August 17, 2016
Town of North Andover
Health Department
1600 Osgood Street, Suite 2035
North Andover, MA 01845
Attn: Mr. Brian J. LaGrasse, CEHT—Director of Public Health
RE: Design Analysis for Siting Subsurface Sewage Disposal System on 500 Boxford Street-Lot 1
& 2 (Map 105C, Lot 42)
Dear Mr. LaGrasse:
The following discussion intended to illustrate our analysis in siting the proposed subsurface
sewage disposal systems and buildings on Lot 1 and 2 at 500 Boxford Street.
310 CMR 15.232 (6), states, "Absorption trenches should be used whenever possible." It is
our opinion that alternative systems have their place where absorption trenches are not practical or
possible, such as replacement of failed systems. With this in mind, the houses and septic systems
were moved around the lots and resized to accommodate the Tide V setbacks and to the maximum
extent possible, the North Andover Board of Health and Conservation setbacks. Specifically,
Lot 1
The house was designed to accommodate the building setback requirements. As shown, the
footprint of the dwelling minus the garage is approximately 1,300 s.f. The septic system was
placed at the rear of the building and approximately 63 feet from the wetlands. Moving the
septic system to the front of the lot as close to the lot line setbacks as possible, still required
a variance for the setback to the wetlands. Another problem is that the building will not fit
within the building setbacks as shown on the accompanying sketch. Additionally,
construction of the driveway to the building would require work within the Conservation
"25 foot no disturb zone".
Lot 2
A similar analysis was performed on Lot 2. Moving the septic system in front of the
proposed dwelling, would require the house to be set back 44 feet from the front lot line in
order to meet the Tide V setback requirements. This would move the building within the 50
foot building setback from the wetlands. Also, the system would be within 100 feet of the
existing well. However, we were able to move the system closer to the front lot line
providing a greater setback from the wetlands of approximately 74 feet.
41607 Letter re Design Analysis 2016-08-17.docx
JN: 41607
t�
Mr. Brian LaGrasse
August 17, 2016
Page 2of2
The septic systems shown on these two lots meet all the requirements of Tide V as required.
The relief requested is for the setback to the wetlands. We believe the building and septic
system configurations provide the least environmental impact to the area.
Accompanying this letter, please find the revised Subsurface Sewage Disposal Plan for Lot 2
dated August 17, 2016. As stated above, the system was moved closer to the front lot line to
provide more of a separation from the wetlands. Since the system on Lot 1 as shown on the plans
dated July 7, 2016 remained the same, the plans were not resubmitted.
Should you have any questions regarding the siting of the construction elements of the site,
please do not hesitate to contact me.
Yours truly,
DK ENGINEERI G ASSOCIATES,INC.
Daniel Koravos, P.E.
President
cc: Mr. William MacLeod,Andover Consultants, Inc.
DK ENGINEERING ASSOCIATES, INC.
]N: 41607
AL
AIL j• /
•
/ •�• 23D
3I 20D 22DD
AL AIL
wa.
• n
AIL
SIC \
AIL \
�18D\ _ \
311L �• \ /
AIL •�17D
AIL ••` `'�
AIL
3& ••� 22.7't
16D• t `"
� � v
AL 25'to
311E A314 AIL2
./9E i
®�.... 8E AL AllSD \
12E t0E \
i
4,013E
� ./ 11E 7E ,� �.•�
I 13E 3ltc
• 14[
` 14E AIL 00
6E
i 3D
12D
19L
411D
1
15E SE
N
AL
Y
` '10D qq
�i
6E ( AL •� \
.� 3E
•� 17E 49d
AL • 2E
18E 1E A AL 1 \ 63
1D •� i' 7D
_azo-
311L ,SIL •„ 8D —
AL
2D 6D
• 314 SDmoo
3D Q
OoA• •• _
i
AL AL
••�eGl` AL .2 D•• 30D \�
25D _ .�••�gOw \\�
•• • _270 2��' — — — — -- -_._ 31D
26D/ — ` �V
\ // A,.
00
��'ry/� � •'off ag \
DE
CK woo
� I �
Lot 1
r. 2.1 Acs.
x
91,820± s.f. I
lk`
94 II
+ I A
-124 ..-- . _.____ - %1 . 500 Boxford Street
Lot 1
SSDS Location Sketch
u u
--- _L6_- ---------=---------
- BOXFOxD ST
DK ENGINEERING ASSOCIATES, INC.
Woodland Ridge Phone: (603) 898-8516
47 Enterprise Drive,#7 E-mail: dan@dkengineering.net
swim P.O.Box 4260 www.dkengr.net
Windham,NH 03087-4260
July 7, 2016
RECEIVED
Town of North Andover JUL 12 2016
Health Department
1600 Osgood Street, Suite 2035 TOWN OF NORTH ANDOVER
North Andover, MA 01845 HEALTH DEPARTMENT
Attn: Mr. Brian J. LaGrasse, CEHT—Director of Public Health
RE: Subsurface Sewage Disposal System Plan for 500 Boxford Street- Lot 1 (Map 105C,Lot 42)
Dear Mr. LaGrasse:
The following is in response to the review comment as outlined in your letter dated June 27,
2016:
Response: The Assessor's Map and Lot numbers have been added to the title block and on
sheet 2.
1. The existing and proposed lot lines should be depicted on the design plan. On page two of three,please depict the oyzginal
three lots and overlay the proposed two lots being created with the proposed dwellings,proposed ystems and all lot line
setbacks, the 100'wetland buffer done, 50'no build done and 25'no disturbance Zone.
Response: Sheet two of three has been updated with the information requested.
2. Note 7 is repeated as note 17.
Response: Note 17 has been removed.
3. Lot 1 asproposed does not have a benchmark and the benchmark on Lot 2 in not within 50-75'from the proposed ystem
(310 CMR 15.220(4)(q).
Response: A new benchmark has been added t
p o the plan.
4. Indicate why the soil absorption gstem cannot be proposedgreater than 100 feet from the wetland resource area and whyyou
cannot comply with section 3.9 of the North Andover Septic Regulations. There is an area in the southeast corner of the
proposed lot that isgreater than 100,feet from the wetland resource area. Please research alternative designs and site layouts
that keep the ystems out of the 100'buffer done or designs that achieve maximum feasible compliance. Please also note that
Section 3.8 of the North Andover Septic Regulations state that a DEP approved device or alternative technology which
reduces wastewater to levels below 30 mg/L BOD and 30mg1 L TSS can be approved by the department without a hearing
before the Board of Health. I have attached a rough sketch that shows 100 linear feet of primary and reserve trenches that
me out of the 100'as a rough demonstration.
Response: The layout of the trenches provided is not feasible. 310 CMR 15.232 (1) states "For
all gravity flow distribution systems, a water tight distribution box designed to
provide equal distribution of septic tank effluent to the distribution lines of the soil
41607 Response Letter re Lot 1 SSDS Comments 2016-07-07.docx
JN: 41607
TECOPY
s� TLED .
-- .•
•A°Rdx�n ate"
North Andover Health Department
(ommunity and Economic Development Division
June 27, 2016
Daniel Koravos, P.E.
DK Engineering Associates, Inc.
47 Enterprise Drive, #7
P.O. Box 4260
Windham,NH 03087-4260
Re:Subsurface Sewage Disposal System Plan for 500 Boxford Street-Lot 1 (Map 105C, Lot
42)
Dear Mr. Koravos,
The proposed wastewater system design plan for the above site dated May 24, 2016, Revised on
June 15, 2016 and received on June 21, 2016 has been reviewed. Unfortunately, the plan cannot
be approved until the following items are corrected. The specific section in Title 5: 310 CMR
15.000, or North Andover regulation that is not met by this design follows each item where
applicable.
1. The existing and proposed lot lines should be depicted on the design plan. On page two
of three,please depict the original three lots and overlay the proposed two lots being
created with the proposed dwellings,proposed systems and all lot line setbacks, the 100'
wetland buffer zone, 50' no build zone and 25' no disturbance zone.
2. Note 7 is repeated as note 17.
3. Lot 1 as proposed does not have a benchmark and the benchmark on Lot 2 in not within
50 - 75' from the proposed system (3 10 CMR 15.220(4)(q).
4. Indicate why the soil absorption system cannot be proposed greater than 100 feet from
the wetland resource area and why you cannot comply with section 3.9 of the North
Andover Septic Regulations. There is an area in the southeast corner of the proposed lot
that is greater than 100 feet from the wetland resource area. Please research alternative
designs and site layouts that keep the systems out of the 100'buffer zone or designs that
achieve maximum feasible compliance. Please also note that Section 3.8 of the North
Page 1 of 2
North Andover Health Department, 1600 Osgood Street, Suite 2035,
North Andover, MA 01845 Phone: 978.688.9540 Fax: 978.688.8476
Andover Septic Regulations state that a DEP approved device or alternative technology
which reduces wastewater to levels below 30 mg/L BOD and 30mg/L TSS can be
approved by the department without a hearing before the Board of Health. I have
attached a rough sketch that shows 100 linear feet of primary and reserve trenches that
are out of the 100' as a rough demonstration.
5. The wetland lines have not been confirmed or approved by the North Andover
Conservation Commission and may be subject to change. A preliminary site walk by the
Conservation Department may be beneficial and reduce additional revisions.
6. To ensure compliance with 310 CMR 15.211, please add a note stating that there is no
septic system on the easterly abutting property (Map 105.0 Block 0040) within 100' of
the proposed well or increase the area depicted on the plan and add 100' circumference
around the subject well.
7. On sheet 3 of 3, remove the "untreated building paper" above the peastone layer in the
soil absorption system. You may change this and use permeable landscaping fabric. The
use of the untreated building paper is not in compliance with Title 5 regulations and will
deteriorate rapidly once installed. This does not appear to accomplish the intended
outcome stated in your letter dated June 15, 2016.
8. Please submit an additional review fee of$125 with revised plans.
Please feel free to contact me at 978-688-9540 or Mill River Consulting at 978-282-0014 with
any questions you may have. We look forward to working with you to obtain a wastewater
treatment and dispersal system which will be in compliance with all regulations and assure
protection of public health and the environment of North Andover.
Sincer ,
2
rian J. aGrasse, CEHT
Director of Public Health
cc: Michael Donovan
Thomas Donovan
Cornelius Donovan
Andover Consultants, Inc.
File
Page 2 of 2
North Andover Health Department, 1600 Osgood Street, Suite 2035,
North Andover, MA 01845 Phone: 978.688.9540 Fax: 978.688.8476
' ,4 J �,,�— 4t`It L' 1 X128,
t �-," \ moi' >
O \`
r-200 �i, ,V -------
D _____- - ,rr^"1 ,,,r-"'`•���
N BOX
SEPTIC '
`• �'�� 'l. .��2 — DECK TANK
11 L.F.AL
r tai r i
30.5
3D
---------------- '
F2° ` PROP. (2 �bk, EXIST!
