they have a very rapid permeability, and a
field assumption was made by you and Daniel O'Connell that
the perc rate would be less than 2 minutes per inch. It was
obvious that the perc rate of the soils would not be greater
than five minutes per inch, which is the fastest effluent
Loading design rate listed in Title ;5 . Since the 2 minutes
per inch rate requires a five foot vertical effluent
separation from the groundwater, the use of this rate for
design purposes results in additional protection of the
groundwater than if the ,previously measured rate of 3 minutes
per inch was used.
It should be noted that the septic system designs for
these two lots were completed before the recent decision by
the Board of Health to allow for a minimum design flow of 440
gallons per day for a single family home . Given that the
proposed leaching fields on the two lots consist of the
minimum size of 900 square feet of leaching area as required
by local regulations, the sizes of the fields cannot be
reduced. This being the case, the two septic systems would
be adequately sized for any percolation _rate ,up to and
including 20 minutes per inch. (440 gallons per day/0 .53
gallons per day per square foot = a required leaching area of
830 square feet) . Since it is clear from the soil
characteristics found in the test pits that it would not be
possible to obtain a percolation rate in excess of 20 minutes
per inch in a properly executed test, no further testing is
warranted. The factor of safety of 10 regarding the perc
rate and its effect on the size of the proposed leaching
area, coupled with the five foot vertical separation to
groundwater because of the 2 minutes per inch perc rate
assumption, will result in the construction of leaching
facilities that meet or exceed all state and local
requirements .
Starr, October 10, 1996
page ,3
Regarding you comment that the perc tests performed on
Lot 8 are "out of date" , we are unaware of any regulation
that would deem the perc tests to be expired. Although the
North Andover regulations state that "the Board of Health
representative may require the area previously tested to be
reperced if there is some question as to the results or
location of previous tests", the plans of record and soils
test results that were submitted to the Town of North Andover
with the Definitive Subdivision Plan and the Notice of Intent
in 1987, clearly document the locations and results of the
tests .
In summation, performing additional perc tests on these
two lots will have no effect on the designs of the septic
systems, will have no additional benefits towards the
protection of the public health, and would be a considerable
waste of time and/or money for the Board of health, the
engineer and the applicant .
The owner of this property negotiated in good faith with
the Town of ,North Andover to settle litigation. It was
expected that use of old percolation tests would not be a
problem. You and Daniel O'Connell also did new ,test pits on
this property in 1996 to complement testing done in 1987 and
1991 . A final day of perc testing is scheduled for October
17, 1996 .
I hope the testing can be resolved on October 17, 1996
so that the design work can proceed.
Please contact me if you have questions or comments
regarding this matter.
Very truly yours-
Phi 'p G. Christiansen
PGC;lc
cc : William Scott
Ralph Joyce
Ren Crete
PROF"ESSIONAL ENUNEERS AND LAND SURVEYORS
7.60 S4.IMMEwR DIREL`l" HAVEaFOUL, MA`ESC';Hl.dSE.G.1°;0130 (50E0373-0310 FAk (508)3
November 6, 1996
Ms. Sandra Starr ,
North Andover Board of Health
1.46 Main Street
North.Andover MA 0184.5
Re: Lots 7 and 8 Long Pasture
Dear Ms. Starr:
Thank you for your recent comments on the septic system designs for the alcove
referenced locations. I have the following responses to your reasons for disapproval:
1. The results and locations of the pert tests that were performed on 10/17/96 have
been added to the plans.
2. The proposed leaching facilties have been changed from fields to trenches.
Enclosed are three sets of the revised plans for your review. Please contact me if
you have any questions regarding these designs.
j*Iu sen .
SEPTIC PLAN SUBMITTALS
LOCATION:
NEW PLANS: YES $60.00/Plan
REVISED PLAN YES $25.00/Plan N(--
DATE:
DESIGN ENGINEER:
When the submission is all in place, route to the Health Secretary
SEPTIC PLAN SUBMITTALS
LOCATION:
NEW PLANS: YES
$60.00/Plan
REVISED PLANS: ` S
$25.00/Plan
DATE: '3— jr) -0't
DESIGN ENGINEER:
When the submission is all in place, route to the Health Secretary
PLAN REVIEW CHECKLIST"
ADDRESS—,/, 7 ENGINEER s.w ..
