HomeMy WebLinkAboutREScheck Compliance Certificate REScheck Software i .
Compliance Certificate
Project Proposed New Residence - Lot 3, 303 Abbott Street
Energy Code: 2009 1ECC
Location: North Andover, Massachusetts
Construction Type: Single-family
Project Type: New Construction
Conditioned Floor Area: 2,533 ft2
Glazing Area 11%
Climate Zone: 5
Permit Date:
Permit Number:
Construction Site: Owner/Agent: Designer/Contractor:
303 Abbott Street, Lot 3 Chris Poravas
North Andover, MA Poravas Design &Consulting
49 Appleton Street
Melrose, MA 02176
339-927-1579
pdcdesignl@gmail.com
Compliance: 1.1%Better Than Code Maximum UA: 368 Your UA: 364
The%Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home.
Envelope Assemblies
Floor 1: All-Wood joist/Truss:Over Unconditioned Space 1,107 30.0 0.0 0.033 37
Floor 2: All-Wood jo I st/Truss:Over Unconditioned Space 365 30.0 0.0 0.033 12
Floor 3:All-Wood joist/Truss:Over Outside Air 13 30.0 0.0 0.033 0
Ceiling 1: Flat Ceiling or Scissor Truss 1,335 38.0 0.0 0.030 40
Ceiling 3: Cathedral Ceiling 150 30.0 0.0 0.034 5
Wall 1: Wood Frame, 16" o.c. 2,863 21.0 0.0 0.057 142
Window 1: Wood Frame:Double Pane with Low-E 307 0.290 89
Door 1: Solid 33 0.500 17
Door 2: Solid 36 0.600 22
Compliance Statement: The proposed building design described her y9 EDA t uilding plans, specifications, and other
calculations submitted with the permit application.The proposed bu 4M. It to meet the 2009 IECC requirements in
REScheck Version 4.5.0 and to comply with the mandatory require r�Es i ed in the `k Inspection Checklist.
0.505 /
Name-Title Sign MASS. �� Date
c2�F�CTM OF MP�����
Project Title: Proposed New Residence - Lot 3, 303 Abbott Street Report date: 11/24/1
Data filename: C:\01-Projects\Residential\Corcoran-North Andover\10-Energy Audits\Abbott- Lot 3.rck Page 1 of 9
Project Title: Proposed New Residence- Lot 3, 303 Abbott Street Report date: 11/24/1
Data filename: C:\01-Projects\Residential\Corcoran-North Andover\10-Energy Audits\Abbott- Lot 3.rck Page 2 of 9
����� �� � Version
� � �
�uv��� ����Y��� ��U��
�"�= = �� _="��� �
� �
� �� Checklist��
� N����N�����= Q������ ���������� � ���0= �
Energy Code: 2009 IECC
Requirements: 0.0Y6 were addressed directly in the RESchecksoftware
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
Is being claimed. Where compliance is itemized in a separate table, a reference tothat table is provided.
Section Plans Verified Field Verified
# Pre-inspection/Plan Review Value Value Complies? Comments/Assumptions
103.2 Construction drawings and fiComplies
[PR111 documentation demonstrate E]Does Not
I energy code compliance for the
EINot Observable
building envelope.
!E]Not Applicable
103.2, :Construction drawings and jElComplies
403.7 documentation demonstrate ElDoes Not
[PR311 energy code compliance for
�E]Not Observable
-0) Jighting and mechanical systems.
Systems serving multiple tlNot Applicable
:dwelling units must demonstrate
compliance with the commercial
403.6 Heating and cooling equipment is Heating: Heating: ElComplies
[PR2]2 sized per ACCA Manual S based Btu/hr Btu/hr
ElDoes Not
!on loads per ACCA Manual J or Cooling: Cooling: �E]Not Observable
14 other approved methods.
