HomeMy WebLinkAboutMiscellaneous - 545 JOHNSON STREET 7/30/2010 SUBSURFACE SEWAGE
DISPOSAL SYSTEM LEA RECEIVED
PUMP SIGN
545 Johnson Street r North Andover MA A M
(Tax Map 98.A Block 13 Lot 0)
OWNER: Frank Peluso
545 Johnson Street
North Andover MA
f JAn/IE: E� °N C
DATE: 7/30/2010
Scanlan Engineering LLC #0321
P.O.BOX 906 GEORGETOWN, MA 01833
978-372-3440
545 Johnson Street Frank Peluso
North Andover MA 545 Johnson Street
(Tax Map 98.A Block 13 Lot 0) North Andover MA
7/30/2010
PUMP CALCULATIONS:
DAILY FLOW: 330 GALLONS/DAY
SOIL PERC RATE: 10 MIN/IN
SOIL TYPE: CLASS II 4 DOSES/DAY
VOLUME/DOSE: DOSE 82.5 GALLONS
PIPE 12.9 GALLONS
TOTAL 95.4 GALLONS/DAY
FORCE MAIN: 2 DIA.
C-VALUE: 140
PUMP CHAMBER: (INSIDE DIMENTIONS) 1000 GALLON MONO TANK
LENGTH 8.83 FT
WIDTH 4.17 FT
EFF. DEPTH 4.00 FT
PUMP CHAMBER INLET 96.93
SUMP 92.93
OFF 93.43
ON 93.80
ALARM 94.30
STATIC HEAD: 93.43 PUMP OFF
100.74 DBOX
Hs 7.31 FEET
EQUIVALENT LENGTH: (2" SCH-40 PVC PIPE)
PUMP CHAMBER 1 90 DEGREE BENDS 5 FT
1 GATE VALVE 1.2 FT
1 CHECK VALVE 14 FT
TOTAL 20.2 FT
USE: 21 FT
PIPE RUN 1 90 DEDGREE BENDS 5 FT
2 45 DEGREE BENDS 5 FT
1 TEE 12 FT
LENGTH OF PIPE 79 FT
ADDITIONAL LENGTH 8 FT
TOTAL 109 FT
USE 109 FT
TOTAL EQUIVALENT LENGTH 130 FT
545 Johnson Street Frank Peluso
North Andover MA 545 Johnson Street
(Tax Map 98.A Block 13 Lot 0) North Andover MA
7/30/2010
SYSTEM CURVE:
Q V Hf/100 FT Hf Hs TDH
GPM FT/SEC FT/100FT FT FT FT
50 4.51 3.96 5.15 7.31 12.46
52.5 4.73 4.34 5.64 7.31 12.95
55 4.96 4.73 6.14 7.31 13.45
57.5 5.19 5.13 6.67 7.31 13.98
60 5.41 5.55 7.22 7.31 14.53
62.5 5.64 5.99 7.78 7.31 15.09
65 5.86 6.44 8.37 7.31 15.68
PUMP SPECIFICATIONS:
MANUFACTURER BARNES PUMPS
MODEL# SE411
HP 0.4
VOLT 115
PHASE 1
RPM 1750
DISCHARGE 2 INCH
IMPELLER DIAMETER 5.44 INCH
OPERATING POINT:
HEAD 15.6 FT
FLOW RATE 65 GPM
TIME ON 1.5 MINUTES
Series S
Performance Curve
www.cranepumps.com AHP, 1750RPM, 60Hz
?2", 2"& 3" Discharge
� inches
TOTAL HEAD (mm)
METERS FEET
9 30
- -.- _--_- -- - -- - -= STANDARD IMPELLER SIZES
- -- - - -- -
_ Pump HP Impeller Dia
- - - ----- - -- - -- - -- ''- - --- - 0.4 5.44(138)
-5.44(138) -- - --- •-- - —-------
25
7 r47 30) --- -
1) -�_20 4}. 8) _
-- - - -
+ - 15
t } ...