15.3'LO WELLING 2.7' s Lot
..- PROP. 91,820 S.F. ,
DRIVEWAY �
i23 TF=131.4 N
�
' 11
kg � BF-123.7
-124• _- 4,2' »i
PROP.t\\ r
WELL
/00
Ajpf/°p -
PROP.
WATER
SERVICE a
r �
. 12 n5.9 Q
''P„.. '^ +. r„....r.,...+. .r .. . ... ...r__ . __ __+_ ... ...... __. .. ..._+..._. __+.. ...
-'" G - STREET Z6
--- BOXFORD
PROP.
LANDSCAPE --'--"----- y-
WALL
_
Mr. Brian LaGrasse
July 7, 2016
Page 2 of 2
absorption system shall be provided between the septic tank and soil absorption
system." With the varying lengths of the trenches as shown on the sketch, the
trenches will not receive equal distribution per linear feet of trench.
5. The wetland lines have not been confirmed or approved by the North Andover Conservation Commission and may be subject
to change.A preliminary site walk by the Conservation Department may be beneficial and reduce additional revisions.
Response: The variance requested is required to file with the Conservation Commission. The
Notice of Intent filing will verify the wetland lines.
6. To ensure compliance with 310 CMK 15.291,please add a note stating that there is no septic ystem on the easterly
abutting property (Map 105.C Block 0040)within 100'of the proposed well or increase the area depicted on the plan and
add 700'circumference around the subject well.
Response: A 100 foot arc centered on the proposed well was added as requested.
7. On sheet 3 of 3, remove the "untreated building paper"above the peastone layer in the soil absorption ystem. You may
change this and use permeable landscaping fabric. The use of the untreated building paper is not in compliance with Title 5
regulations and will deteriorate rapidly once installed. This does not appear to accomplish the intended outcome stated in your
letter dated June 15, 2016.
Response: The "untreated building paper" has been removed from the detail.
8. Please submit an additional review fee of S 125 with revised plans.
Response: The additional fee accompanies this letter.
I believe all you concerns have been addressed. Should you have any question or require
additional information, please do not hesitate to contact me.
Yours truly,
DK ENGINEERING ASSOCIATES,INC.
Daniel Koravos, P.E.
President
cc: Mr. William MacLeod,Andover Consultants, Inc.
DK ENGINEERING ASSOCIATES' INC.
I
JN: 41607
I
i
DK ENGINEERING ASSOCIATES, INC.
Woodland Ridge Phone: (603) 898-8516
47 Enterprise Drive,#7 E-mail: dan@dkengineering.net
P.O.Box 4260 www.dkengr.net
Windham,NH 03087-4260
June 15, 2016
Town of North Andover RECEIVED
Health Department
1600 Osgood Street, Suite 2035 JUN 21 2016
North Andover, MA 01845
TOWN NORTH ER
LTH DEPARTMENT
Attn: Mr. Brian J. LaGrasse, CEHT—Director of Public Health
RE: Subsurface Sewage Disposal System Plan for 500 Boxford Street-Lot 1 (Map 105C,Lot 42)
Dear Mr. LaGrasse:
The following is in response to the review comment as outlined in your letter dated June 9,
/ 2016:
( 1. The Assessors map and lot numbers are not indicated on the design plan (NA 3.2).
Response: The Assessor's Map and Lot numbers have been added to the title block and on
sheet 2.
2. The existing and proposed lot lines should be depicted on the design plan.
Response: The existing and proposed lots lines have been added to sheet 2.
3. TP-5 was not depicted on the design plan (3 10 CMB 15.220(4)(h)).
Response: TP-5 has been added to the design plan (sheet 1).
/ 4. The percolation test results should indicate a percolation rate of<2 minsl inch.
Response: The less than symbol has been added to the percolation rates.
5. On sheet 1 of 3, the graphical representation of the test pits should be shown as they were excavated instead of circles as
depicted in the site plan view.
Response: The rectangular test pit symbols have been added to the plan.
6. Indicate why the soil absorption ystem cannot be proposed greater than 100 feet from the wetland resource area and
maintain compliance with section 3.9 of the North Andover regulation. There is an area in the southeast corner of the
proposed lot that isgreater than 100 feel from the wetland resource area.
Response: Considering the required setbacks from the property lines and the required size of
the proposed septic system, the area outside the 100 foot wetland buffer zone in the
southeast corner of the lot is insufficient to contain the system.
7. No benchmarks were depicted on the design plan (3 10 CMB 220(4)(8)).
41607 Response Letter re Lot 1 SSDS Comments 2016-06-15.docx
JN: 41607
` Mr. Brian LaGrasse I
June 15, 2016
Page 2 of 2
Response: A benchmark has been added to the plan and a.note stating additional benchmarks
will be set prior to construction.
8. The foundation drain location and elevation were not depicted on the de ign plan (NA 3.2).
Response: The foundation drain has been added to the plan on sheet 1. Also on sheet 1 note
17 was added indicating the setback requirements.
9. Depict the setback distance from the proposed well to abutting soil absorption ystems to ensure compliance with 310 CMR
fj 15.211.
Response: To the south of the proposed well, a 100 foot offset is within the right-of-way of
Boxford Street. The westerly property line is within 28 feet of the wetland on the
abutting property. The 100 foot offset from the proposed well is approxunately
twelve feet from the lot line and 18 feet from the wetlands. The easterly lot line of
the property is approximately 125 feet from the proposed well.
V 10. On sheet 3 of 3, the loading (H-10 or H-20) of the septic tank was not depicted on the design plan (3 10 CMR
15.226(3)).
Response: Note 3 on sheet 3 has been added stating that the septic tank shall meet H10
loading requirements.
11. 6"of crushed stone is required beneath the distribution box(310 CMR 15.221(2)).
Response: In the "Concrete Distribution Box" on sheet 3, note 3 was added stating that 6
inches of crushed store is required beneath the distribution box.
12. On sheet 3 of 3, explain the purpose for the "untreatedbuilding paper" above the peastone layer in the soil absorption
ystem. Also explain how the use of the untreated building paper is in compliance with Title 5 regulations.
• Response: The "untreated building paper" is provided to assistin preventing fines from
entering the stone trenches and help minimize surface water from inundating the
system. Oak PNoJSu\
I believe all you concerns have been addressed. Should you have any question or require
additional information, please do not hesitate to contact me.
Yours truly,
DK ENGINEERING ASSOCIATES,INC.
Daniel Koravos, P.E.
President
cc: Mr. William MacLeod,Andover Consultants, Inc.
DK ENGINEERING ASSOCIATES, INC.
JN: 41607
t
• LED j
North Andover Health Department
Community and Economic Development Division
June 9, 2016
Daniel Koravos, P.E.
DK Engineering Associates, Inc.
47 Enterprise Drive, #7
P.O. Box 4260
Windham,NH 03087-4260
Re: Subsurface Sewage Disposal System Plan for 500 Boxford Street-Lot 1 (Map 105C,
Lot 42)
Dear Mr. Koravos,
The proposed wastewater system design plan for the above site dated May 24, 2016 and received
on June 1, 2016 has been reviewed. Unfortunately, the plan cannot be approved until the
following items are corrected. The specific section in Title 5: 310 CMR 15.000, or North
Andover regulation that is not met by this design follows each item where applicable.
1. The Assessor's map and lot numbers are not indicated on the design plan (NA 3.2).
2. The existing and proposed lot lines should be depicted on the design plan.
3. TP-5 was not depicted on the design plan (3 10 CMR 15.220(4)(h)).
4. The percolation test results should indicate a percolation rate of<2 mins/inch.
5. On sheet 1 of 3, the graphical representation of the test pits should be shown as they were
excavated instead of circles as depicted in the site plan view.
6. Indicate why the soil absorption system cannot be proposed greater than 100 feet from
the wetland resource area and maintain compliance with section 3.9 of the North Andover
regulation. There is an area in the southeast corner of the proposed lot that is greater than
100 feet from the wetland resource area.
7. No benchmarks were depicted on the design plan(3 10 CMR 220(4)(q)).
8. The foundation drain location and elevation were not depicted on the design plan(NA
3.2).
Page 1 of 2
North Andover Health Department, 1600 Osgood Street, Suite 2035,
North Andover, MA 01845 Phone: 978.688.9540 Fax: 978.688.8476
• '' 9. Depict the setback distance from the proposed well to abutting soil absorption systems to
ensure compliance with 310 CMR 15.211.
10. On sheet 3 of 3, the loading (H-10 or H-20) of the septic tank was not depicted on the
design plan (3 10 CMR 15.226(3)).
11. 6"of crushed stone is required beneath the distribution box (3 10 CMR 15.221(2)).
12. On sheet 3 of 3, explain the purpose for the "untreated building paper" above the
peastone layer in the soil absorption system. Also explain how the use of the untreated
building paper is in compliance with Title 5 regulations.
Please feel free to contact the office or Mill River Consulting at 978-282-0014 with any
questions you may have. We look forward to working with you to obtain a wastewater treatment
and dispersal system which will be in compliance with all regulations and assure protection of
public health and the environment of North Andover.
Sincerely,
ti
Br an J. LaGrasse, CEHT
Director of Public Health
cc: Michael Donovan
Thomas Donovan
Cornelius Donovan
Andover Consultants, Inc.
File
Page 2 of 2
North Andover Health Department, 1600 Osgood Street, Suite 2035,
North Andover, MA 01845 Phone: 978.688.9540 Fax: 978.688.8476
• TOWN OF NORTH ANDOVER
Office of COMMUNITY DEVELOPMENT AND SERVICES _.
HEALTH DEPARTMENT
1600 OSGOOD STREET; SUITE 2035
NORTH ANDOVER,MASSACHUSETTS 01845
Susan Y.Sawyer,RENS,RS 978.688.9540—Phone
Public Health Director 978.688.8476—FAX RECEIVED
healthdent(a,townofnorthandover.com
www.townofnorthandover.comAGG 13 2015
APPLICATION FOR SOIL TESTS TOWN OF NORTH ANDOVER
HEALTH DEPARTMENT
DATE: August 3, 2015 MAP&PARCEL: 105C 42
LOCATION OF SOIL TESTS: 50'northwest of existing dwelling(see sketch) 660
OWNER: Thomas Donovan Contact#:
APPLICANT. Andover Consultants, Inc Contact#: 978-687-3828
ADDRESS: 1 East River Place,Methuen,MA 01844
ENGINEER: Andover Consultants,Inc Contact#: 978-687-3828
CERTIFIED SOIL EVALUATOR: James Fairweather
Intended Use of Land: Residential Subdivision Single Family Home Commercial
Is This: Repair Testing: Undeveloped Lot Testing: Upgrade for Addition:
In the Lake Cochichewick Watershed? Yes No ✓
THE FOLLOWING MUST BE INCLUDED WITH THIS FORM
➢ Proof of land ownership(Tax bill,or letter from owner permitting test)
➢ 8.S"x 11"Plot plan&Location of Testing(please indicate test nit sites on the plan)
➢ Fee of$425.00 per lot for new construction. This covers the minimum two deep holes and
two percolation tests required for each disposal area. Fee of$360.00 per lot for repairs or upgrades.
