To: Scott Stocking, Town Planner
From: Fire Chief Dolan
Red Stevens Memorial Library Addition
Dates October 2 , 1987
As presented at the discussion of the Development Committee
regarding the proposed addition to Stevens Memorial Library,
I have the following comments :
The Fire suppression and detection systems throughout the
building must be updated to include a fire suppression system
for at least the addition and the detections system, composed
of smoke and heat detectors, connected to the Municipal Fire
Alarm System through a master fire alarm box.
The issue of parking and the closing of Middlesex Street
from Main Street and Green Street would not create a lack of
access for the Fire Department if this area was maintained
as a parking lot.
The proposal submitted by Officer Rand and the architect which
would provide that parking area is agreeable to us.
I would submit specifics to Fire Department requirements at the
time of site plan review.
William V. Dolan, Fire Chief
�u
,, �raWa e pa a°m`u�o
p
� H ANDOVER � a� IPA ENu
-IRE 1'4EADQLJAF1'rERS
CENTRAL. F'
r�us
,r s
s! 01845
Tel. (617) 686-3812
,
Chief of l7r",p arPrrwn
r
rj `„ J
A �
ar fa I
Tod Scott Stocking, Town Planner
From: Chief Dolan
Re: Parking-Proposed Library Addition
Date : October 16, 1987
I have reviewed the plans delivered to me on October 15 , 1987
which show twenty parking spaces behind the proposed library
addition.
This causes no problem for Fire Department access and meets
with my approval.
r
S '4�' &'41,.
Q William V. Dolan, Fire Chief
"SMOKE DE"TECT01"IS SAVE UVE'("5'”
Fd" �� ��
�
-1 ANDOVER FIRE DEPARTMEN'll'
CENTRAL FIRE I-4E DQ ART"ERS
,,. 24 Mair� Sh sit
AC10 a ire w CN 01845
W11J_1ANA V, DOL-AN Tel. (617) 686-3812
G'hief of LJeR:ra(bnent
To: Mr. Scott Stocking, Town Planner
From: Fire Chief Dolan
RE: Site Plan Review- Stevens Memorial Library
Date: 9 November 1987
I have reviewed the plan date 10/23/87 by Amsler-Hagenah
MacLean Architects, Inc. and have the following comments :
1 . As I stated in my letter of 16 October there is
adequate fire access provided by this plan.
2 . An automatic fire detection system will be required
which shall consist of double action pull stations ,
heat and smoke detectors, horn lights, an outside
annunciator panel and fire alarm control panel. This
system shall be connected to the municipal fire alarm
system through a master fire alarm box. Plans for
this system shall be submitted to the Fire Chief for
approval prior to installation.
3 . A fire suppression system, sprinklers, shall be in-
stalled in accordance with M.G.L. Chap 148 sec 26 G.
Plans for this system shall be submitted to the Fire
Chief for approval prior to installation,
4 . All underground fuel storage shall be in compliance with
North Andover Fire Department requirements .
5. A secured key access box must be installed and located
at a site approved by the fire department.
I intend to be at the November 23rd meeting of your board.
f�
William V. Dolan
Fire Chief