To: No. Andover Planning Board
From: Fire Chief Dolan
Re: Site Plan Review - Merrimack Valley Credit Union
Date: October 7, 1985
I have reviewed the site plan for the proposed Merrimack Valley
Credit Union building and I have the following comments and
recommendations:
1. There is a need for fire hydrants on the site since the
nearest hydrant is on the right of way, 50 ' from Osgood
Street.
2. In accordance with MGL Chapter 148 Sec. 26G, the bulding
must have a full sprinkler system with a fire department
connection and both a mechanical water motor gong and
electric bell when water flows. Plans for the design of
the system must be submitted to the Fire Chief for approval.
3. The building must have a fire detection and alerting system
to include, but not limited to, double action pull stations,
audible and visual warning devices, smoke and heat detectors,
an annunciator panel and a central panel with battery back up
and a sprinkler flow switch. Plans must be submitted to
the Fire Chief for approval.
4. Both systems for detection and suppression must be connected
to the municipal alarm system in accordance with fire depart-
ment procedures.
5. The owners should contact the Fire Chief for any special fire
protection needs, ie. computer rooms or equipment.
6 . A fire lane must be located from the handicap ramp to the
far right corner of the building on the Osgood Street side.
The lane will be painted by striping and letter the words
"Fire Lane No Parking" .
T '7 1985
"
SMOII E DETECTORS SAVE LJVES 4
2.
7. No temporary occupancy permits should be issued until all
requirements have been met.
8. At least a binder coat of hot top shall be placed on all
areas to be used by motor vehicles prior to occupancy.
9. If underground fuel storage is needed, the storage must
comply with Fire Department regulations.