GENERAL INFORMATION
➢ Only Certified Soil Evaluators may perform deep hole inspections.
➢ Only Mass.Registered Sanitarians and Professional Engineers can design septic plans.
➢ At least two deep holes and two percolation tests are required for
each septic system disposal area.
➢ Repairs require at least two deep holes and at least one percolation test,at the.discretion of the BOH
representative.
➢ Full payment will be required for all additional tests within two weeks of testing.
➢ Within 45 days of testing,a scaled plan(no smaller than 1"-100')shall be submitted to the Board of Health
showing the location of all tests(including aborted tests).
➢ Within 60 days of testing soil evaluation forms shall be submitted.
Please Do Not Write Below This Line
,K11S 6 -�5
N.A. Conservation Commission Approval Date: C, r.2C
Signature of Conservation Agent: rC,/� W�-k "ou
Date back to Health Department: (stamp in):
�i I it I 1
Ovzlz
x �
x
8
LOT C %
LOT B 78,420 S.F.
58,200 S.F. mt_.
X21
m,t .A,. �, \
�.- �_ffi —�� PT
w' •. m•' _ w '\ \®�$. Q PRoaose0 PERI TEST
p 1 , ""' �" �0 —� + { 0 .Y a • 1'.�® PROPOSED DEEP HOLE TEST
Nil
EA
v
i
LOT OWNERS:
LOT D OT B.
740 S F NORTH ANDOVER MA 01845
1
i
iAEL DONOVAN
—
1N2CJOHNSON STREET
,�sl
.n.
...__...... -- LOT C: THOMAS DONOVAN
.::t5JW.01'-
_ - YMEATINA, VE
� 4&'�\ FUOUAY VARINA NC 27526
___ 5000 E ORI
tiy93Tto'W 1°• TA 'F(r('I
OAT.I./ C 'l�-��_�•-¢.= >A. 'N LOT D: CORNELIUS J.DONOVAN
JTR U'T-•ry. �" �/ 12 TROLLEY CAR LANE
-�`�+�1 '>•` .., y moi• LONDONDERRY,NH 03053
O SOIL TEST PLAN
= 500 BOXFORD STREET
C NORTH ANDOVER, MASS.
OWNER: SEE UST
_ ) ^ DATE: July 30.2015
-Z `/ SCALE: 1"-40'
rn m NOTES:
13 A VARIANCE FROM THE NORTH ANDOVER BOARD OF HEALTH
D REGULATIONS,DESCN REOLTIREMMM TABLE I'SETBACK DISTANCE andover
TABLE'FOR A SOIL ABSORPTION SYSTEM DISTANCE TO A WETLAND z a L j REOU REDDW A SYSTEM TO BE OVER 50'BUT LESS THAN 100^)IS C Inc.UI ldn l3
2)WETLANDS FLAGGED BY NORSE ENNROMMENTAL SERVICES,INC. Methu—M,s,!ace 01844
P:\ts\t4-89\OWG\9TE.oWG �`G!'1 3. LOTS B.C d D ARE SHOWN ON N.D.E.R.D.PLAN 7(7580. 0 40 80 120 160 Ft.
0 10 10 40 Meter
Hadge, Lisa
From: Isaac Rowe <irowe@millriverconsulting.com>
Sent: Wednesday, December 02, 2015 3:14 PM
To: Hadge, Lisa; 'Pam Lally'
Cc: Grant, Michele;Isaac Rowe
Subject: RE: 500 Boxford
Attachments: 500 Boxford St (2 lots) - Soil testing results 12-2-15.PDF
Lisa/Michele,
Attached are the soil testing results for the above referenced property.
Your office should confirm the applicant has paid the correct fee for(2) new construction lots.The application indicates
an addition to the existing dwelling.The soil evaluator,Steve Erickson, indicated we were testing for
(2) new lots. MRC will be invoicing appropriately.
These projects will likely be seeking variances from the BOH regulations to site a leaching facility less than 100'to a BVW
for new construction.
Please let me know if you have any questions.
Thanks,
Isaac M. Rowe, R.S.
Project Manager
Mill River Consulting
6 Sargent Street
Gloucester, MA 01930-2719
Phone:978-282-0014 ext.804
Fax: 978-282-1318
irowe@millriverconsulting.com
www.millriverconsulting.com
-----Original Message-----
From: Hadge, Lisa [mailto:lhadge@townofnorthandover.com]
Sent:Tuesday, November 17, 2015 9:32 AM
To: Dan Ottenheimer; Isaac Rowe; Pam Lally
Cc: Grant, Michele
Subject: 500 Boxford
Good Morning,
Andover Consultants are taking this off hold. I am sending the applications to you again. Please read the attached email
from Jen Hughes of Conservation. I will have Heidi from Conservation update the Application for Soil Testing when she
gets back in the office. Please call Norse Environmental, either Steve Ericson or Maureen Herald (both certified soil
evaluators)at
978-649-9932 to set up the soil testing.Thanks.
-----Original Message-----
From: noreply@townofnorthandover.com [mailto:noreply@townofnorthandover.com]
4`RM� ,,
x
gy,lbw ......_.:.- ....,... ...... ..,.-._:.-,....-... ....,. , ,r•. .. _ ..
may.
t £
1IN I 1 NIIN11 N111 � -f - •
k 1 1 IIINII NIIIN IIIIN � ' . `' • '
11111 IN/I NI IIIMNII
111111 IIIIIIINN 111111111111IL
., IIN IIIN IIIN:�i��•��1,,��11r
} 1 1 111NIIN IIII�Wimll ..a �
�1�1
�I�1�G11�i11'NIIIIIIII�ICI�/�i�®
�- -IIINO'� dl, NIIEL�1�' �li`3�1
Saw
:
������� r-
1�..�'h
MINES IIII 1 111111
!► , I�° �1 NII �A IIIN 'ter"' �!
�NNN ■Nei ��� � 1 �
111 �i�i
,..����4r+swa,..ar...<_.sc.._..r ..._.._..,..'-'..:.....,._. ..._:.;...:.:_'....a:.._e.�...:.mow—...._:_.✓..,.._.r.+:.., j3 ,.r ..-. , .. .............. .„
k
Gaffney, Heidi
From: Hughes, Jennifer
Sent: Thursday, October 22, 2015 4:15 PM
To: BILL MacLEOD (wsmacleod@verizon.net)
Cc: Gaffney, Heidi
Subject: 500 Boxford Street
Bill,
I reviewed the four test pits proposed at 500 Boxford Street. All are within fairly level, open areas of the lot and appear
to be more than 50'from the BVW. I ask that when you access test pit#1 (the farthest in on the property)that you
access to the left of the pine trees as you face them.There is a wetland flag not far to the right of those pines. Please let
me know when work will begin and when you are finished.Thanks.
Jennifer A.Hughes
Conservation Administrator
Town of North Andover
1600 Osgood Street,Suite 2035
North Andover,MA 01845
Phone 978.688.9530
Fax 978.688.9542
Email ihushes@townofnorthandover.com
Web www.TownofNorthAndover.com
1
Grant, Michele
To: jimfairweather@andoverconsultants.com'
Cc: Blackburn, Lisa;Isaac Rowe
Subject: RE: 500 Boxford St
Hi Jim,
As per our phone conversation this morning.A request from Andover Consultants to hold off on scheduling Soils
Evaluations at 500 Boxford. Please let us know when you are ready to move forward with scheduling the Soils.
Thank you,
Michele E.Grant
Public Health Agent
Town of North Andover
1600 Osgood St I Suite 2035
North Andover,MA 01845
Phone 978.688.9540
Fax 978.688.8476
Email mgrant@townofnorthandover.com
Web www.TownofNorthAndover.com
•..
N. V ,
x ;Kt!�
From: Grant, Michele
Sent: Friday, August 14, 2015 9:02 AM
To: 'jimfairweather@andoverconsultants.com'
Cc: Blackburn, Lisa
Subject: 500 Boxford St
Good Morning Jim,
Heidi informed me of the criteria's that are needed for ConCom. Did you want me to still move forward with scheduling
the soils evaluations?
Please advise
Sincerely,
Michele E.Grant
Public Health Agent
1
Town of North Andover
1600 Osgood St I Suite 2035
North Andover,MA 01845
Phone 978.688.9540
Fax 978.688.8476
Email merant@townofnorthandover.com
Web www.TownofNorthAndover.com
2
Grant, Michele
To: Pam Lally
Cc: Isaac Rowe; Dan Ottenheimer, Blackburn, Lisa
Subject: 2 Soils 500 Boxford street
Attachments: 201508131118.pdf; 201508131117.pdf
Hi Pam,
There are 2 soils here.Three lots,One is an existing house and 2 are vacant lots.They are combining these lots to make
2 lots.
Thx
Michele E.Grant
Public Health Agent
Town of North Andover
1600 Osgood St I Suite 2035
North Andover,MA 01845
Phone 978.688.9540
Fax 978.688.8476
Email mgrant@townofnorthandover.com
Web www.TownofNorthAndover.com
I
1
a
,�3 �p15
August 3,2015
V 90�
s ��1pF NpEpP��M�'
To whom it may concern:
We the undersigned,owners of property at and adjacent to 500 Boxford Street in the Town of North
Andover,authorize Andover Consultants,Inc.to conduct soil testing on our land and to prepare all
necessary plans and file all necessary applications and forms with all government agencies
including the Town of North Andover Boards and Commissions and the Commonwealth of
Massachusetts Department of Environmental Protection for work related to our properties.
Sincerely,
Michael Donovan, Lot B(Assessor Map 105C Lot 41)
Michael Donovan
Thomas Donovan.Lot C(Assessor Map 105C Lot 42,aka 500 Boxford Street)
Thomas Donovan
Cornelius J. Donovan,Lot D(Assessor Map 105C Lot 43)
Cornelius J. Donovan
DK ENGINEERING ASSOCIATES, INC.
Woodland Ridge Phone: (603) 898-8516
47 Enterprise Drive,#7 E-mail:dan@dkengineering.net
P.O.Box 4260 www.dkengr.net
® Windham,NH 03087-4260EiiE!RECEIVED
August 17, 2016 AUG 18 2016
TOWN OF NORTH ANDOVER
HEALTH DEPARTMENT
Town of North Andover
Health Department
1600 Osgood Street, Suite 2035
North Andover, MA 01845
Attn: Mr. Brian J. LaGrasse, CEHT—Director of Public Health
RE: Design Analysis for Siting Subsurface Sewage Disposal System on 500 Boxford Street-Lot 1
& 2 (Map 105C, Lot 42)
Dear Mr. LaGrasse:
The following discussion intended to illustrate our analysis in siting the proposed subsurface
sewage disposal systems and buildings on Lot 1 and 2 at 500 Boxford Street.