2 - -- -- -
5 -- --
- - - ----- V9674
U.S.GALLONS 25 50 i 75 100 125 150
PER MINUTE
LITERS 7 8 9
PER SECOND 1 2 3 4 5 6
Testing is performed with water,specific gravity 1.0 @ 68°F 4(20°C),other fluids may vary performance
CRANE SAGE 3
PUMPS & SYSTEMS PAGE �
DATE 6104
A Crane Co.Company USA:(937)778-8947 - Canada: (905)457-6223 • International: (937)615-3598
Series SE
2" Spherical Solids Handling
www.cranepumps.com Manual &Automatic
1%", 2" & 3" Discharge
DISCHARGE .......................2" NPT, Female,Vertical
LIQUID TEMPERATURE
SE411 ...........77°F(25°C) Continuous
SE421 ...........104°F(40°C)Continuous
VOLUTE...............................Cast Iron ASTM A-48, Class 30
MOTOR HOUSING..............Cast Iron ASTM A-48, Class 30
SEAL PLATE ......................Cast Iron ASTM A-48, Class 30
IMPELLER:
Design.............2 Vane, Open with pump out vanes on back
side, Dynamically Balanced, ISO G6.3
Material ..........Cast Iron ASTM A-48, Class 30
SHAFT ., ........................416 Stainless Steel
SQUARE RINGS .................Buna-N
i HARDWARE........................300 Series Stainless Steel
PAINT...................................Air Dry Enamel
SEAL: Design ............Single Mechanical, Oil Filled Reservoir,
Secondary Exclusion Seal
Material...........Carbon/CeramicBuna-N o 0
Hardware-300 Series Stainless
CORD ENTRY......................15 ft. (5m) Quick Disconnect Cord with plug
On 115Volt, Pressure Gromment for sealing
and strain relief
SPEED.................................1750 RPM (Nominal)
UPPER BEARING................Single Row, Ball; Oil Lubricated
Load................Radial
LOWER BEARING...............Single Row: Ball, Oil Lubricated Series: SE (SE411 & SE421)
Load................Radial&Thrust 4HP 1750RPM 60Hz
MOTOR: Design ............NEIvIA L Torque Curve, Oil Filled, Squirrel
Cage Induction
Insulation........Class B
SINGLE PHASE...................Permanent Split Capacitor(PSC)
Includes Overload Protection in Motor
LEVEL CONTROL..............."A" -Wide Angle, PVC, Mechanical, 15 ft(5m)
cord with Piggy-Back Plug, N/O
"VF"-Vertical Float, PVC, Snap Action,
15 ft(5m)cord,with Piggy-Back plug. MW
OFF point ONLY is adjustable
OPTIONAL EQUIPMENT.....Seal Material,Additional Cord
C " us
CSA 108
UL 778
6 LR16567
Sample Specifications:Section 1 Page 3.
DESCRIPTION:
SUBMERSIBLE NON-CLOG SEWAGE PUMP
DESIGNED FOR TYPICAL RAW SEWAGE
APPLICATIONS
a
CRAM E PUMPS & SYSTEMS PAGE SECTION 1B
DATE 12107
A Crane Co. Company USA: (937) 778-8947 • Canada: (905) 457-6223 International: (937) 615-3598
Series
2" Spherical Solids Handling -
Manual &Automatic www.cranepumps.com
9%", 2" & 3" Discharge
SE411VF SE411 & SE421 (Less Float) Inches
SE411 A (mm)
10.75 10.75
(273) 5.32 _ �j�1.56 (273) �-_5.32 f1.56
t- ---(135) I (40) (135) (40)
i o i 1 ' o 1 i 1 1
1
i
(197) t - I (197)
0
t p
16.76 I 116.76
(426) � 1(426)
8.75
( (222)
y 5.00; 5.00
1 (127) (127) i
STOPSTABLE ('0)
MODEL NO PART NO HP VOLT/PH Hz RPM NEMA FULL LOCKED CORD CORD CORD
(Nom) START LOAD ROTOR SIZE TYPE O.D
CODE AMPS AMPS inch (mm)
SE411 096747 0.4 115/1 60 1750 C 12.0 19.0 14/3 SJTOW 0.375(9.5)
SE411A 096748 0.4 115/1 60 1750 C 12.0 19.0 14/3 SJTOW 0.375(9.5)
SE411VF 100836 0.4 11511 60 1 1750 C 12.0 1 19.0 14/3 SJTOW 0.375(9.5)
SE421 096750 0.4 23011 60 1 1750 C 6.2 13.0 14/3 1 SJTOW 0.375(9.5)
Mechanical Switch on SE-A;cord 16/2,SJOW.Piggy-Back Plug
Vertical Switch on SE-VF,cord 16/2,SJOVV,0.320(8.1 mm)O.D.Piggy-Back Plug
IMPORTANT I
1.) PUMP MAY BE OPERATED"DRY FOR EXTENDED PERIODS WTHOUT DAMAGE TO MOTOR AND/OR SEALS.
