FIRE DEPARTMENT
NORTH ANDOVEVA
e ; jj „ (, N,r, AL F'H�iE 1-1EAD� QUAL T R
t g f 1. 6" 686--3812
WH-LIAM V. DOk ADAM
C,°N"!01 leaf-,Jal tfnmO ��t
To: Town Planner
From: Fire Chief Dolan
RE: Site Plan Review - Flagship Drive- Chanel Bldg.
Date: 13 July 1987
I have the following comments regarding this proposed
building.
1) An automatic detection and suppression system must
be installed. These systems must be connected to the
municipal fire alarm system through a master fire alarm
box. The developer must contact the fire chief for
the requirements for these systems prior to installation.
2) Material Safety Data sheets must be submitted to the
fire department prior to occupancy.
3) Permits will be required for all flammable storage
according to M. G.L. Chap. 148 and all flammable storage
shall be in accordance with N.F.P.A. 30 .
4) Welding operations must be in accordance with N.F.P.A. 51B
5) The Paint Shop, in particular the spray booth area must
be in accordance with N.F.P.A. 33 .
6) The intended purpose for the gas ovens should be given
to the fire department and the intended fuel to be used
so stated.
7) An additional fire hydrant is needed at the west corner
of the building.
8) A 360° fire department access must be maintained especially
after the proposed expansion takes place.
9) The wire mesh between the stock room, carpenter shop and
the drive bay is unacceptable. A safer redesign of
this area is needed.
10) Underground storage of fuel tanks will be in compliance
with fire department regulations and no permits will be
isssued if the conservation commision finds the lot unsuitable
for such tanks.
11) No open burning is permited except in compliance with the
fire department' s regulatios during open burning season.
Due to the special operations, welding,paint spray etc. this
dI .., 4 ' c� 4 X l P
&SWO �9 (" .) 0.)
Flagship Drive-Chanel Bldg. Page 2
building, and its safety are of prime interest to the
fire department. As always we are willing to work with the
developer to insure that safety in the final finished building.
I plan to be at the July 20th meeting of the Planning Board.
William V. Dolan
Fire Chief