310 CMR 15.232 (6), states, "Absorption trenches should be used whenever possible." It is
our opinion that alternative systems have their place where absorption trenches are not practical or
possible, such as replacement of failed systems. With this in mind, the houses and septic systems
were moved around the lots and resized to accommodate the Title V setbacks and to the maximum
extent possible, the North Andover Board of Health and Conservation setbacks. Specifically,
Lot 1
The house was designed to accommodate the building acrequirements.uirements. As shown, the
footprint of the dwelling minus the garage is approximately 1,300 s.f. The septic system was
placed at the rear of the building and approximately 63 feet from the wetlands. Moving the
septic system to the front of the lot as close to the lot line setbacks as possible, still required
a variance for the setback to the wetlands. Another problem is that the building will not fit
within the building setbacks as shown on the accompanying sketch. Additionally,
construction of the driveway to the building would require work within the Conservation
"25 foot no disturb zone".
Lot 2
A similar analysis was performed on Lot 2. Moving the septic system in front of the
proposed dwelling, would require the house to be set back 44 feet from the front lot line in
order to meet the Title V setback requirements. This would move the building within the 50
foot building setback from the wetlands. Also, the system would be within 100 feet of the
existing well. However, we were able to move the system closer to the front lot line
providing a greater setback from the wetlands of approximately 74 feet.
41607 Letter re Design Analysis 2016-08-17.docx
JN: 41607
Mr. Brian LaGrasse
August 17, 2016
Page 2 of 2
The septic systems shown on these two lots meet all the requirements of Title V as required.
The relief requested is for the setback to the wetlands. We believe the building and septic
system configurations provide the least environmental impact to the area.
Accompanying this letter, please find the revised Subsurface Sewage Disposal Plan for Lot 2
dated August 17, 2016. As stated above, the system was moved closer to the front lot line to
provide more of a separation from the wetlands. Since the system on Lot 1 as shown on the plans
dated July 7, 2016 remained the same, the plans were not resubmitted.
Should you have any questions regarding the siting of the construction elements of the site,
please do not hesitate to contact me.
Yours truly,
DK ENGINEERING ASSOCIATES,INC.
Daniel Koravos, P.E.
President
cc: Mr. William MacLeod,Andover Consultants, Inc.
DK ENGINEERING ASSOCIATES, INC.
JN: 41607
drant M cheIe j
To: jimfairweather@andoverconsultants.com
Cc: Blackburn, Lisa
Subject: 500 Boxford St
Good Morning Jim,
Heidi informed me of the criteria's that are needed for ConCom. Did you want me to still move forward with scheduling
the soils evaluations?
Please advise
Sincerely,
Michele E.Grant '
Public Health Agent
Town of North Andover 4
1600 Osgood St I Suite 2035 cry -/'rte
North Andover,MA 01845 )�,iv C
Phone 978.688.9540
Fax 978.688.8476
Email mgrant@townofnorthandover.com
Web www.TownofNorthAndover.com
4v
1
Grant, Michele
From: Isaac Rowe <irowe@millriverconsulting.com>
Sent: Thursday,August 13, 2015 3:59 PM
To: Grant, Michele
Cc: Isaac Rowe
Subject: RE: 500 Boxford St -test pit applications
Ok thanks. I will wait to hear from you that the test pits have been approved by Con Com prior to scheduling the soil
testing.
Thanks,
Isaac M. Rowe, R.S.
Project Manager
Mill River Consulting
6 Sargent Street
Gloucester, MA 01930-2719
Phone: 978-282-0014 ext.804
Fax:978-282-1318
irowe(a),millriverconsulting.com
www.miliriverconsulting.com
From: Grant, Michele [ma i Ito:MGra nt(atownofnortha ndover.com]
Sent: Thursday, August 13, 2015 1:25 PM
To: 'Isaac Rowe'
Subject: FW: 500 Boxford St-test pit applications
Hi Isaac, Please see below and the attached
From: Gaffney, Heidi
Sent: Thursday, August 13, 2015 1:22 PM
To: Grant, Michele
Subject: FW: 500 Boxford St-test pit applications
From: Gaffney, Heidi
Sent: Thursday, August 13, 2015 1:22 PM
To: 'James Fairweather'
Subject: FW: 500 Boxford St-test pit applications
Hi Jim, I should have added first that the test pit locations as currently proposed will require a filing, but if moved to
more than 75'from the wetland/ephemeral pool habitat then I can sign off without a filing.
Heidi Gaffney
Conservation Field Inspector
Town of North Andover
1600 Osgood Street,Suite 2035
North Andover,MA 01845
Phone 978-688-9530
1
1
Fax 978-688-9542 jy
Email hgaffnev@townofnorthandover.com
Web www.TownofNorthAndover.com
y `k
From: Gaffney, Heidi
Sent: Thursday, August 13, 2015 11:48 AM
To: 'James Fairweather'
Subject: 500 Boxford St-test pit applications
Hi Jim, I took a look at the test pit applications and believe that there is ephemeral pool habitat in this area,which will
require the test pits to be at least 75'from the wetland. Please revise the sketch to show that the test pits are at least
75'from the wetland and then I can sign off on them. You may want to consider an ANRAD to have the wetlands
reviewed?
Heidi Gaffney
Conservation Field Inspector
Town of North Andover
1600 Osgood Street,Suite 2035
North Andover,MA 01845
Phone 978-688-9530
Fax 978-688-9542
Email hgaffnev@townofnorthandover.com
Web www.TownofNorthAndover.com
•.aG'rt' c��w
All email messages and attached content sent from and to this email account are public records
unless qualified as an exemption under the Massachusetts Public Records Law.
Visit us online at www.townofnorthandover.com
Social Networks
twitter.com/north_a ndover
www.facebook.com/northandoverma
2
Grant, Michele
From: Gaffney, Heidi
Sent: Thursday, August 13, 2015 1:09 PM
To: Grant, Michele
Subject: FW: 500 Boxford St -test pit applications
From: Gaffney, Heidi
Sent: Thursday, August 13, 2015 11:48 AM
To: 'James Fairweather'
Subject: 500 Boxford St- test pit applications
Hi Jim, I took a look at the test pit applications and believe that there is ephemeral pool habitat in this area,which will
require the test pits to be at least 75'from the wetland. Please revise the sketch to show that the test pits are at least
75'from the wetland and then I can sign off on them. You may want to consider an ANRAD to have the wetlands
reviewed?
Heidi Gaffney
Conservation Field Inspector
Town of North Andover
1600 Osgood Street,Suite 2035
North Andover,MA 01845
Phone 978-688-9530
Fax 978-688-9542
Email heaffney@townofnorthandover.com
Web www.TownofNorthAndover.com
1
Grant, h-ichele
From: Isaac Rowe <irowe@millriverconsulting.com>
Sent: Thursday, August 13, 2015 1:03 PM
To: Grant, Michele
Cc: Isaac Rowe
Subject: RE: 500 Boxford st.Test pit plan
Let me know when Con Com has signed off on the soil test application.
Thanks,
Isaac M. Rowe, R.S.
Project Manager
Mill River Consulting
6 Sargent Street
Gloucester, MA 01930-2719
Phone: 978-282-0014 ext.804
Fax:978-282-1318
irowe@millriverconsulting.com
www.millriverconsultine.com
-----Original Message-----
From: Grant, Michele [maiIto:MGrant@townofnorthandover.com]
Sent:Thursday,August 13, 2015 12:17 PM
To: Isaac Rowe
Subject: 500 Boxford st.Test pit plan
Hi Isaac,
Sorry, I forgot this when I sent the soils application
Thx
Michele
-----Original Message-----
From: noreply@townofnorthandover.com [mailto:noreply@townofnorthandover.com]
Sent:Thursday,August 13, 2015 12:28 PM
To:Grant, Michele
Subject: Message from "ComDev-Health-Ricoh"
This E-mail was sent from "ComDev-Health-Ricoh" (Aficio MP C3002).
Scan Date:08.13.2015 12:28:04(-0400)
Queries to: noreply@townofnorthandover.com
All email messages and attached content sent from and to this email account are public records unlA-s gLJii; �
exemption under the Massachusetts Public Records Law.
Visit us online at www.townofnorthandover.com
Social Networks
twitter.com/north_andover
www.facebook.com/northandoverma
2
TOWN OF NORTH ANDOVER
Office of COMINIUNITY DEVELOPMENT AND SERVICES
HEALTH DEPARTMENT
1600 OSGOOD STREET; SUITE 2035
NORTH ANDOVER, MASSACHUSETTS 01845
978.688.9540—Phone
978.688.8476—FAX
E-MAIL: healthdept@northandoverma.gov
WEBSITE: hqp://www.northandoverma.gov
SEPTIC PLAN SUBMITTAL
FORM
Date of Submission:w
Site Location: J�6 ZFPk,=;012Z 157%
Engineer:
New Plans? Yes ✓$275/Plan Check# //47 1St submissioni� ���® 1 (�
review only) JUN 01 2016 I
Revised Plans?Yes $125/Plan Check# TOWN OF NORTH ANDOVER
HEALTH DEPARTMENT
Site Evaluation Forms Included? Yes P"" No
Local Upgrade Form Included? Yes No "U1..4
Telephone#: 91 7 e'- 6 e,7_3 g 2 A , Fax#:
E-mail: 4V S IV A G/c:::r P AZI 2PA J, V e7-
Homeowner
THomeowner
Name: IFL 161704-Ap A14 ti
OFFICE USE ONLY
When the submission is complete (including check):
➢ Date stamp plans and letter
➢ Complete and attach Receipt
➢ Copy File; Forward to Consultant
➢ Enter on Log Sheet and Database
• I
Commonwealth of Massachusetts
City/Town of North Andover
Percolation Test:
Fon,n.:12.
Percola on test results.must be submitted wiflt the-Soil suitability Assessment for On-site Sewage
Disposal DEFT has provided this form.for use by local Boards of Health, Other forms may be used,but
the information must be.substantially the same as that provided here. Beforei using this form,check with
the local Board of Health to determine the form they use.
Important:When A. Site Information
fitlfhg:cutforms
on the'comput&.
useorityrthe tate Michael Dondyat,Thoma"s&Catherine:Dohovart
key,t o move your Owner Name
cursor-do hotS U/✓!� . G r-
use,
use.the return 504 Boxford Street:.Map 105C Lots 41 42 L
_ .
key; Street Address or t of !
