HomeMy WebLinkAboutWater Based Fire Protection Systems Inspection and Test Repor - Correspondence - 1/8/2015 Superior Fire Protection, I
WATER-BASED FIRE PROTECTION SYSTEMS INSPECTION & TEST REPORT
*This report 'i based on the scope of work as referenced in the N PA 253 2011 Edition.
Property Name: McGar 1 mt Address: 401 Andover St
Inspector:Ju tin Guillemette Date: 1- -1 it /Stale: North er, MA
Last Inspection Dale: New Min a : X Bi-Annual: uarter :
Gauge Reath Stand Pi e: stem: 55 Supply: 55
#of ems: of Zones: Alarin valve: Shotgun: X
N NIA Y N N/A
Is System ill service X All OSY in good condition X
Back flow valves open X All PIV in good condition X
Sprinkler control valve open X All WPIV in good condition X
Stand pipe control valve open X All BFV in good condition X
Floor control valves open X Spare leads In head cabinet X
Glycol loop valves open X Head wrench available X
Tamper switches in good Visible heads appear free of non-
condition � roved coverings X
Valve. and controls accessible Visible spray patterns free X
Obstruction
Alarm valves in good condition Visible storage&stock stored X
X below s rinllem• l*r!
Alarm flame free of leafs X water flow alarm devices activated X
Building appears to be
completely rin led X Exterior alarms tagged X
Trim valves in correct position X All valves properly tagged withX
sljie
Retard eha fiber free of leafs X Hydraulic name plate attached,if
roided
Visible piping in good condition X Visual inspection: All visible piping X
appears in good condition
YDC visible X Is there an Anti-freeze system X
FDC swivels spin free X If yes,was anti-freeze system tested X
FDC plugs/caps in place X
System Inspection Tag X Refractometer Reading New 1/8/15
..................
System left in service X ALL QUESTIONS WITH"NO"ANSWERS
Alarm panel clear X ...............
MUST BE EXPLAINED
planation: (Please see Addendum for deficiency details)
SUPERIOR FIRE PROTECTION,hVC. 230L0jVD0jVDERRYTURNP1KE-. HOME", NEW HAAMSfIIR 0.3106 P(6 03)6444700 F(603)6 4-87VQ
"PLEASE NOTE THIS INSPECTION WAS DONE BASED ON THE GUIDELINES OF NFPA 25 AND ANY ITEMS
OUTSIDE THE DESIGNATED SCUPS OF WORK,CONTINUES TO BE THE RESPONSIBILITY OF THE BUILDING
OWNER. ADDITIONALLY,, ANY ITEMS FOUND OUTSIDE THE SCOPE OF NFPA 25 WILL BE NOTED ON AN
ADDENDUM AND IS NOT A COMPLETE VALUATION OF THE SPRINKLER S STEM. LISTED ITEMS WERE
FOUND ON VISIBLE INSPECTION AND IS NOT A COMPLETE EVALUATION OF YOURSPRINKLER SYSTEM.
{
r
Superior Fire Protection, Inc.
WATER-BASED FIRE PROTECTION SYSTEMS INSPECTION & TEST REPORT
*This r t is based on the scope of work as referenced in the N PA.25,2011 Edition,
ALARM VALVE I! shot
Year Male Model Size Serial
CONTROL VALVES
Valve Type Open Secured Signs Condition
y N y N Y N
City Connection
Control wive OS&Y x x x Good
'Wank Control
Valves N
Punip Control
Valves N/A
Zone Control
Valves BFV x x x Good
ystenn Control
Valves BFV x x x Good
MAIN BRAN Flow TEST Inch drain valve fully opened
Sprinkler Supply Gauge 55 psi
Sprinkle-System Gauge 5 pl
ALARMS N NA
Water Motor gong working properly x
Electric bell working properly
Supervisory alarms working properly X
WATER FLOW TIMES
Zone Seconds Zone Seconds Zone Seconds
Main 43
Inspector's Signature e;
Property Owner/
Authorized Repres n five Date:
"PLEASE NOTE THIS INSPECTION WAS DONE BASED ON'rHE GUIDELINES OF NFPA 25 AND ANY ITEMS OUTSIDE THE
DESIGNATED SCOPE of WORK,CONTINUES To BE'TIIE RESPONSIBILITY of THE BUILDING OWNER. ADDITIONALLY,
ANY ITE-LNIS FOUND OUTSIDE THE SCONE OF N PA 25 WILL BE NOTED ON AN ADDENDUM AND IS o'r A COMPLETE
EVALUATION OFTHE SPRINKLED SYSTEM. LISTED ITEMS WERE FOUND ON VISIBLE INSPECTION AND IS NOT A
COMPLETE EV LUNFIf N of YOUR SPRINKLER SYSTEM.
FIRE
PRAjWECTION
INC-
Sprinkler Inspection Addendum
Property Name: McGaL1 M Alt
Address: 401 Andover St. North Andover, MA.
Inspector's Name: Justin Efate: 1-8-15
Items listed below are not part of an NFPA 25 Inspection and are outside of the scope of the Inspection Agreement with the
Company. The identific t[on of these Items does not constitute a design review or engineering analysis of your system.
These items were noticed during an inspection of your fire protection system performed in accordance with NFPA 25 but are
not part of the NFPA 25 inspection. Superior Fire Protection makes no guarantee or assurance that any or all design or
engineering defects or deficiencies have been detected.
Deficiency
No head wrench in head box
Deficiency
gauges,over ars old
Deficiency # ,
.Missing signs 3 control valve, 1 main drain)....
Deficiency #
Add heads unit 11- 1 lead in closet) (unit 12- 1 head in kitchenette) unit 201 - 1 head
By back window it 102 back hall by bathro ms need 2 heads) (unit 10 1 head
Deeds to be moored away from waif
Deficiency
Add Esc in unit 202 5- semi r c chrome. 2- short donkey... Esc must t e split ese
o put on existing heads.