Loading...
HomeMy WebLinkAboutMiscellaneous - Exception (452)SEWAGE PUMP STATION DESIGN COMPUTATIONS DIA (IN) Job No. 9302 . For: Michael & Elaine Morgil/o Calculated by: CRO Date: 02/28/2002 Checked by: VVT 5.0 CALCULATE EQUIVALENT LENGTH: 10.0 FT FRICTION LOSSES IN PUMP CHAMBER: 2 2.5 QTY DIA (IN) LOSS/FITTING (FT) FITTING TOTAL FT 1 2 5.0 900 BEND 5.0 FT 0 2 2.5 450 BEND 0.0 FT 1 .. 2 14.0 CHECK VALVE 14.0 FT 1 2 1.2 GATE VALVE 1.2 FT TOTAL LOSS b 21.0 FT 1 20.2 FT FRICTION LOSSES IN, -PIPE RUN: QTY DIA (IN) LOSS/FITTING (FT) FITTING TOTAL Hs 2 2 5.0 900 BEND 10.0 FT 2 2 2.5 450 BEND 5.0 FT 0 2 2.0 22.50 BEND 0.0 FT 1 2 12.0 TEE (Side In/Out) 12.0 FT 17.4 25 2.6 LENGTH OF RUN 95.0 FT 18.8 30 3.1 MISC. PIPE 9.5 FT TOTAL LOSS 35 3.6 132.0 FT 131.5 FT TOTAL.EQUIV. LENGTH: -� I 153 FT SYSTEM CURVE: Q V HF/100 HF Hs TDH GPM FPS FT FT FT FT 10 1.0 0.5 0.77 14.57 15.3 15 1.5 1.1 1.64 14.57 16.2 20 2.0 1.8 2.79 14.57 17.4 25 2.6 2.8 4.21 14.57 18.8 30 3.1 3.9 5.90 14.57 20.5 35 3.6 5.1 7.85 14.57 22.4 40 4.1 6.6 10.05 14.57 24.6 45 4.6 8.2 12.50 14.57 1 27.1 Page 3 9302SDSrev.xls