North-,Apdover �
.. �...u._.,. ,_:: -
eityrrowr� stati up code
Contact P�sori(if drffereM from t7wner) Telephone Number'
e .. -
^^" t3 . Test Results
1=15'. _...... 11:00 a�rrt�. 1212/15_.__.. 11 oa_a.m�;..
Date- Time Date, rime
Observation Hole It Pers."? Pers 2
Depth of Pere 5&„ 52"
11":19 11:21:
Start Pre-Soars
End Pte-Soak
11:34: _ i 11:36 _-----—
11:34 -- 1
Time..at:12" _ f.36
Time at 9" 1.1: Ei = = 11:38
' - -
1.1:46.
11:4 t
Time at 6" -. . --------- -- ---
Time(9--W) 4:Mins.... 3 Mina.
<.2 Min.11nch: <2 Min.11nch
RateEMirtalnch}
Test Passed; Test.Passed'.
Test Failed: ❑ Test Failed:.
Steve Eriksen
Test Performed By:
Issac Rowe.-North Andover Board of Health
_..-..._.__._.- --. _:...- ----..._�_.. - -- - . - . -...........- _. ..... .__ ..... ........
Board of Healon W7tne3s
Comments:
t5form12.doa 08/15 Perc Test•Page 1 of 1
Commonwealth of Massachooet#s
' — City/Town of[forth Andover
Form 11 - Soil Suitability Assessment for Oft-S�te
SawaOe Disposal
A. Facility Information
Michael Donovan, Thomas&Catherine Donovan
Qwrw Name
500 Boxford Street Map 1050 Lots 41 &42
Street Address Marys of#
North.Andover MA
01845
City State die Gale
B. Site Information
1. (Check one) ® New,.Cormtruction ❑ upgrade ❑ Repair
2. Soil Survey Available?' Yes. [}. No If yes: Web Soil Survey 2538
Sowsaa soil map UMt
Hinckley Loamy Sand Slope&Droughtiness
Sod Name y����l
' SOrI t.11111{�Qns• ..
Glacial Ouhvash Outwash Plain
GedogiclParent:t+Aaterial land.form
3. Surficial Geological Report Available? ❑.Yes ® No. If yes:
Year:Puplished4ourc4 Puglication Scab Map Unit
4. Flood Rate Insurance Map
Above the 500, ear flood poundary? ® Yes ❑ No Withinft 100-year flood baumary? ❑ Yes No
If Yea,continue to Wi,
5. Within a.velocityzpne? [], Yes ® No
MassG.I%�Aletland Data:Layer --
6. Within a Mapped Wetland Area? ❑ Yas: ®.Na wedand Type
7. Current Water Resource Conditions.(t1SGS): 12/15 Range: ❑ AWve Normal ,❑ Normal 23 Wow Normal
MRrrtluYear
8. Other references reviewed:
tWrrnl 1 test 1 and 2•rev.ah 5 Form I I-Sot!Suitability Asse"rnent for On-S"Sewape Dwgmsal •Page t of 8
Commonwealth of W%sachuse#ts,
City/Town of North Andover
Form 11 - Soil Suitability Assessment for On-Sitp S�t�►� e
. Di P .Sal
C. On-Site Review (minimum of two holes
required at
.0 Proposed primary and resent disposal gree)
Deep Obsemation Hole Number. DH71 _12/2115 11:00'a.m: Rain:
Ting aAEeather
I. Location.
Ground Elevation at Surface of Hole- See.Plan
L.atiturJell.ortgitude: 42 40 04N 171 030.6811V
feet
Description of Location: Existing single€arnjly lot -shown on the plan as Lot,1"fest 1
2. Land Use: Cleared backyard area None
(®:g,;woQdlan�l,a6[1Wakt r�l fell a&ant:►4t:efc.)` SursfaM:Stones(e.g;;.cobbles,gWnes,.bqulci�rs,qtc .Slope(°6}
Grass, rubus and multiflora rose Outwash plain Toe810pe.
Vectation Landform
Rositiark qn Landw pa,(SUi.SK 151S,FS,TS)
3. Distances from; Open Water.Body. >50 fL Drainage Watr >50 ft. Wetlands >50 ft
feet .feat leaf
Property trine; >10 ft Drinking Water VVO >10Q ft. Other
feet teat feet
4, Parent Material Glacial Qutwash
.Unsuitable Materials Present- ❑ Yes
No
If Yes: ❑. Qisturbed Soil. ❑ Fill Materia! ❑ Impervious Layer(§) (]. vVeotoerewFrack
.Gtwe'a Rock ❑ Bedro
5- Groundwater Observed: ® Yes ❑ No If':Yes 75" 75"
Cepweeping from,.Rit. Do .5ronaingwaiwin,Hoe
Estimated Depth to High Groundwater 60"
—_
'inches elevayora.
Vormt.1 test 1 ano 2-fey,ail Foran 11—Soil SuitaRifity'A"essment for on
SttQ Sevrage Disposal:•page Z:of 8
Commonwealth of Massachusetts
--r� Gityliown of North Andover
Form 11 Soil. Suitability Assessman#for Qn=Sife So-wage DisPossl
C,.On-$its Review(continued);
Qeep Q04eryatian Hole Number QH-1
( Redoximorphic Features: Coarse fragments
$oil hgnzpn(Soil lfttrtx>Polar- Solt T#4wa° °�'by Yotume. Soil
Qaptl�{in;) Wyor it S440Mre; Consistence .other
111ctii ,�AAuosellj (USDA{ i Gabbles SQ
i
Dept►, Color Fierwrit Crawl;� {Moil t)
0-10" Ap 10.yr 2/2: FSL_ Granylar. Fr!a4te
aW 10 yr 4/4 FSL 1Rlleal4 SloctGy Friahis
7-5 r 6/6. 10% Med.Co � 40°'6, Sin ie Gralrt
1.8-66" C1 2.5y 514 60" y. 9 . : U>ose
66-80" C22.5y 314, 7 5_yr 2/2 15% : l.S*G 30/9. X5°6: Nlaipwiva Finn
i
Additional;Notes:
t5focm4l test 1 and.2•rev:apt Form 1'S-$cil$uilakililY A sesprt►eni fo-Pik. •; wa9e;Qist�os f•..Foes 3:of 8
Comm:onweatth of Massachusetts
JTZ
City/Town of.North Andover
Farm 11 SOR Suitability Assessment for Qty-Site Sewage .[disposal
C. Or -Site Review (continued)
Deep Qbsenratiorn Hote Number: DH-2 1212115 1.1:OU a.m. Rain
Rate. Time weather
1. Location-
Ground Elevation at Surface of Hole See Plan Latitude/Longitude' 42'40"0,4'.'N, / 74'.02'0.68*W
_...__.
feet.
2. Land Use Cleared backyard.area: None,- 0.3%
(e g.,woodland,airicWturai Heid,vacant;tot,et;;). Surface Stoner,-:{a.g. oobOW,.stones;boulderaj_etc.) Slgpo Gam?
Grass;.rubus and multiflora rose Outwash plain Toeslope
vegetation Landform, RositigR ga.LanJrcrapa(S11,$l{,E;S,FS,u
3. Distances:from: Open Walter E$ody >50 ft. Drainage Ways >50 ft.. Wetlands. >50.ft
feet:
few
Property:Line > 10 ft. Drinking Water Well > 100-ft. Qther
feet: few feett
4. Parent.MatleriaG Glacial Dutwash Unsutablie;,GAaterials Present:' ❑ Yes No
If Yes: ❑ Disturbed.Soil ❑ F71:Material ❑:.Impervious: s
P La er Y ( ) 0 VVeatheredfFractured Rock 0 Eledrock
5. Groundwater Qt*erved; Yes ❑ No if yes: 74" 74"
DWth:.Weeping from Pit Depth:Standing-►Ngtgr In tin e
Estimated Depth to.High::Groundweter,.. 54
inches _, elevation
t5form1ltest 1and 2 rev.&15 Fonm1t.—Soti.Suikab�tity:AssessmeptfotQ Sika&ewage;4isppwl "P;age408
Commonweaith_of.Massachusetts
City/Town of Forth Andover
r.
Form 1 tw Soil SUitability Assessmentfor Qin-S 4+rAa Disposal
C- an-Uo Review (continued)
Deep Observation Hale-Number. DH-2
ReclwblmorpttiC Features Coarse,Fragmen
$oil.Horizon!Soil Matrix:Color Sod Taxture IkWI Y914", &oU
Depthts
( ) t ay4r Moist-{Muru911) {l1SDI►}:
Sail St[uctute.Constistencs other
pttt. 091W ercer# ravel blas, :
St4nas.
0-91 Ap 10 yr 2/2 F$L Granular F.riabie
9-20" BW 10 yr 4/4: FSL
Weak-,Blocky Friable
20-88" C17 2.;5y 5 A 54" T;5yr.616 15% CS&G' 30° 15% in9le grain Loose
I
' t
i
A.dditlonal Notes:
t5form1l test 1 and 2 rev.8115. Form 11-Snit Suitability rAsses,6mntfor Qrt-Site Sewage Dispgsa Page 5 0f 8
Gomrnonweaith of M;issachuso is
_ Cityffown of Noo Andover
Fou- 11 Soil Suitability Assessment for On-Site Se. ale Dip.
D. Determirtatioo of'Ki$1h: roundwVar.F.1evation
1; Methoo"'Used Obs. Hole'ADH-1 ObS,H,ple; :pts,-2
® Depth observed standing water irtn:observation:hole 75" 74"
inches indict
Depth weeping from side of observakion hole75" 7'.
niche$ inch"
Depth:to soil redoximQrphic features: (mottles) so° W
4040 inches
L7 Depth to adjusted seasonal high,groundwater(S1)
(USES methodology)
laches _.. . .-_.
Niches,
index.Weik`Number
Reading tate;
Sc-I&x(Qwc—owffw)iowrj
Obsw Hole.# Sc Sr owc :S+n
Wtn>iX owl: Sh
obs. Hole.# s� Sr owe owe Qwr s
E-Depth of Peru out$ Mete ial
1. Depth of Naturally,Occurring
'Flo Material
a, goes at,least four feat of nattiraliy occurring;pervious material exist in all areas obse"Od throughout . 0,1P riaposed for the.soil
absorption:systern?
Yes [] No
b.. if yes,at:what depth was it obserued?. Upper bound aey: '201J: Lower boundary: f8".___�.
inqaiaFhas
c. if nq at what depth waS'impenrious material gbserved? Upper boundary: Lower boundary
t5ftxm1l test 1.and 2•-.rev-8A5 Form,91—Soil SuitsbdityAasessment for on-;kteSswage.
