Loading...
HomeMy WebLinkAboutGLSD Organics to Energy Project - Lab Test Results - 240 CHARLES STREET 8/1/2019 3 Richard E. 1ir From: Flaherty, Daniel M. <fIahertydm@cdmsmIth.com Sent: Thursday, August 1, 2019 11: 1 AM To-. 'Joseph Peluso' c: Storrs, Edward; Cheri R. uen ; fiord E. Hear Subject: Greater Lawrence Sanitary District - CHP -- Scrubber Tank Factory Tests Attachments: MX-264020180430082954.pdf Joe, Please find attached factory tests for the H S and Siloxane vessels installed at GLSD. These vessels were additionally field tested by the plumbing contractor with a soapy solution at all joints and weld seams after installation. Daniel M. Flaherty*PE DM Smith 75 State Street, Suite 701 Boston, IAA 02109 617.452.6312 S 20IM3,0000-001 GLS�D H2S Vessel 6V-2,43-41, RT-301, #187,8 Serial Jail / /or ii/ i SOLUTIONS 5451 U S 0 N Dubuque,I i563-585-0967 Fax t 1--58 5-0970 "�'""M1,. ,�...�:, �/pan,:�:.eiri�r .�,>.;�^�i ,Nm��a!z^�'.',�. .��7+7,. ,�tlllYl /lhrir�PW���T�G�u�ww""'anwmr�,��n'ii�r�or�r rrnn��wwr�� iu��mrwr!✓arua�"lu��ir,«m�muw�a�v�'urwauv�,^il�uiv�rv�im,�e .��w��x��u_s�,v,��.a,���u, nru �m�wwa�,��^r�s�„r, .�,..,.,. :;,,,, ,,,,�„rrr,,,,�,�,,,,�:,�,y o,��; Unison Soltitions,Inc. Wield Inspection 00CLUMM"It INSPECTOR WELDER ' VVELD TYPE 10011% NO VISUAL, TR I PE TIC I SPEC I � VISUAL � INSIDEOUTSIDE GROOVEFILLETINSPECTION INSIDE T ID I (X, (X [IUD#1 (ID UI P"I '' P" P p I P'i (P I P ! f w r P i J1 I N 13 M o. , uJ O 1 ,1 1 .�. ;ff, 1 s O1N1T I 9, r r , JOIN'.1,. I JOINT x� ouu� r JOINT 11, 01 p l 17 r IN T w1 J � .. w a, I NIT , t , 01NT .I L ` ! b I, md D w x, , JOINT flN ' 1 N,T Al d ' JOINT I , J 0 1 N T JOINT 1S TO 11 1 of f , ! ! � s l r y a � s u r� unison soludons" Inc. Weld Inspection DOC1.11110flt Non-Codo Vessels/Filtots 7"11�,�7r7l=-,Pllm�=PWllg"l���,�Illwl�=,��,�II X A"'14 ll'�`//' "w PIROJECT: 243 -GLSD SERIAL,UU MBER.- '1818 1)Wil/G It W-243-11 P&ID DESIGNATOR: Fl-T-301 1�ill$PECTOR YIELDER VIELD TYPE "10 0 11% M VI S U A L, PI I M A R Y'I N S P E C T I ON RC-INSPECTION' GROOVE FILLET VISUAL, VERIFIED INSIDE OLJTSIDE NOTES INSIDE OUTSIDE, INSPECTION P130CEDURE PASSiFAIL RASS/FAIL PASSIFAIL PASSIFAIL liNSIDE OUTSIDE If, 1XI (ID#1 ((D#1 fP';F) ()P IF I [P F] (P I F) If It J" I I( ..�.�LL�,.."_ ice,. , ij j II PRESSL)RE TEST SECTION PRESSURE"rEST REQUIRED---- TEST DATLE .TEST FLUID Hydro PRESSURE(psil I r utes) 30 inin DURATION fr li,I T [NIE THOD of DETECTION PASSYFML RETEST PASSWAIL TEST TECHN11CIAN 10# SUPGRVISOR SIGNATURE mmy===a Revision 04 2/15/2017 2430000-,1,001, GLSD, H25, Vess,el 6V-243-11 FLT-302 #1879 Senal r' r� r ri ri/ amr'/r ' .. /09 ' ........ r f/, "IL/w si S 0 L U T 10 N S 5,45,1 e l l e, . Phone.- 563-585-0967 Fax; 63-58 - 70 �Y v Unison Solutions, Inc. Yfold Inspection Document N W r f W i r 1 i r 0 / i lteis _..il�r>;�.�u�ufrra�rr✓fir,.ry"°�rm,..,...,1, iJ.. Bl6.l,i ,Y;i�i�„r .,�„r... ;i „�,- ::, ,,,,,:,; ,.,,"_�..,,""„ „ ,., ��V` �ii"��h r IRxI,NU✓ a''l�c .�G,,,,r�uu,�_?lwL.,.,�,w..,.l:�.�.,er, e_.,ww r� a�,u r���.u.��,,.,,.,emu,�r„,>kw„�,rro^o��im�c+�rr �� ,.�.. .., � �� ..,eurrsu..�rumrrr�rr®r�,r„Mc„n�x-�n�re„rrsu� r,� d�amr^. �.���� ,«,,,„a ..rw= ., -2e,1 -11 P&III DIESIGNAT "r'-3 INSPECTOR WELDER WELD TYPE , " IMARY I SP iI CI �� I�� �..r IEINETIN VISUAL VERIFIED INSIDE OUTSIDE INSIDE ou'rsIDE GR OOVE FILLET NOTES INSIDE UT'SIDE 1 I [ID 41 (fo#1 ��' � i P I 'I I Jv ,JOINT IA y JOINT IC 7 r_ i I ry u , I I T 1 F a u u � r ✓ M � I NT I I o Y n I j I I I I I i JOINT I J� II , I , JOINT 1 K � � I ��.rxr.r..y,rxw.�w � ,— ,�.�,wnwMwwwxw.wwwwnn� JOINT 11 I A JOINT I NI r x U k�r J1 N nI ."M.fiSFihr�® 4n�wwn,w�o�w, u�p�,�y;,yx o, r' o ; JOIN_, yI "56-INT 10 J01 NT -1 f ,JOINT xS r JOINT 1 I� N F J011wr IG u „ x ; a i wlsio / 1 Unison Solulions, Inc. �+r�wvu,, ....'�H"o.. ,�,,.:,YYJIW,,,w�,r�,;,v1 Y .�--• vy.i„mn. nw,vaw� (�r..� �.,r-u�!.,;taw��.,w(xr�i.:,r�rm��c�nr,�.��uza�r�r�vur�.m�,.�.�rir. .crn,ufranariiu^u�.�ra.�vnur�.,,rtr�.-^s:�ue��.,, �r��n��,2�,...�.,��„,,.„I.�7vY17�"+t�",�,n„.n✓�I�,,m,,.r..�auemiuin��r�N�.�.-ul�'nn�o�rwvu7„�✓a�,o-iJr. mr�.�r�,� tl�� �., w.�^?�.mm,.�vz�.�,.ar.�,w,:m�,mr�rru�^� R OJ E C T 243 -USD SERIAL NUMBER. INSPECTOR VVELDER "WELD TYPE 0 0„� ND VISUAL, PRIMARY INSPECTION C-I 9l r"I mm. .mm_ VISUAL VERIFIED INSIDE SIDE OUTSIDE � I Y I ,ITSI' E I ITS T INSP TI lkI PROCEDURE I m j n _ , d , A � � R YR a TP° f � Y, I I I r PRESSURE TEST SECTION PRESSURE TEST RIE rESTDATE I TEST'f7- 11 Hydro PRESSURE]psi] 0.858 DURATION(minutes] 30 min METHOD of I E . ,, IO PASW I'L R T T PASSI AIL TEST T C'[I ICAAN I ar, / O "22m 1 "7A, '430000-,001 GLSD H2S Vessel 6V'-24,3-11 FLT-303 Serial #18,80 J/ i i SON Unison solutions", 11,1c. Weld Inspection, Docuniont N o" c ode,ves s e I S/F,i Re r's "I'm ""Im , .................. PROJECT: 43-G,LSD SERIAL NUMBER: '1880 DVVG #: 1,P&ID DESIGNA-riOR: F LT-3 0 3 INSPECTOR WELDER WELD TYPE 1001% N'0 V I SU A L, PRIMARY INSPECTION REINSPECTION (ID#1 VISUAL i VFRIFIED, INSIDE OUTSIDE INSIDE OUTSIDE NOTES GROOVE FILLET III PE c'n i PROIC E DU RE PASSIFAIL PASSIFAII PASSIFAIL PASSWAIL INSIDE OUTSME [X) (XI [ID#1 (ID 01 JOHNIT 1A OY JOINT IB JOINT IC oolwm _7L..... JOINT 10, / JOHNIT I It JOHNIT 1F JOINT lG T IH lJOINT -11 j INT IJ iJOINT lK j 01 1 N T 1 L I Ni J T 1 1 -will f J 0 1 N'T 1 N O,% w �, V"(11,III jOINT 10 Of r J 0 11 N T 11 7 J.