INTEROFFICE MEMORANDUM
TO: Curt Bellavance DATE: July 24, 2014
Community Development Director
FROM: Ray Santilli
Assistant Town Manager
SUBJ: Site flan Review—New Central Fire Station
As a follow-up to the Planning Board's public hearing for a Site Plan Review for the
construction of a new Central Fire Station at 795 Chickering Road,the following information is
provided:
• Enforcement of no parking on Prescott Street will be provided by the North Andover
Police Department at the beginning of construction and when the building is
operational. This will be imperative in order to provide access of construction
vehicles to the site during construction and, more importantly,to allow the fire trucks
to safely return to the premises once the building is operational.
o I have spoken to the property owner (Mr. Zahouriko) on the east side of the property.
He understands that we do not have the space for any plantings on the fire station side
of the property line so he is going to add screening on his side of the property line.
• The dumpster will remain as on the original plans in the corner on the east side. If the
dumpster was to be moved to the south side of the corner, this would hinder snow to
be pushed into that corner until removal is possible. I spoke to Mr. Zahouriko about
this issue and he understands and accepts why it needs to be left in its original
location.
TOWN OF NORTH ANDOVER
DIVISION OF PUBLIC WORK'S
384 ()SG00D STRE'F'T
NC)RITI ANDOVER, MASSACI-It)SETTS 0 1845-2909
BRUCE' RTI 11110I)EIAU, PE.
Lugene 11, Willis, PE Telephow (978) 085-09,50
Direclor ol'Erigineen,ng Fow (9 78 M8 95 73
August 1, 2014
Curt Bellavance, Director Community development
North Andover Planning Dept.
Osgood Landing
Re: Prescott St. Fire Station site plan review (4)
1 have received Polaris Consultants LLC response to my review
comments dated July 30, 2014. My comments have been addressed
adequately.
Si re
2
-2
Eugene P. Willis PE
Director of Engineering
Cc: file, Chris Logan, Bruce Thibodeau,,Ray Santilli
TOWN OF NORTH ANDOVER
DIVISION OF PUB.I.AC WORKS
384 OSCi( OD STR1;1?T
NORTH ANDOVER, MASSAC:1-11)SI;`ITS 01845-2909
BRUCE D. THIBODFAU, PE
DIRECTOR
Eugene P. fflillis, FZ �, � Telephone (978) 685-0950
Direc°lor of'En neer•ing Far (97,.t) 688-957:3
July 15, 2014
Curt Bellavance, Director Community development
North Andover Planning Dept..
Osgood Landing
Re: Prescott St. Fire Station site plan review (3)
1 have received revised plans dated July 3, 2014; 1 offer the following
comments/suggestions:
1 . The plan legend as shown is incomplete.
2. Does the proposed new hydrant's proximity to the electric transformer
create a potential safety concern?
3. For cost savings, would a Siamese connection at the building be sufficient
for fire protection rather than the proposed, free standing hydrant as
shown on the east lot line?
4. There does not appear to be sufficient cover over drain line from north CB
to WQI-3. Labelling obscures elevations on other structures. Cover
should be verified for all drain lines.
5. For cost savings, are catch basins necessary at the WQI manholes?
6. Would it be possible to change the drain manhole type at WQl-1 , 2, & 3 to
a deep sump manhole with an inlet frame and grate creating points that
the parking areas drain to? Would setting these frames' elevation to a low
point below elevation 164 allow for the elimination of proposed catch
basins and shallow pipes?
7. Create a low point in grass ring paver area that drains pavement and
relocate WQl 1 with sump and inlet frame and grate to this area.
8. The proposed sewer as shown on profile is a 4" diameter; the sewer dept.
requires it to be 6". The profile labelling should be changed. The sewer
service connection detail shown on sheet C7.0 is correct.
Page 2
07/18/14
9. Are any stormceptors or an equal being proposed for removal of total
suspended solids? The Town does not have personnel to maintain these.
10. The invert for the proposed 36" RCP under the Rte. 125 driveway is
not shown. What is the depth of cover and loading on the pipe?
11 . Add to General Notes Miscellaneous #4 Sheet C 6.0— "the electronic
version of the as-built drawing shall be on state plane coordinate in
compliance with MASSGIS standards."
The design engineer may contact me directly if he would like to do so.