Btu/hr— Btu/hr
E]Not Applicable
Additioma[ Cmmmmnmmts/Assmmnpt1oms:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low impac-t-(-Tier-3)---]
Project Title: Proposed New Residence Lot 3, 303 Abbott Street Report date: 1I/24/1
Data filename: C:\0l'Pro]ect$Res|denda|\Corcoran'NorthAndover\lO-EnergyAudits\Abbott- Lot 3.rck Page 3of A �
�
_T
2009 IECC Foundation Inspection Complies? Comments/Assumptions
30 A protective covering is installed to ;❑Complies
[Ft`J1�j�' �protect exposed exterior insulation �❑Does Not
I and extends a minimum of 6 in. below ;❑Not Observable',
grade.
j❑Not Applicable
4F Snow-and ice-melting system controls ❑Complies
�F(��� z )Installed. ❑Does Not
r
❑Not Observable;
j❑Not Applicable
Additional Comments/Assumptions:
i
I
11 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Proposed New Residence- Lot 3, 303 Abbott Street Report date: 11/24/1
Data filename: C:\01-Projects\Residential\Corcoran-North Andover\10-Energy Audits\Abbott- Lot 3.rck Page 4 of 9
Section Plans Verified Field Verified
# Framing/ Rough-In Inspection Value Value Complies? Comments/Assumptions
& Req.ID
402.1.1, Door U-factor, U- U- ❑Complies ;See the Envelope Assemblies
402.3.4 ,❑Does Not
:table for values.
[FR1]1 ❑Not Observable
P
" ❑Not Applicable
402.1.1, Glazing U-factor(area-weighted U- U- ;❑Complies ;see the Envelope Assemblies
402.3.1, average). ❑Does Not table for values.
402.3.3,
402.5
❑Not Observable
[FR2]1 ;❑Not Applicable
i
303.1.3 U-factors of fenestration products` t❑Complies
[FR411 :are determined in accordance flDoes Not
(with the NFRC test procedure or
110 ;taken from the default table. ❑Not Observable
❑Not Applicable
402.3.5 Sunrooms enclosing conditioned U- U- ❑Complies
[FR8]1 (space have a maximum ❑Does Not
p jfenestration U-factor of 0.50 in j❑Not Observable
Climate Zones 4-8. New glazing E❑Not Applicable
:separating the sunroom from
P
conditioned space must meet
:code requirements.
402.3.5 Sunrooms enclosing conditioned U- U ❑Complies
[FR9]1 :space have a maximum skylight ❑Does Not
U-factor of 0.75 in Climate Zones
4-8 : ❑Not Observable
❑Not Applicable
402.4.4 Fenestration that is not site built 1 l❑Complies
[FR20]1 is listed and labeled as meeting ( j❑Does Not
10, �AAMA/WDMA/CSA 101/LS.2/A440 $
or has infiltration rates per NFRC ❑Not Observable
400 that do not exceed code i �❑Not Applicable
,
limits, r
402.4.5 IC-rated recessed lighting fixtures; {❑Complies
016,12 !sealed at housing/interior finish r �❑Does Not
!and labeled to indicate-2.0 cfm
leakage at 75 Pa, l❑Not Observable
❑Not Applicable
403.2.1 ;,Supply ducts in attics are ; R- R- ;❑Complies
[FR12]1 insulated to >_R-8.All other ducts ' R_ R_ ❑Does Not
in unconditioned spaces or j
outside the building envelope are ;❑Not Observable
i Insulated to >_R-6. ;❑Not Applicable
403.2.2 ;All joints and seams of air ducts, fi❑Complies
[FR13]1 :air handlers,filter boxes, and l❑Does Not
:building cavities used as return
' �E]Not Observable
:ducts are sealed. I
❑Not Applicable
403.2.3 Building cavities are not used for ❑Complies
[FR15]3 supply ducts. ❑Does Not
1❑Not Observable
bNot Applicable
403,E HVAC piping conveying fluids R-
R- ;,E]Complies
[FR'I712 above 105°F or chilled fluids ! ;❑Does Not
below 55 °F are insulated to >_R-
4 ?3 ;❑Not Observable
❑Not Applicable
403,4 ;Circulating service hot water R- R- ❑Complies
[FRl8]2 pipes are insulated to R-2. : ❑Does Not
;
' '❑Not Observable
❑Not Applicable
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Proposed New Residence- Lot 3, 303 Abbott Street Report date: 11/24/1
Data filename: C:\01-Projects\Residential\Corcoran-North Andover\10-Energy Audits\Abbott- Lot 3.rck Page 5 of 9
Section Plans Verified Field Verified
# Framing /Rough-In Inspection Value Value Complies? Comments/Assumptions
& Req.ID
4153,5 !Automatic or gravity dampers are ❑Complies
1 Et19z installed on all outdoor air ;❑Does Not
�y intakes and exhausts.