—GENERAL
3 COPIES !,,,�-,� STAMP G.,,, LOCUS f ..., .... . ......
NORTH ARROW SCALE--
CONTOURS «.�,'" PROFILE t °"
SECTION BENCHMARK - ' SOIL &
WETS. DISCLAIMER WELLS & WETS _
PERCS ELEVATIONS
WATERSHED?
DRIVEWAY (Elev) WATER LINES"" FDN DRAIN '
SOIL EVAL J.,
SCH40 �°�� TESTS CURRENT? +�.�"��- 7 �'7 �c���A)l��.-
SEPTIC TANK
MIN 15006 & � . 17 INVERT DROP ` GARB. GRINDER D (2 comps +200)
10 ' TO FDN �"-'°" MANHOLEI.� „, ELEV ` GW c..,-"° # COMPS . GB
R-BOX
SIZE # LINES FIRST 2 ' LEVEL STATEMENT
INLET �.a .” � OUTLETS`� /w = . (2" OR . 17 FT) TEE REQ'D? �+�)
LEACHING
MIN 440 GPD? '"` RESERVE AREA 4 ' FROM PRIMARY? Ay2 a ..LOPE;
100 ' TO WETLANDS 100 ' TO WELLS '"" 4 ' TO S .H.GW
20 ' TO FND & INTRCPTR DRAINS 400 ' TO SURFACE H2O SUPP
4 ' PERM. SOIL BELOW FACILITY MIN 1211 COVER '""" FILL?
BREAKOUT MET? °
TRENCHES
MIN 440 gpd SLOPE (min . 005 or 6 11/100 ' ) SIDEWALL DIST. 3X EFF.
WORD (MINE ' ) RESERVE BETWEEN TRENCHES? " " IN FILL? MUST
t� "
BE 10 ' MIN. lO 4" PEA STONE? .""VENT? (>3 ' COVER; LINES >501 )
BOT _ + SIDE DxLx2x X LDNG(G%t2)' TOT `
r
(L x W x #) ( #)
Copyright d 1996 by S.L. Starr / '
PITS
MIN 440 LEACHING— MIN I (13 'x16 ' ) PIT— MANHOLE/PIT_
GW MIN 4 ' BELOW BOTTOM— EXC 2x EFF W OR D— 12"-48" STONE_
BOT + SIDE x LOAD 7f— = TOTAL
x W x #) (L+W)xD x TG/ t2)
—M AMBERS
MIN 440 LEACHING— GW MIN 4" BELOW— COVER >3 FT ® VENT_
MANHOLES— 1211-48" STONE— SPLASH PADS— SLOPE . 005
BED/TRENCH_(Bed max. 60 ' X 601 ) MIN 131 X 161 PIT_
BOT + SIDE— X LOAD—= TOTAL
(L x W x #) (2 x (L+W)xD x #) (G/ft2)
FIELDS
MIN 440 GPD 900 ft2 BED GW MIN 4 ' BELOW BOTTOM OF FIELD
PIPE ENDS JOINED?
411 PEA STONE? 6-- DIST LINE SLOPE .005?
>3 COVER-VENT SCH 40 MIN 1211 COVER
RATE , X TOTAL
X
L ')W LDG
DOSING TANKS AND PUMPS
DIMENSIONS X X PUMP CAPACITY gpm
—W D –Vol .
DISCHARGE SIZE DISCHARGE RATE DISCHARGE TIME
gpi'a
MANHOLES TO GRADE ALARM SEP. CIRC. GW_(Min. 11 below
inlet) HWL— LWL CHECK VALVE BLEEDER HOLE MANUAL
OP. SWITCH— ENUF STORAGE?— TDH WEIGHTED?_
Copyright 0 1996 by S.L. Starr
Town of North Andover LL4,1
OFFICE OF C® ITT DEVEL®P' ENT SERVICES
30 School Street North Andover,Massachusetts 01845
WILLIAM J. SCOTT
Director
May 28, 1997
Ms. Robin Barclay
425 Forest Street
North Andover, MA 01845
Dear Ms. Barclay:
As an update on the status of Long Pasture Subdivision, please be advised that the
following lots have approved septic plans: Lot#1A, Lot#7, and Lot #8.
If you have any questions, please do not hesitate to call the Board of Health Office at the
number below.
Sincerely,
Sandra Starr, R.S.,
Health Administrator
SS/cjp