Cc: file, Bruce Thibodeau, Ray Santilli
TOMIN OF NORTI I ANDOVEIR
DIVISION OF 1"11 J13 IA(I/' WORKS
1 -2909
384 OSGOOD STREE7NORT11 AN DOVER, MASSA(IMS1.'41"S 0 1845
�
POLARIS
Consultants,','', LLC
34 Main Street,Suite 2O1
Plymouth,K4ADZ3GO
Phone:617-689-1010
Fax:617-689-3010
July 9O, 20I4
Eugene P. Willis, P.E
Director oIEngineering
Town nf North Andover
384 Osgood Street
North Andover, M/\ OlQ45
BE: Fire Station—North Andover, Momommbuaeitm
Site Plan Review Comment Response
Dear Mr. Willis:
At the request of our client, Donham & Sweeney Architects, we are writing this letter to respond
k» your North Andover Fire Station site plan review comments dated July }5' 2O)4.
Our proposed oonmm000| responses are an follows and are in the same order as they were
provided in your letter:
%. The Revised Site Plan drawings have updated legend,
2. The proposed transformer in 10 feet from the proposed hydrant will be protected by
bollards. We do not anticipate a safety concern.
9. The DJozib Andover Iqn: Department (0AID) has requested u free standing hydrant.
The plans have been revised io have uoB-iuobDICl.water pipe,stemming to two 6-incb
DXCLpipes (one to the hydrant and n mc000d to the building for potable water and fire
protection).
4. We have revised the grading the in the visitors parking lot to provide for 15-iocbes of
cover over the 8-inch SI)Il17 drain pipe.
5. Based on m negative Qegount for Determination of Applicability (RD/\) from the
Conservation Commission, water quality inlets (W()l) are not required. Standard drain
nmumbo|en to provide additional auroy volume and oil water separation are proposed.
6. Based on n negative RDA' WOIo are not required. The invert elevations of the pipes
now entering standard drain o)uoholco are dictated by the elevations of the infiltration
areas and the ucnd to ak>ue the lOO'ysar storm volume. The elevations are also dictated
Willis Eugene
July 30,2014
Page 2o[2
by the shallow 0pnoodwutnr at the Site, the groundwater relation to the bottom of the
infiltration areas, and the need for minimum pipe slopes. We have divide the small I-
acre site into four distinct proposed drainage areas and we can make minor adjustments
10 the proposed grading (as indicated in the visitors parking amoo) but it we need to
increase the pipe cover oiAoifiomoUy, it would ozguimo bringing in additional fill and
raising the Site. In lieu of bringing in fill, we have used a 1/2-inch thick walled pipe that
io rated for lOO pounds per square inch.
7, lA/e have relocated DD0H-I to the grass paver area amrequested.
Q. The proposed sewer line label on Sheet C4.0D has been changed bm6 inches.
9. Based on a oogudvc RDA, we do not need to remove Total Suspended Solids (T8S) to
meet the more stringent Massachusetts SLoromwu0or Management Policy. Standard drain
manholes will be used to provide additional sump capacity for TSS removal.
10. At the request of Eggleston Environmental the 36-iuub diameter pipe has been changed
0m u llQ-fbut-long, 3-font by 2-foot box culvert in order to better mimic the geometry of
the eximdVgmwva6n. The invert elevation ioimEl. 158.6 and the invert out ioEl. 157.32.
The pipe has a slope ofl.l796 and will be H-20 rated.
11. The general note for the digital as-built submittal has been added toSheet 6.0.
We appreciate the opportunity to work with you on this project, and should you have any
questions,please dn not hesitate in contact nmcut 617-750-0135.
Very Truly Yours,
Paul [}. Costello, P.D.
Principal-In-Charge
Cc CudBo|lmvuoce, North Andover Community Development
Brett[)onhmnm, Doohumm and Sweeney Architects
Chris Logan, Donhnnn and Sweeney Architects
TOWN OF NORTH ANDOVER
DIVISI+C)I' OF PUBLIC WORKS
384 OSGOOD STREET
NORTH ANDOVER, MASSACHUSETTS 01845-2909
BRU(",J:;D. Tf fIBODE3AU, P.E.
DIRECTOR
Eugene P 0711is PE' Telephone (978) 685-0950
Director rfTrgireer irg Fa. (97<�) 688-957-3
July 15, 2014
Curt Bellavance, Director Community development
North Andover Planning Dept.
Osgood Landing
Re: Prescott St. Fire Station site plan review (3)
1 have received revised plans dated July 3, 2014; 1 offer the following
comments/suggestions:
1 . The plan legend as shown is incomplete.
2. Does the proposed new hydrant's proximity to the electric transformer
create a potential safety concern?
3. For cost savings, would a Siamese connection at the building be sufficient
for fire protection rather than the proposed, free standing hydrant as
shown on the east lot line?
4. There does not appear to be sufficient cover over drain line from north CB
to WQI-3. Labelling obscures elevations on other structures. Cover
should be verified for all drain lines.