— JOINT '110 It'd -71 JOINT I R J I Al" O JIONT 19.N ................ J IT 01� WIT 1 T u. T 1 U ............. .............. Revision Ott 2/15/2017 Unison Solutiorts, lac., Weld Inspection DoCLI11101"It P R 0 J E CT., 243 -G,LSD SERIAL NUMBER.- "18,�8,0 D ID vv G #: 6 V-2 el 31-11 P&10 D E-SIGNA"FOR. FLT-303 INSPECTOR WELDER YlE LD TY P E 1100"/o MC)WSUAL,] PRIMARY INSPECTION REINSPECTION 111D 41 GROOV'E F'ILLE�T VISUAL VERIFIED INSIDE OUTSIOE NOTES INSIDE OUTSIDE INSPEC TION PROCEDURE PASSIFAIL, PASSIFAIL PAS"811F A IL PAS5iFAIL INSIDE OUTSIDE (XI (XI (ID (P Fj (P I F) py pp AI 7) PRESSURE TEST SECTION PRESSURE TEST REQUIRED .TEST DAr,E TECST FL U I D Hydro PRESSURE[psi') 01,8158 DUR,ATION 30 min NIET H 0 D of DET EC T 10 N P PAS3i5AJL ,A RETEST PASSIFAIL TEST TECHNICIAN ID# SUPERVISOR S[G N A Tli R E', RevIsior)04 2�151/20,17 1 2430000-001 u, L ��, �x� H2S Vessel 6V-24,341 FLT,,304 S e ria,I #188 1: r/ r ri %fir //iiii rr�D/ �� //< ri///rill .............. /00 /// %/r/i'rill r � r irii /�// /�r r r /iiiS 0 L U 10, NS r w 5451 Chavenelle m, 563-585-0970 Unison Solution:8, 1.110. t"Mold, Inspection Document Non-codo vessolsir-11ters ............ PROJIECT: 243-0.LSD _ERIAL NU NIBER: 1 al 0 Vil G ff 6 V- 4,'."i-1'1 P&ID DE:SIGNATOR: Fl-T-3,0zi INSPECTOR WELDER VVELD TYPE 1100%, NO,VISUAL, PRIMARY INSPECTION REINSPECTION III#1' VISUAL VERIFIED INS4DE OUTSIDE. INSIDE ou'rSIDE NOTES GROOVE" FILLET - PROCEDURE PAS S IL P IFAASSIFAIL INSPC CTION PA5SIFAIL PASSIFAIL (x) (XI I 1 1 INSIDE OUTSIDE (10�11 [I D X) (P IF] (P I FI (p I F1 (P I F1 JOINT 1A '41 JOINT T(B JOINT 'I C JOINT I D JOI NT 1 E JOINT 'IF J 01 Ni T "I G xy Afl�, JOINT 'I H, JOINT 11 JOINT 1,1 J 0 JOINT 11tl JOINT 11 mef, )fl JOINT "'IN JOIN,T 10 JOIN-1- 'I P JOINT I Q JOUNT I i'OIN 1' 1 S 0 1 i'l T 'I T if J I 'll U ............ Rev�sion 04 2115/20:17 Unison Solutions, hic. Y/old, Inspection Document Non-Code Vessels/Filters „ .,.. „o ,.:�,.. ...,.. � ,^,: ,��.. ��mm .,.,, .,. ,+!n�vww_,,.:, �vrcaw.r.rtw aix,« �W� ,r�..vwvremwr�rvr�a,,mwmr.�mm rvmrm�n�tl�mu� w:wm«,mv,✓� "`,�*�M"'„�JRwY°7 ��1 sr.�ury mMuw4iu„ci,,N'Yc.«yrVrww"s^„v w��r,�.nw^nirve��r.,,wV�N�«,,-rrrwnnr,�>�r n r,.....atmu,,,uu�Sri,...