Loading...
HomeMy WebLinkAboutMiscellaneous - Exception (455)SEWAGE PUMP STATION DESIGN COMPUTATIONS Job No. 9302 For: Michael & Elaine Morgillo Calculated by: CRO Date: 02/28/2002 Checked by: VVT CALCULATE EQUIVALENT LENGTH: FRICTION LOSSES IN PUMP CHAMBER: QTY DIA (IN) LOSS/FITTING (FT) FITTING TOTAL HS 1 2 5.0 900 BEND 5.0 FT 0 2 2.5 450 BEND 0.0 FT 1 1 , 2 14.0 CHECK VALVE 14.0 FT 1 2 1.2 GATE VALVE 1.2 FT TOTAL LOSS 25 b 21.0 FT 1 20.2 FT FRICTION LOSSES IN PIPE RUN: QTY DI_ A (IN) LOSS/FITTING (FT) FITTING TOTAL HS 2 2 5.0 900 BEND 10.0 FT 2 2 2.5 450 BEND 5.0 FT 0 2 2.0 22.5° BEND 0.0 FT 1 2 12.0 TEE (Side In/Out) 12.0 FT 17.4 25 2.6 _ LENGTH OF RUN 95.0 FT 18.8 30 3.1 MISC. PIPE 9.5 FT TOTAL LOSS _ 35 6 132.0 FT 7.85 131.5 FT 40 TOTAL EQUIV. LENGTH: b b 1 153 FT SYSTEM CURVE: Q V HF/100 HF HS TDH GPM j FPS FT FT FT FT 10 ; 1.0 0.5 0.77 14.57 15.3 15 1.5 j 1.1 j 1.64 j 14.57 16.2 20 ! 2.0_ 1 1.8 I 2.79 14.57 17.4 25 2.6 _ 2.8 T4.2 14.57 18.8 30 3.1 j 3.9 i 5.90 j 14.57 20.5 _ 35 6 5.1 7.85 ( 14.57 22.4 40 4.1 i 6.6 10.05 i 14.57 j 24.6 45 I 4.6 j 8.2 I 12.50 14.57.11 27.1 Page 9302SDSrev.xis