Commonwealth of.Massachusetts.,
--- City/Town of North Andover
Form 11 Soil Suitability Assessment for On-Site. SO
Wzj e Disposal
F. Board of Health Witness
Issac Rowe North:Andover
Name of Roard,.of tieakh,Winess Bq f;Beat!
G. Soil Evaluator Certification
I certify that l am;currently:approvad py the Department af.Enviconmolntal.Prp.WOon pursuan(to X10 CMR 15.017:to.coruiuct soil.
evaluations and that the`above analysis,ha.5 beer:performed by me c onsj§tenf_;vltith thg-segti�red trajnin�;a pefti a and cxp-0 fence
described in,3TO CMR 15.41,7. I; rther'certify'that the tesults.of my soil avA,14ataon,as indiof +ad to t atla.q ted Soil`.Evaluation Form,,
are accurate and in accordance with 31Q CMR 15.100 through 1;5,.107.
12/8/15
Signature.of$ov Eval�atOr [late
Steven.Eriksen 6/30/16.
Typed or Printed:Name.ot Soil Evaluator f License# Expiration Date of t keno
Nuke; In accordance with 31D OMR 1.6.018(2)this fonn,myst be,submi..ed tothe.approving.aWhority within 60 days.of the,date of field testing,and
to thedesigner and:.tkte property owner with Percr3l4in (estcrC,)12
t5.form t 1.test 1 and,2--rev.-.8115 Form 11—&oil.;S,uitattility A,ssessrtrtit f9r:0q5itg SQwage Qisposal •Page 7 of 8_
Commonwealth of Massachusetts
City/Town of North Andover
Form I I . Sell Suitability Assessment for tin-Site Samoage [As.posal
Field Qiagrams
Use this sheetfor field,.diagrams:
t5foffntttest 1 and.2-rev.8/15
fgrm 11,—P,0,Suitiity"AS6essfatenf for Qn^&i ; +�+ 84�ispasal 'Pa9e$'of 8
Gommonweaith of Massachusetts
�T CityfTown of,North Andover
Form 11 - Soil Suitability Assessment for On-S to Sewee Disposal
A. Facility Information
Michael Donovan, Thomas&Catherine.:Donovan
Owner Name
500 Boxford Street Map 105C Lots 41 &42
Street Address MawL.ot#
T _
North.Andover MA 01,845
City :State Zip Code
B. Site.information
1. (Check:one) Q New Construction 0 Upgrade ❑ .Repair
2. Soil Survey:Mailable? ® Yes: ❑ N.o: If yes: Web Soil Survey 253B
Source; soil Map Unit.
Hinckley LoamySand Slope&Droughtiness
Soil Name Soil t andations
Glacial Outwash Outwash Plain
GeologiclParent Material l andfarm
3. Surficial Geological Report AyailaWe?❑ Yes No: If yeS:
Year Pyblish osource Publication Scale MapUnit
4. Flood Rate Insurance Map
Above the 500- ear flood boundary?y ry. �, Yes ❑ No Within the 100-year flood boundary? [] Yes 0 No
If Yes,continue to#5:
5. Within a velocity zone?' ❑ Yes . No
6. Wfithin a Mapped Wgband:.. •. ? M.asAGIS Wetland Data.Layor.;
a ❑ Yes No wetland TYpd --
7. Current Water Resource Conditipns(USGS} 12/15 Range: ❑ Above Normal [] Normal Below Normal'
Manthl.Year
8. Other references reviewed:
t5form 11 test.5 and 6 rev.11116 Form 11—Soil:SuitabilAy A.asessmertt for On-Sits Sewage Disposal.•Page.1 of a
Commonwealth of Massachusetts
4 -- C4iTown of.North Andover
Form 11 - Soil Suitability Assessment for On!,-. ite. Sewage Disposal
C. On-Site Review (minimum of two holes required at every ry
q proposed primary and reserve disposal area,
Peep Qbsecvation Hole.Number: . .DH-S 1212115 11:00 amRain
Qate Tune Weather
1. Location
Ground Elevation at Surface of Hole- Seeee Plan . L.a0tu e/Longitude; 42 40:04N t 7103 0.68W
Description of Location; Existing single family lot-deep hole performed between Test 1.and Test 2
2- Land .Use Cleared backyard area None° 0_3%
(e g, Ymodiand,egfi4ulturAl field,vacant lot,etc:) Surface..S nes(e:g.,.cobbles:stones,boulders,etc;) Slgpe(%)
Grass, rubus and.multiflora rose Outwash plain Toeslope.
Vegetation Landform Posihnn gn 1,4n4cape-M.SK 1 S,.FS.TS)
3. Distances from;. Open 1NAW.Sody° >50 ft. Drainage;Way >80 ft; Wetlands- > 50 ft
teat feet
Property Line > 10 ft Drinking Water Well > 100 ft: Other
feet feet feet
4. Parent Material: Glacial Outwash Unsuit IP..Materials Present: ❑ Yes
No
If Yes: ❑ Disturbed Soil ❑ Fill Material C3. Impervious..Layer(s).
(] Weamered/Fractured-Bock ❑ Bedrock
5. Groundwater Observed: El Yes [] No If-yes-.. 801! 80"
Qepth�Weepin (from Pit Depth Standing Water in Hole
Estimated Depth to High Groundwater:' S4"
inches elevation
t5forml t.test 5.and 6•rev.8115 Fom1 11—Sci{SudabA4 Assessment for On-Sita.$QWage Disposal •Page 2 of 8
Commonwealth of Massachusetts
-� City/Town of North_Andover
Form 11 - Soil Suitability Assessment-forQn-Site Sewage. Disposal
G: On-Site Review(continued)
Reap:ObsErvabon Hole Number DH-5
Rodoximorphi FeaWres �a8
rrwng
Depth tin.fSoil ho rliorg$oil Matrix:Color!- Soil Texture: ? V ta
l
Layer Moist(lllunseli) (uaW►l Soil Structure Consistence, Mar
!Co
pop#' Color Percent Gravel (Moil►
0-8" Ap 10 yr 212 FSI Granular friable
BW 10 yr 4/4 FSI IlVeak:Blocky Friable
1"T' Cl 2.5y 514 54" 7.5yr:6/6 10% m.-c S& 0% ' Singlg.grain, Loam
I _
87-9011, C2 2,5 y:W4 ! 7.5 yr 2J2: 15'k bS.&;G 300/0 1:5%a massi4e- Firm
l
I
Additional.Ngtp.--
t6fonni 1 test 5 and:6•rev,8116 Form 11.—S.oil,Swtaoility Assessment for Qn-- ite$owago Dispp3o •Page 3 of$
Commonwealth of Massachusetts
_ - CitylTown of North Andover
Form 11. - Steil Suitability. Assessment for Qn-Site: Saw
y . D��$��sal
D. Determ;inaVQn of High Groundwater Elevation
1:. Method Used. Obs. Hole#:DH-S O4s.tion#.DH-6
Depth observed standing water.in.observatiom hole
inches - _ ._,. _
inches
® Depth weeping from s de:gf,obsenration hole. 8.o"
lochs& inches
CD.opth to soil redOximorphio.features (mottles)' 54
� $0"
inches incher.
[� Depth.ta adjusted seasonal high,groundwater(Sh)
(U:SGS rr>Qthodalogy)
inches inches
IndexWell Reading Date:
Sh Sc—[S,X:(Qwc—awrr")olwil
Obs. Hole# $c Sr O fs. QllVnsa Uw, Sn
Obs. Hole# Sr; Sr Owe owe ow, SI,
E. Depth of Pervious llefera
4 Depth of Naturally Qccurring Pervious Material.
a. Does at least.four feet.of naturally occulting pervious material exist in all areas observed throughout the area;prpposed for the sail
absorption system?
a Yes ❑ No
b. If yes,at,what,depth was it observed? Uppor bounCary, 18" Lower boundary. 105"
inFt►p& IpFhet
c_, if no,at what depth oras imperuious mate.,a[observed? Upper boundary: Lower boundary:
lathes inches
t5forrn.S:1 test 5 and 6•rev.8115 Form 11,—,S #Suita¢d"try,.
AseSsment for op-Site Seprag ptsposal •Aage:6 of 8
Commonwealth of Massachtito"
Citylrown of North.Andover
Form 1'( - SQiI S>Jitabllity, As assmont for 0n-Sete sewage Disposal
F. Board of Health Witness
issac Rowe _ North Andover Board of Health
Namoc of 134a[d of tloslth witness Baarsi.of Health
G. Soil Evaluator C.ertittcat Qin:
I certify that;l am ourrenPy app 9ved,by'the pe artment of F.,_VIrctntnental Prpt 40A.pursuant to.310::CMR 15.017 to wnduct soil
eveluatigns,artd that the abue,ef> IYi ha .ban performed dY me corrsi�stant With tqe.required tirakiino,.eacpertise:.and eacpa:rienee
described in311?t1NIR;1 017. I f4rfher rerkiijr fhb aha f alts of my snif.aualttati9 ,as rtdi ate l iti ae.aitactied.:Soil EYaluation F�rrn,
are accuratQ.and in acc r ,atldawi
11 4-CM91 10;440 throu.9h
Sipnatute of'Sotl:Evaluator Arte•.'_.._. .
Steven Eriksen. 6/30116
Typed orPrtnuoMame of'401,Evalugi;q Jl,ictense.F E rat-0 Data:oflicense.
Ngta; In:ac natant a with 31q:CMR 10::01.8{2}-this form:must be:spomitted to the approuiN,authority,.wdhin:604ays.cifthe date.of field testing,and
tQ tide Qesign rang the'PrQperty,Q#ner,w.0i' i 6 e, 12
i5formli test land*rev:8/15 Fort>i 11-Soil.Su a0 4y Ass sfn t#QrQn.;�ite$$++�a9q O p�sal •pe9e 7'of.8
andover 1 East River Place
consultants Methuen, Massachusetts 01844
inc. Tel. (978) 687-3828
Fax 978 686-5100
www.andoverconsultants.com
_
May 31, 2016 Cv�
� II-_II ��
UvJ lel, �tN/arts
J
Town of North Andover
Board of Health
1600 Osgood St.
North Andover, MA 01845
RE: Request for Variance
Lot 1 and Lot 2 at 500 Boxford St.
North Andover, Mass.
Dear Members of the Board:
This office represents the three individual owners of three lots at and
adjacent to 500 Boxford Street. The owners are listed below:
Michael Donovan RECEIVE®
12 Johnson Street JUN;
North Andover, MA 01845
TOWN OF NORTH ANDOVER
Thomas Donovan HEALTH DEPARTMENT
5000 Wheatridge Drive
Fuquay-Varina, NC 27526
Cornelius J. Donovan
12 Trolley Car Lane
Londonderry, NH 03053
The property in question has been in the Donovan family since 1946, when
Cornelius and Catherine Donovan, parents of the current owners, purchased
this site containing 5.24 Acres, more or less.