0
i -i'❑Not Observable
( �❑Not Applicable
Additional Comments/Assumptions:
it
1 High Impact(Tier 1) 2Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Proposed New Residence- Lot 3, 303 Abbott Street Report date: 11/24/1
Data filename: C:\01-Projects\Residential\Corcoran-North Andover\10-Energy Audits\Abbott- Lot 3.rck Page 6 of 9
Section Plans Verified Field Verified
# Insulation Inspection Value Value Complies? Comments/Assumptions
& Req.ID
031 ;All installed insulation is labeledg t❑Complies
[IN131 or the installed R-values y T❑Does Not
i provided.
I a o❑Not Observable
❑Not Applicable
402.1.1, Floor insulation R-value. R- R- ;❑Complies ;See the Envelope Assemblies
402.2.5, ❑ Wood ❑ Wood ❑Does Not table for values.
402.2.6 ❑ Steel ❑ Steel ;❑Not Observable
[IN1]1
;❑Not Applicable
303.2, ;Floor insulation installed per �❑Complies
402.2.6 ^manufacturer's instructions, and ❑Does Not
[IN2]1 in substantial contact with the
underside of the subfloor, ; ❑Nat Observable
I❑Not Applicable
402.1.1, :Wall insulation R-value. If this is a: R- R- ❑Complies ;See the Envelope Assemblies
402.2.4, mass wall with at least 1/z of the ❑ Wood ❑ Wood o❑Does Not table for values.
402.2.5 ;wall insulation on the wall 1❑ Mass ❑
[IN3]1 exterior, the exterior insulation Mass ❑Not Observable
p 1 requirement applies. ❑ Steel ❑ Steel ❑Not Applicable
o
l
303.2 Wall insulation is installed per i❑Complies
[IN4]1 manufacturer's instructions. n I❑Does Not
I f UNot Observable
❑Not Applicable
402.2.11 ;Sunroom wall insulation has a R- R- ;❑Complies
[IN8]1 I minimum R-value of R-13. New ❑Does Not
;walls separating the sunroom 1
!from conditioned space must ;❑Not Observable a
meet code requirements. ;❑Not Applicable
303.2 ;Sunroom wall insulation installed �❑Complies
[IN9]1 :per manufacturer's Instructions. ( ;❑Does Not
1
❑Not Observable
t❑Not Applicable
402.2.11 Sunroom ceiling minimum R- R- ;❑Complies
[IN10]1 I insulation R-value of R-19 in ❑Does Not
;Climate Zones 1-4, and R-24 in
10-11 ,Climate Zones 5-8.
I ;❑Not Observable ;
❑Not Applicable
303.2 ;Sunroom ceiling insulation is ;❑Complies
[IN11]1 installed per manufacturer's ❑Does Not
Instructions.
(❑Not Observable
1 Q �❑Not Applicable
Additional Comments/Assumptions:
1 1 High Impact (Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Proposed New Residence - Lot 3, 303 Abbott Street Report date: 11/24/1
Data filename: C:\O1-Projects\Residential\Corcoran-North Andover\10-Energy Audits\Abbott- Lot 3.rck Page 7 of 9
Section Plans Verified Field Verified
# Final inspection Provisions Value Value Complies? Comments/Assumptions
& Reci.ID
402.1.1, ;Ceiling insulation R-value.Where R- R- ;❑Complies ;see the Envelope Assemblies
402.2.1, > R-30 is required, R-30 can be ❑ Wood ❑ Wood ❑Does Not table for values.