2.) THIS PUMP IS APPROPRIATE FOR THOSE APPLICATIONS SPECIFIED AS CLASS I DIVISION II HAZARDOUS LOCATIONS.
3.) THIS PUMP IS NOT APPROPRIATE FOR THOSE APPLICATIONS SPECIFIED AS CLASS I DIVISION I HAZARDOUS LOCATIONS.
4.) INSTALLATIONS SUCH AS DECORATIVE FOUNTAINS OR WATER FEATURES PROVIDED FOR VISUAL ENJOYMENT MUST BE INSTALLED IN ACCORDANCE
WITH THE NATIONAL ELECTRIC CODE ANSI/NFPA 70 AND/OR THE AUTHORITY HAVING JURISDICTION.THIS PUMP IS NOT INTENDED FOR USE IN
SWIMMING POOLS,RECREATIONAL WATER PARKS.OR INSTALLATIONS IN WHICH HUMAN CONTACT VVITH PUMPED MEDIA 15 A COMMON OCCURRENCE.
SECTION 1B
PAGE 2 CRANE PUMPS & SYSTEMS
DATE 12/07
A Crane Co. Company USA: (937) 778-8947 • Canada: (905)457-6223 • International: (937)615-3598
545 Johnson Street Frank Peluso
North Andover MA 545 Johnson Street
(Tax Map 98.A Block 13 Lot 0) North Andover MA
7/30/2010
BUOYANCY CALCULATIONS:
STRUCTURE: 1500 GALLON MONOLITHIC
2-COMPARTMENT SEPIC TANK
DIMENSIONS: (OUTSIDE)
LENGTH 11.00 FT
WIDTH 5.83 FT
HEIGHT 5.83 FT
INVERT-BOTTOM 4.58 FT
WEIGHT: 13320 LBS
MANHOLE DIAMETER 2 FT
# MANHOLES 3
FOOTPRINT 64.1 SF
ELEVATIONS:
FINISH GRADE 99.60
MANHOLE GRADE 99.60
ESHGW 96.90
INLET INVERT 97.20
TOP 98.45
BOTTOM 92.62
SOILS INFORMATION:
UNIT WEIGHT OF SOIL 115 LB/CUBIC FT
WEIGHT OF SOIL* 7235 LBS
FORCES:
BALLAST WEIGHT 0 LBS
WEIGHT OF SOILS 7235 LBS
WEIGHT OF TANK 13320 LBS
WEIGHT OF DISPLACED WATER 17127 LBS
NET FORCES**: 3428 LBS (NEGATIVE INDICATES FLOATATION)
FACTOR OF SAFETY: 1.20
*Neglect weight of soil over ballast.
**Station assumed totally dry inside.Neglect weight of equipment inside and outside soil friction force.
545 Johnson Street Frank Peluso
North Andover MA 545 Johnson Street
(Tax Map 98.A Block 13 Lot 0) North Andover MA
7/30/2010
BUOYANCY CALCULATIONS:
STRUCTURE: 1000 GALLON MONOLITHIC
PUMP CHAMBER
DIMENSIONS: (OUTSIDE)
LENGTH 9.67 FT
WIDTH 5.00 FT
HEIGHT 5.83 FT
INVERT-BOTTOM 4.67 FT
WEIGHT: 14825 LBS
MANHOLE DIAMETER 2 FT
#MANHOLES 1
FOOTPRINT 48.4 SF
ELEVATIONS:
FINISH GRADE 99.50
MANHOLE GRADE 99.50
ESHGW 96.90
INLET INVERT 96.93
TOP 98.09
BOTTOM 92.26
SOILS INFORMATION:
UNIT WEIGHT OF SOIL 115 LB/CUBIC FT
WEIGHT OF SOIL* 7331 LBS
FORCES:
BALLAST WEIGHT 0 LBS
WEIGHT OF SOILS 7331 LBS
WEIGHT OF TANK 14825 LBS
WEIGHT OF DISPLACED WATER 13999 LBS
NET FORCES"`: 8157 LBS (NEGATIVE INDICATES FLOATATION)
FACTOR OF SAFETY: 1.58
*Neglect weight of soil over ballast.
**Station assumed totally dry inside. Neglect weight of equipment inside and outside soil friction force.