In December of 1970, Catherine Donovan hired Stowers Associates to
survey the land and subdivide it into 4 lots. The subdivision plan was endorsed
by the Planning Board on April 4, 1977 and recorded at the Registry of Deeds
on April 8, 1977. The plan showed Lots A, B, C and D and a copy of the plan is
attached.
Bill/Letters/Town of North Andover—500Boxford.doc
Civil Engineers e Land Surveyors o Land Planners
andover
consultants
inc.
Page 2
Town of North Andover
On January 5, 1992, Catherine Donovan conveyed the lots to her children.
Her daughter, Kathleen Garon, was deeded Lot A. Her sons, Michael Donovan,
Thomas Donovan and Cornelius Donovan were deeded Lots B, C and D
respectively. Each child had expectations of building a house on each of the
lots. In fact, Kathleen built a house on Lot A.
Over the years, since the land was subdivided in 1970, regulations have
changed and become more restrictive. It is now impossible for any of the three
brothers to build on their lot, primarily due to the North Andover Minimum
Requirements for Onsite Wastewater Disposal Systems.
Michael, Thomas and Cornelius Donovan are proposing to reconfigure their
three individually owned lots into two new lots. Based on this new configuration
we have completed percolation tests and test pits for the two lots and have
designed subsurface sewage disposal systems. The designs comply with all of
the requirements of Title 5 and also comply with the North Andover Minimum
Requirements with the exception of the distance to a wetland resource area.
Title 5 requires a 50 ft. setback from a wetland, for which we comply, but North
Andover requires 100 ft. It is this section of the regulations that we request a
variance.
The applicants believe they qualify as seriously aggrieved parties and are
eligible for a variance.
Enforcement of the setback distance provisions in the local requirements
would be manifestly unjust since it would render lot B, owned by Michael
Donovan, and lot D, owned by Cornelius Donovan unbuildable. Lot C contains
an abandoned dwelling and is owned by Thomas Donovan.
Testing has been completed for two newly configured lots. During our field
surveys and testing no soils or site conditions were noted that would be unique
to the Town of North Andover. The conditions observed are similar to those we
have seen in surrounding towns in the Merrimack Valley. Two systems have
been designed to comply with Title 5 and all of the provisions of the North
Andover Requirements with the exception of the distance to wetlands. On lot 1
we can provide 63 ft. and on lot 2 we can provide 65 ft.
Enforcement of the 100 ft. setback distance would render lots B and D
unbuildable and deprive Michael Donovan and Cornelius Donovan of all
beneficial use of their property.
andover
Hants
Page
Page 3
Town of North Andover
By allowing the variance, the brothers can eliminate the existing abandoned
house and it ancient septic system and only two dwellings will be built, with
modern sewage disposal systems.
We appreciate the consideration of the board in this variance request.
Sincerely,
ANDOVER CONSULTANTS I C.
William S. MacLeod, P.E., P.L.S.
President
WSM/an
N O
(/ NORTH ANpOV6R, Mf45S.
Ololutd/��Ltel�+� (1D S u Fr vr. r�-o i
� ONOVl9N
/ef""e�'8� � SGFilE 1"•.yp- sro�.FRs Assn e� r�=.
IJ RtG. Lq Ho Su.a yr 5
O OECE N,gER 19y0 M£rN°/£N, MASs.r
't M-CH /9y'/
O
so
PpFpppdo , rt ,
lhy 50 pND R cNvlpTT NS °'nowwt'R•,STio F.� pF
DFS D9 of TNF Ce T rN p
Mpssp sr r,S-.
On rd GK.P"� Rrc. AP Ne SVMVLroR
\ fIANNING ,APD A:'�-\•••
2 -r— `-, PLANNING BCAi:D CCNTRCL L:•\'. •.�;:i4 AI"J7L°4�l
K O I C`�""�
BY
0.53'2q rE AS TO CONI C- . . y;`I?>BOARD
o Q l
/ M
Of',ll°
.pp 10- wq\ ylm V N-7`•
��ew P.Po In 9gI ,\�\p �A�-• L
ARFA•S8,200 � S• °4 ° N -
w
P y m t
m •LOT C m-
Z
V IN AREA' HG D.50 0 F�
0 7-
�
O / J \ p•
/OHO/
ZW ` --1gN399 � Y9" Sy /o \.,. S3G.a/ x'25,00 /d_yp-1✓I�: NfF CNpR yoTT
v
L4 m Po `' l° � D x S7,
r L L4,
List of Abutters for Notification of Hearing before the North Andover Board of Health for
a variance on 2 lots at 500 Boxford Street.
(This list is a consolidation of 3 lists certified by the Assessor, eliminating duplicates and
the applicants.)
Page 1 of 2
MAP LOT# Name&Address
105.C/5 Brett Rodden
10 Duncan Drive
North Andover, MA 01845
104.B/19 Seon Tae Jeong
50 Duncan Drive
North Andover, MA 01845
104.B/56 Karen Mello
40 Duncan Drive
North Andover, MA 01845
104.B/139 George Adams
1634 Salem Street
North Andover, MA 01845
104.B/171 Paul Schmitt
28 Duncan Drive
North Andover, MA 01845
104.B/174 Gary Wieman
88 Duncan Drive
North Andover, MA 01845
104.B/188 Edward McGetrick
89 Duncan Drive
North Andover, MA 01845
104.B/189 Paul Rabbit
75 Duncan Drive
North Andover, MA 01845
105.C/9 &49 Elsie Pouliot
465 Boxford Street
North Andover, MA 01845
List of Abutters for Notification of Hearing before the North Andover Board of Health for
a variance on 2 lots at 500 Boxford Street.
(This list is a consolidation of 3 lists certified by the Assessor, eliminating duplicates and
the applicants.)
Page 2 of 2
MAP LOT# Name&Address
105.C/22 Messina Development Co. Inc.
277 Washington Street
Groveland, MA 01834
105.C/25 Lauren Cramer
537 Boxford Street
North Andover, MA 01845
105.C/40 Linda Dean
7 Duncan Drive
North Andover, MA 01845
105.C/80 Michelle Pouliot
525 Boxford Street
North Andover, MA 01845
105.C/82 S&L Homes LLC
10-1 Middlesex Avenue
Wilmington, MA 01887
105.C/26 Alexandre Klimenko
545 Boxford Street
North Andover, MA 01845
105.C/27 Justin Motta
577 Boxford Street
North Andover, MA 01845
Abutter to Abutter If ) Building Dept. ( ) Conservation ( ) Zoning ( )
Town of North Andover
Abutters Listing
REQUIREMENT: IVIGL 40A,Section 11 states in part"Parties in Interest as used in this chapter shall mean the petitioner,
abutters,owners of land directly oppositeon any public or private way,and abutters to abutters within
three hundred(300)feet of the property line of the petitioner as they appear on the most recent applicable
tax list,not withstanding that the land of any such owner is located in another city or town,the planning
board of the city or town,and the planning board of every abutting city or town."
Subject Property:
MAP PARCEL Name Address
105.0 41 Michael Donovan 12 Johnson Street North Andover,MA 01845
Abutters Properties (Boxford Street)
Map Parcel Name Address
104.B 19 Seon Tae Jeong 50 Duncan Drive,North Andover,MA 01845
104.6 56 Karen Mello 40 Duncan Drive,North Andover,MA 01845
104.B 139 George Adams 1634 Salem Street,North Andover,MA 01845
104.8 171 Paul Schmitt 28 Duncan Drive,North Andover,MA 01845
104.6 174 Gary Wieman 88 Duncan Drive,North Andover,MA 01845
104.B 189 Paul Rabbitt 75 Duncan Drive,North Andover,MA 01845
105.0 5 Brett Rodden 10 Duncan Drive,North Andover,MA 01845
105.0 9&49 Elsie Pouliot 465 Boxford Street,North Andover,MA 01845
105.0 22 Messina Development Co.lnc 277 Washington Street,Groveland,MA 01834
105.0 40 Linda Dean 7 Duncan Drive,North Andover,MA 01845
105.0 42 Thomas Donovan 5000 Wheatridge Drive,Fuquay-Varina,NC 27526
105.0 43 Cornelius Donovan 12 Trolly Car Lane,Londonderry,NH 03053
105.0 80 Michelle Pouliot 525 Boxford Street,North Andover,MA 01845
105.0 82 S&L Homes LLC 10-1 Middlesex Avenue,Wilmington,MA 01887
This ceilifies that the na'maS appearini;or, `
records lsai- the Asselso 99M M as of
Ccrtifiec hte�-l�/,�
Abutter to Abutter( ) Buildinq Dept. ( ) Conservation ( ) Zoning ( )
Town of North Andover
Abutters Listing
REQUIREMENT: MGL 40A,Section 11 states in part"Parties in Interest as used in this chapter shall mean the petitioner,
abutters,owners of land directly oppositeon any public or private way,and abutters to abutters within
three hundred(300)feet of the property line of the petitioner as they appear on the most recent applicable
tax list,not withstanding that the land of any such owner is located in another city or town,the planning
board of the city or town,and the planning board of every abutting city or town."
Subiect Property:
MAP PARCEL Name Address
105.0 42 Thomas Donovan 5000 Wheatridge Drive,Fuquay-Varina,NC 27526
Abutters Properties (Boxford Street)
Map Parcel Name Address
104.13 19 Seon Tae Jeong 50 Duncan Drive,North Andover,MA 01845
104.13 56 Karen Mello 40 Duncan Drive,North Andover,MA 01845
104.6 139 George Adams 1634 Salem Street,North Andover,MA 01845
104.8 171 Paul Schmitt 28 Duncan Drive,North Andover,MA 01845
104.6 174 Gary Wieman 88 Duncan Drive,North Andover,MA 01845
104.13 188 Edward McGetrick 89 Duncan Drive,North Andover,MA 01845
104.B 189 Paul Rabbitt 75 Duncan Drive,North Andover,MA 01845
105.0 9&49 Elsie Pouliot 465 Boxford Street,North Andover,MA 01845
105.0 22 Messina Development Co.lnc 277 Washington Street,Groveland,MA 01834
105.0 25 Lauren Cramer 537 Boxford Street,North Andover,MA 01845
105.0 40 Linda Dean 7 Duncan Drive,North Andover,MA 01845
105.0 41 Michael Donovan 12 Johnson Street,North Andover,MA 01845
105.0 43 Cornelius Donovan 12 Trolly Car Lane,Londonderry,NH 03053
105.0 80 Michelle Pouliot 525 Boxford Street,North Andover,MA 01845
105.0 82 S&L Homes LLC 10-1 Middlesex Avenue,Wilmington,MA 01887
Thio celtifie� that fihe ra�rt W app Willi or
I-ecordu of the sse rr, a►�� at
C e rtifieddate
Abutter to Abutter( ) Building Dept. ( ) Conservation ( ) Zoning ( )
Town of North Andover
Abutters Ustinq
REQUIREMENT: MGi.40A,Section 11 states in part"Parties in Interest as used in this chapter shall mean the petitioner,
abutters,owners of land directly oppositeon any public or private way,and abutters to abutters within
three hundred(300)feet of the property line of the petitioner as they appear on the most recent applicable
tax list,not withstanding that the land of any such owner is located in another city or town,the planning
board of the city or town,and the planning board of every abutting city or town."