402.2.2 ,used if insulation is not
[Fill' compressed at eaves. R-30 may ;E] Steel ❑ Steel !❑Not Observable
p be used for 500 ftz or 20% ;❑Not Applicable
(whichever is less)where
!sufficient space is not available.
303.1.1.1, ,Ceiling Insulation installed per $ i❑Complies
303.2 manufacturer's instructions. t ❑Does Not
[FI21' Blown insulation marked every
Itip 1300 ft2. ❑Not Observable
j t❑Not Applicable
402.2.3 ;Attic access hatch and door R- R- ❑Complies
[FI3]' !insulation ?R-value of the :❑Does Not
adjacent assembly. j
❑Not Observable
❑Not Applicable
402.4.2, ;Building envelope tightness ACH 50 = ACH 50 = {❑Complies
402.4.2.1 !verified by blower door test result: ❑Does Not
[FI17]' of<7 ACH at 50 Pa.This
!requirement may instead be met ❑Not Observable
,via visual inspection, in which ❑Not Applicable
case verification may need to
,occur during Insulation
Inspection.
40 .4 I'Wood burning fireplaces have i {❑Complies
(FI$]2 �gasketed doors and outdoor I E❑Does Not
combustion air. 5 ❑Not Observable
� f
t❑Not Applicable
403.2.2 Post construction duct tightness cfm cfm ❑Complies
[FI4]' :test result of:58 cfm to outdoors, ;❑Does Not
or<12 cfm across systems. Or,
'❑Not Observable
rough-in test result of<6 cfm
,across systems or_<4 cfm ❑Not Applicable
:without air handler. Rough-in test; !
:verification may need to occur !
:during Framing Inspection. ! !
403.1„l Programmable thermostats ❑Complies
[Fl9]2 installed on forced air furnaces. Q ❑Does Not
l ;❑Not Observable
El Not Applicable j
40 ,1.2 ;Heat pump thermostat installed ; ❑Complies
[FIx0]
on heat pumps. o ❑Does Not
❑Not Observable
5 t❑Not Applicable
40$.4 }Circulating service hot water o �❑Complies
[F111"] !systems have automatic or �❑Does Not
!accessible manual controls.
t❑Not Observable
a I T❑Not Applicable
403.9.1 j Readily accessible switch on ❑Complies
[FI12]3 heaters for swimming pools. ;❑Does Not !
y❑Not Observable
�E]Not Applicable
403.9,2 ,Timer switches on pool heaters {❑Complies
[FI19]3 :and pumps are present. ❑Does Not
❑Not Observable
❑Not Applicable
11 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Proposed New Residence- Lot 3, 303 Abbott Street Report date: 11/24/1
Data filename: C:\O1-Projects\Residential\Corcoran-North Andover\10-Energy Audits\Abbott- Lot 3.rck Page 8 of 9
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
403.9.3 Heated swimming pools have a l ❑Complies
[1`120]3 cover. Covers on pools heated ❑Does Not
over 90°F are insulated to R-12. ;
❑Not Observable
�❑Not Applicable
404.1 ;50%of lamps in permanent I❑Complies
[F16]1 ifixtures are high efficacy lamps. ❑Does Not
`til' ; ; _ J❑Not Observable
j❑Not Applicable
401.3 1Compliance certificate posted. {❑Complies
(Fi712 , t❑Does Not
❑Not Observable
❑Not Applicable
303.3 Manufacturer manuals for ; N❑Complies
[FI18]3 ;mechanical and water heating ❑Does Not
equipment have been provided. i
?❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Proposed New Residence- Lot 3, 303 Abbott Street Report date: 11/24/1
Data filename: C:\01-Projects\Residential\Corcoran-North Andover\10-Energy Audits\Abbott- Lot 3.rck Page 9 of 9
2009 IECC Energy
Effidency Certificate
ME
Wall 21.00
Floor 30.00
Ceiling / Roof 38.00
Ductwork (unconditioned spaces):
I
Window 0.29
Door 0.60
IIIIIIIIIIIIIIIIIIINION
. .. . .
Heating System:
Cooling System:
Water Heater•
Name: Date:
Comments