HomeMy WebLinkAboutMiscellaneous - Royal Crest Bldg 15-11I -11u, -) v P� j S�-7 m35� ef a i 7j 1, T i SMITH & WESSEL ASSOCIATES, INC. HAZARDOUS BUILDING MATERIALS AND AIR QUALITY SPECIALISTS September 16, 2015 Mr. Jason Cael, Service Manager Royal Crest Estates 50 Royal Crest Drive North Andover, MA 01845 Re: Visual Mold and Moisture Assessment, Royal Crest Estates, Unit 15-011, North Andover, MA Dear Mr. Cael: Introduction Apartment Investment and Management Company (AIMCO) retained Smith & Wessel Associates, Inc. (SWA) to perform a visual mold and moisture assessment in Unit 15-011, and in the front stairwell and laundry room of Building 15 at the . Royal Crest Estates apartment complex located at 50 Royal Crest Drive in North Andover, Massachusetts. Eric Hanson, SWA's Certified Indoor Environmentalist, performed the assessment on September 16, 2015. The assessment was conducted in response to the tenant's concern about visible mold in the stairwell and laundry room, and potential mold found on oven mitts stored under the kitchen sink in Unit 15-011. Because elevated moisture is one of the leading causes of fungal amplification, contributes to the destruction of indoor building products, and can lead to the deterioration of buildings, SWA conducted testing of various building materials using a Protimeter Surveymaster moisture meter. The Surveymaster is a conductance type meter that uses a two -pin inspection mode enabling the consultant to instantly assess moisture conditions not only on a component surface, but also at depth. The Surveymaster identifies by means of green, yellow, and red LEDs whether a surface is in an air-dry (0-18%), borderline (18-22%), or damp condition (>22%) and quantifies this condition in terms of percent wood -moisture -equivalent (%WME). 188 GREENVILLE STREET TELEPHONE: (978) 346-4800 SPENCER, MA 01562 FAX: (978) 346-7265 Findings Visible mold was confirmed on sheet rock walls and on wallpaper backing in both the laundry room and stairwell. However, moisture readings taken in those locations showed that the materials were in an air dry condition (less than 18% WME) and thus, not generally conducive to further mold growth. Because moisture levels were low and no mold -related damage to the walls was observed, the sheet rock can be cleaned with a bleach and water solution or with an anti- microbial agent, such as ShockWaveTM RTU (Shockwave), and then allowed to fully dry. Shockwave is an EPA -registered disinfectant, sanitizer and cleaner designed specifically for mold remediation contractors. When the walls are dry they can then be painted with a mold -inhibiting paint. The affected wallpaper should be completely removed and discarded. Moisture levels throughout Unit 15-011 were all less than 10% WME. There was no indication of water damage, musty odors, or other conditions that would indicate that there are any mold -related issues within the apartment. As a precaution, a small spot on the wood in the cabinet beneath the kitchen sink should be cleaned as outlined above, even though there was no indication that the spot was mold. Should you have any questions or concerns please do not hesitate to contact me. Respectfully submitted, SNnN & f zwex Awomnw /NC. Eric Hanson Certified Indoor Environmentalist Sknu & if+6S u Asvoc nw, /IVC Page 2 SWA 15365 9/16/15 Appendix A Photographs Smfm s WE&= AStsMMnX, INC SWA 15365 Page 3 .9/16/15 Building 15 Stairwell Building 15 Laundry Room Grant, Michele From: Sawyer, Susan Sent: Monday, September 14, 2015 12:34 PM To: Grant, Michele Subject: FW: Chronic Mold Problem at Royal Crest Attachments: Mold_Buildingl5_Hallway_Black_Mold_Closeup jpg; Mold_Buildingl5 _Hal lway_Black_Mold_2jpg; Mold_Buildingl5_Hallway jpg; Mold_Building15 -Lau ndry_Room_Black_Mold_Closeup jpg; Mold_Buildingl5_Laundry_Roomjpg; Mold_Apartmentll_Kitchen jpg; Mold_Apartmentll_Kitchen_Sink jpg From: Ashley Haskell [mailto:ashley617(agmail.com] Sent: Monday, September 14, 2015 12:31 PM To: Sawyer, Susan Cc: mathew.bynum(a aimco.com; Vandal, Alise; Laura Callahan Subject: Chronic Mold Problem at Royal Crest Good Afternoon Mrs. Sawyer, I am writing in regards to a chronic mold problem here at Royal Crest. My son and I had gotten mold so bad in our previous apartment at Royal Crest that they moved us to a hotel, for five months, and then Royal Crest moved us to a completely different building, where we now have mold again. The black mold appears to be in the hallway and laundry room of Building 15, and it is in my actual apartment in the kitchen of unit 11. I have attached pictures of the hallway and the laundry room of Building 15, and the kitchen in my apartment. I am asking that you please send out an inspector to test the mold because I cannot afford to have my son or I get sick, be displaced, or lose any of our belongings again. I realize your time is valuable and I appreciate you getting back to me when you can. Thank you, Ashley Haskell 1 d _ s _ _ , • Ts 3� CIA - • , 9i Wit " g , , ¢ x � i ,,�„ w •-it'll - i a s:, ' d � a r , a s , I `4g 5, a ,c oil r 17. _ x x ff x. d i a � e s, -WAN"IN iii Ot a z +j .. c Yr n, Of 3.z 4 � x I F x k P _ # 4 ! e - it �L. Via• . �I R -z i� 4 d � 'j 4 YA; t 4 I Ili ji li THE NTERNATIONAL MAWW. 7��"WiWffMvW01MFJhTM=IAiMFM THE PINES: THE OAKS: designed by Geoffrey Cornish & Robert Trent Jones, Sr. = designed by Tom Fazio RESERVATIONS: (978) 779-6919 GOLF SHOP: (978)779-6910 CONFERENCE CENTER AND GUEST LODGE fax (978) 779-0231 fax (978)779-0273 fax (978)779-0292 159 Ballville Road • Bolton, MA 01740-1227 • (978) 779-6911 • www. the internationaI.co n home of the World's Longest Golf Course 8,325 yards