Subiect Property:
MAP PARCEL Name Address
105.0 43 Cornelius Donovan 12 Trolly Car Lane,Londonderry,NH 03053
Abutters Properties (Boxford Street)
Map Parcel Name Address
104.8 189 Paul Rabbitt 75 Duncan Drive,North Andover,MA 01845
105.0 9 Elsie Pouliot 465 Boxford Street,North Andover,MA 01845
105.0 22 Messina Development Co.lnc 277 Washington Street,Groveland,MA 01834
105.0 25 Lauren Cramer 537 Boxford Street,North Andover,MA 01845
105.0 26 Alexandre Klimenko 545 Boxford Street,North Andover,MA 01845
105.0 27 Justin Motta 577 Boxford Street,North Andover,MA 01845
105.0 40 Linda Dean 7 Duncan Drive,North Andover,MA 01845
105.0 41 Michael Donovan 12 Johnson Street,North Andover,MA 01845
105.0 22 Tohmas Donovan 5000 Wheatridge Drive,Fuquay-Varina,NC 27526
105.0 80 Michelle Pouliot 525 Boxford Street,North Andover,MA 01845
105.0 82 S&L Homes LLC 10-1 Middlesex Avenue,Wilmington,MA 01887
105.0 83 James Santoianni 550 Boxford Street,North Andover,MA 01845
Thin WOOS that thP-"Mat'a ,P63r+�i on d*
records of the A e8s as of
Certified b. date �6
North Andover Health Department
(ommunity and Economic Development Division
October 7, 2016
Michael Donovan Cornelius Donovan
12 Johnson Street 12 Trolley Car lane
North Andover, MA 01845 Londonderry,NH 03053
Thomas Donovan
5000 Wheatridge Drive
Fuquay-Varina,NC 27526
Re: Subsurface Sewage Disposal System Plan for 500 Boxford Street—Lot 1
(Map 105C,Lot 42)
To Whom It May Concern:
- The proposed wastewater system design plan for the above site dated May 24, 2016 with a final
revision date of August 17, 2016 and received on August 18, 2016 has been approved subsequent
to the Public Hearing on September 13, 2016. Your variance request from the North Andover
Septic Regulations, Section 3.9 has been approved and the setback from the soil absorption
system has been reduced from 100' to 73.7'.
The design has been approved for use in the construction of a new on-site septic system for a 4-
bedroom (maximum of 9 total rooms) home utilizing a gravity leach field system. This design
plan approval is valid until October 7, 2019.
During this time, a licensed septic system installer must obtain a permit and complete this work,
and a Certificate of Compliance be endorsed by the installer, designer and the Town of North
Andover.
This approval is also subject to the following conditions:
1. Prior to the issuance of the Disposal Works Construction Permit,the applicant must
submit a foundation as-built at the same scale as the approved plan
Page 1 of 2
North Andover Health Department, 1600 Osgood Street, Suite 2035
North Andover, MA 01845 Phone: 978.688.9540 Fax: 978.688.8476
500 Boxford Street—Lot 1 October 7, 2016
2. Prior to the issuance of the Disposal Works Construction Permit,the applicant must
submit the floor plans of the proposed dwelling showing no greater than 4 bedrooms
or a total of 9 rooms.
3. If site conditions are found in the field to be different from those indicated on the
design plan and/or soil evaluation, the originally issued Disposal System Construction
Permit is void, installation shall stop, and the applicant shall reapply for a new
Disposal Systems Construction Permit(3 10 CMR 15.020(1)).
4. It is the responsibility of the applicant and/or the applicant's septic system designer,
septic system installer or other representative to ensure that all other state and
municipal requirements are met. These may include review by the Conservation
Commission, Zoning Board, Planning Board, Building Inspector, Plumbing Inspector
and/or Electrical Inspector. The issuance of a Disposal System Construction Permit
shall not construe and/or imply compliance with any of the aforementioned
requirements.
Please feel free to contact the office with any questions you may have. We look forward to
working with you to obtain a wastewater treatment and dispersal system which will be in
compliance with all regulations and assure protection of public health and the environment of
North Andover.
Sincere ,
.�
Wan J. aGrasse, CEHT
Director of Public Health
Encl. Installers list
cc: William McCloud,Andover Consultants
File
Page 2 of 2
North Andover Health Department, 1600 Osgood Street, Suite 2035,
North Andover, MA 01845 Phone: 978.688.9540 Fax: 978.688.8476
Blackburn, Lisa
From: Gaffney, Heidi
Sent: Monday,August 17, 2015 8:44 AM
To: Blackburn, Lisa
Subject: FW: 500 Boxford St-test pit applications
From: Gaffney, Heidi
Sent: Thursday, August 13, 2015 1:22 PM
To: 'James Fairweather'
Subject: FW: 500 Boxford St -test pit applications
Hi Jim, I should have added first that the test pit locations as currently proposed will require a filing, but if moved to
more than 75'from the wetland/ephemeral pool habitat then I can sign off without a filing.
Heidi Gaffney
Conservation Field Inspector
Town of North Andover
1600 Osgood Street,Suite 2035
North Andover,MA 01845
Phone 978-688-9530
Fax 978-688-9542
Email hgaffnev@townofnorthandover.com
Web www.TownofNorthAndover.com
s,rearn,ry .
From: Gaffney, Heidi
Sent: Thursday, August 13, 2015 11:48 AM
To: 'James Fairweather'
Subject: 500 Boxford St- test pit applications
Hi Jim, I took a look at the test pit applications and believe that there is ephemeral pool habitat in this area,which will
require the test pits to be at least 75'from the wetland. Please revise the sketch to show that the test pits are at least
75'from the wetland and then I can sign off on them. You may want to consider an ANRAD to have the wetlands
reviewed?
Heidi Gaffney
Conservation Field Inspector
Town of North Andover
1600 Osgood Street,Suite 2035
North Andover,MA 01845
Phone 978-688-9530
Fax 978-688-9542
Email hgaffnev@townofnorthandover.com
Web www.TownofNorthAndover.com
1
andover 1 East River Place
consultants Methuen, Massachusetts 01844
Inc. Tel. (978) 687-3828
Fax 978 686-5100
www.andoverconsultants.com
July 1, 2015
Michele Grant, Health Inspector
North Andover Board of Health
1600 Osgood Street, Bldg 20, Unit 2035
North Andover, MA 01845 RECEIVED
Jul- 0 6 2015
RE: Concept Plan 7OWN OF NORTH ANDOVER
500 Boxford Street HEALTH DEt ARTMENT
North Andover,MA
Dear Ms. Grant:
Per your telephone conversation with Bill MacLeod on Tuesday June 30, 2015, I have attached a
concept plan for your review. The plan depicts three existing lots at and adjacent to 500 Boxford
Street and a plan depicting a proposal to reconfigure the parcels into just two lots. In the
proposed condition, the existing dwelling will be demolished and two new dwellings
constructed. The proposal will require a variance from the Board of Health to permit
construction of the two soil absorption systems fifty feet from a wetland where 100 feet is
required. Mr. MacLeod wishes to meet with you to discuss the concept and to obtain your
opinion as to how the Board will react to the proposal.
If you have any questions, feel free to contact our office at your convenience.
Sincerely,
ANDOVER CONSULTANTS,INC.
James S. Fairweather 11, P.E.
Civil Engineer
Enclosure
Civil Engineers • Land Surveyors • Land Planners
Grant, Michele
From: Grant, Michele
Sent: Wednesday,July 08, 2015 12:04 PM
To: Gaffney, Heidi
Cc: Blackburn, Lisa
Subject: 500 Boxford street
Attachments: 201507081211.pdf
Hi,
Please see the attached letter from Andover Consultants.
As per our conversation regarding 500 Boxford street. Its 3 lots. One lot has a house on it. They are reconfiguring down
to 2 lots and 2 houses.They want to put the systems 50 ft from the wetland. They don't want to spend any money if
they don't have a shot of building. I spoke to Bill MacLeod today and he said he was going to have a conversation with
Jen.
Thx
Michele E. Grant
Public Health Agent
Town of North Andover
1600 Osgood St I Suite 2035
North Andover, MA 01845
Phone 978.688.9540
Fax 978.688.8476
Email mgrant@townofnorthandover.com Web www.TownofNorthAndover.com
-----Original Message-----
From: noreply@townofnorthandover.com [ma iIto:noreply@townofnorthandover.coml
Sent:Wednesday,July 08, 2015 12:12 PM
To: Grant, Michele
Subject: Message from "ComDev-Health-Ricoh"
This E-mail was sent from "ComDev-Health-Ricoh" (Aficio MP C3002).
Scan Date:07.08.2015 12:11:56 (-0400)
Queries to: noreply@townofnorthandover.com
1
NOTICE OF REQUEST FOR VARIANCE
AND PUBLIC HEARING AT NORTH ANDOVER
BOARD OF HEALTH
Notice is hereby given that the North Andover Board of Health will hold a Public hearing on
June 28, 2016, at 7:00 p.m. in the Community Room of the North Andover Police Dept.,
1475 Osgood Street,North Andover,Mass. upon the petition of Michael Donovan,
Thomas Donovan and Cornelius J. Donovan.
The applicants have requested a variance from the North Andover"Minimum Requirements
For The Design, Construction And Maintenance Of Onsite Wastewater Treatment And Disposal
Systems"
Plans have been prepared for the design of sewage disposal systems for 2 lots.
The designs comply with all of the requirements of Title 5 and also comply with the North
Andover Minimum Requirements with the exception of the distance to a wetland resource area.
Title 5 requires a 50 ft. setback from a wetland, for which the plans comply, but North Andover
requires 100 ft. It is this section of the regulations that a variance is requested.
The applicants believe they qualify as seriously aggrieved parties and are eligible for a
variance.
Enforcement of the setback distance provisions in the local requirements would be
manifestly unjust since it would render land owned by Michael Donovan and land owned by
Cornelius Donovan unbuildable and deprive Michael Donovan and Cornelius Donovan of all
beneficial use of their property.
Plans and forms submitted may be viewed at the Health Department office at 1600
Osgood Street,North Andover, MA during regular business hours.
If you have any questions, you may also contact the applicants engineer,
William S. MacLeod, at Andover Consultants Inc., tel 978-687-3828, ext. 11.
I
Legal/Notice of Request for Variance-Donovan.doc