5. For cost savings, are catch basins necessary at the WQI manholes?
6. Would it be possible to change the drain manhole type at WQI-1, 2, & 3 to
a deep sump manhole with an inlet frame and grate creating points that
the parking areas drain to? Would setting these frames' elevation to a low
point below elevation 164 allow for the elimination of proposed catch
basins and shallow pipes?
7. Create a low point in grass ring paver area that drains pavement and
relocate WQI 1 with sump and inlet frame and grate to this area.
8. The proposed sewer as shown on profile is a 4" diameter; the sewer dept.
requires it to be 6". The profile labelling should be changed. The sewer
service connection detail shown on sheet C7.0 is correct.
Page 2
07/18/14
9. Are any stormceptors or an equal being proposed for removal of total
suspended solids? The Town does not have personnel to maintain these.
10. The invert for the proposed 36" RCP under the Rte. 125 driveway is
not shown. What is the depth of cover and loading on the pipe?
11 . Add to General Notes Miscellaneous #4 Sheet C 6.0— "the electronic
version of the as-built drawing shall be on state plane coordinate in
compliance with MASSGIS standards."
The design engineer may contact me directly if he would like to do so.
Cc: file, Bruce Thibodeau, Ray Santilli
'TOWN OF NORTI I ANDOVER
DIVISION OF PUBLIC WORKS
384 OSGOOD STRE"ETNORTH ANDOVER, MASSACHUSETT'S 01 845-2909
•
CONSERVATION DEPARTMENT
Community Development Division
MEMORANDUM
DATE: June 30,2014
TO: Planning Board
John Simons, Chairman
FROM: Jennifer Hughes, Conservation Administrator
On behalf of the North Andover Conservation Cominission(NACC)
CC: Ray Santilli, Assistant Town Manager
Curt Bellavance,Community Development Director
Louis Napoli, Chairman NACC
SUBJECT: Fire Station,Comer of Chickering Road and Prescott Streets
Prior to the Planning Board hearing on the Chickering Road/Prescott Street Fire Station, I wanted to
update you on the requirements of the NACC regarding the site. On several other development projects
(West Mill, Brooks School), applicants have been required to file at least an RDA when they have
proposed changes to existing drainage that outlets to or that could potentially alter a wetland resource
area. To be consistent, the town's proposal to change the drainage at the site at the intersection of
Prescott and Chickering Road should be held to the same standard. There is a swale with Bordering
Vegetated Wetland characteristics along Chickering Road/Route 125 within the Mass Highway
Layout.
To receive a Negative Determination(essentially a determination of no impact),the town would need
to show that this Swale was constructed for drainage purposes and has only developed wetland
characteristics due to the fact that it has not been properly maintained for many years. This would also
involve showing that the swale does not drain to or from an existing wetland resource area. Plans I
have seen show that the Swale does drain to Cochichewick Brook several hundred feet away, so the
town should also show that all new stormwater will be handled on-site and not be discharged into the
swale.
If you have any questions regarding the Commission's requirements, please let me know. I have
spoken with Lisa Eggleston, stormwater peer review consultant, and she is aware of the Commission's
request as well.
1600 Osgood Street,Suite 2035,North Andover,Massachusetts 01845
Phone 918.688.9530 Fax 978.688.9542 Web www.townofnorihandover.com
Enright, Jean
From: Santilli, Ray
Sent: Friday,June 27, 2014 10:09 AM
To: Bellavance, Curt; Enright,Jean
Subject: FW:Traffic plan for proposed new fire station
Ray Santilli
Assistant Town Manager
Town of North Andover
120 Main Street
North Andover, MA 01845
Phone 978.688.9516
Fax 978.688.9556
Email rantilli@townofnorthandover.corn
Web www.townofnortliandover.com
�_ll�Illfl i 9i
From: Gallagher, Paul
Sent: Friday, June 27, 2014 10:08 AM
To: Santilli, Ray
Subject: Traffic plan for proposed new fire station
Mr. Santilli,
have reviewed the proposed traffic lights and traffic plan of the new fire station with my traffic unit and command
staff. I recommend favorable action and Lieut. Foulds will continue as the police liaison on the project.
Any questions please let me know.
Regards,
Paul J.Gallagher
Chief of Police
North Andover Police department
1475 Osgood Street
North Andover,MA 01.845
Phone 978.683.3168
Fax 978.685.0249
Email mallagherPnapd.us
Web wwvr.napd.us
1
note h µ,.Massachusetts MW„ ,.X.�S XP ry r n State's office has determined that most ernaiis to and from monici alM„of ices and are public records..For more
Please r7ote the Secretary of t p I
information please refer to:http://www,sec.state.ma,t,is/r)re/Dreidx.htin.
Please consider the environment before printing this email.
2