<,�r..uY✓i�.:k:d1ti`rer..,"<':��'..JI'rT1'.... ,: 243 NUMBER: 1 1 INSPECTOR W E L D ER WELD TYPE 100% NO VISUAL, PRIMARY INSPECTION REINSPECTION, i VISUAL VERIFIED INSIDE d T 1 � w INSIDE OUTSIDE NIOTIII^ I u'rsI1: ( 1 J 1 #1 (ICE 1 I 1=] P I ] (P I ) I t r a yWLI � . o ;r r i r pro i i i r I {p� j i � d I a A." ^ , j I i i f I f i 'i f i I I PRESSURE TEST SECTION PRESSURE TEST REQUIRED TEST DATE TEST FLUID Hydro PRESSURE fell 0,858 NlEl'HOD of DETECTION IPASSiFAIL RETEST PASSITAIL ^ TESL"TE HN10AN ID 4 I I VISOR SIGNATURE 2 3,4 Laawrence Sam,tary Dil,strict FLT-,361 Siloxacne Vess,el 1886 N I r soI, i S. 0 L U T 10 N i, 5451, have i l e } Unison Solutions, Inc, Weld Inspection DOGLImont Non-Code Vessels/Filters : -21 MID DESIGNATOR: FLT161 INSPECTOR WELDER WELD TYPE 100% NO VISUAL PRIMARY AR INSPECTION REINSPECTION VISUAL VERIFIED INSIDE OUTSIDE INSIDE OUTSIDE GROOVE FILLET INSPECTIONP€O OI� NOTES JOINT 1 A _ JOINT 1 ,SIT I JOINT-1 D JOINT 1 E JOINT 1F rr i JOINT IG JOINT 1 H JOINT It JOINT U JOINT 1 I el- Zan £r, ° i JOINT IL JOINT 1M JOINT 1 N /Sfy JOINT 1 .JOINT 1 P 514 /,10A JOINT 1 lMce "let JOINT 1 I 4.1 /mv/ A-) JOINT -1 i JOINT 1T_ - F - '�*'..++iS l z+y li 1+ k J11T 1V4 Revision 04 '1 12 12 -1 Unison Solutions, Inc. Weld Inspection Document Non-Code 1sselslFllters PROJECT:- 2 -GLSD SERIAL DUMBER: 1886 DWG#: *2 3-2`i i P ID DESIGNATOR: FLT-361 WELDER INSPECTOR WELD TYPE '100% NO VISUAL, PRIMARY Y INSPECTION REI ISPE TION VISUAL VERIFIED R I� ILL ET INSIDE OUTSIDE NOTES INSIDE OUTSIDE INSPECTION:PROCEDURE PAS WAIL AIL PA S)FAIL PASSIFAIL, PASSIFAIL INSIDEOUTSIDE' 1 I 1 I (ID ] ID 41 (P r F1 (P I F] (P)F) [P I F1 JOINT 1W JOINT 1X x #. J OINT I k JOINT 1 � JOINT 1AA f JOINT 1 AB . .JOINT 1A IJ, � JOINT T 1AD t, JOINT 1 A + '91 f ", a , . % JOJNT 1AF JOINT 1A .JOINT 1 H JOINT 1 AI t. x 5 PRESSURE TEST SECTION PRESSURE TEST REQUIRED x''k `} v � TEST DATE ` TEST FLUID Hydro " PRESSURE[psi) 15.6 DURATION[minutes) 30 fnin ` METHOD of DETECTION 5 i DABS/FAIL 3 RETEST PASS/FAIL TEST TECHNICIAN ID SUPERVISOR I NATU E ►i lon 04 1 1 i 16 I 243,0000-001 Greateir Lawrence Sanitary District i 1 FLT-362 1887 JF- r r r r / r/ar (�i) 0 l j LU uu , IA 52,002 Phone: 563- 85- 967' Fax: 563-5 5- 97 tflSOII SOILM n , In . Veld Inspection Document Non-Code Vessels/Filters P O,JE T: 43 - L SERIAL NUMBER: 'i 7 1 --- .�P&D GESIIA'rO# : FLT-362 WELDER INSPECTOR I WELD TYPE 'I VI €IAL, PRIMARY INSPECTION REIN PE T1 �1 VISUAL VERIFIED INSIDE OUTSIDE INSIDE OUTSIDE GROOVE FILLET INSPECTIONPROCEDURE NOTE I1�,1SIE� �L�� ID � � € � PAIFAIL PAS �FAI[. I� IFAIL s�A1FAIL. AID It] (ID#1 JP I F) [p I Fj [P i Fj (P i F1 JOINT 1 W JOINT 1 11 -=---- JOINT 1Y { JOINT 1 ,JOINT 1A r .JOINT 1 A ,.JOINT 1A -r JOINT 1AD JOINT 1AE ►.. f , JOINT `I I^ J JOINT 1A JOINT 1 AID JOINT MI PRESSURE TEST SECTION PRESSURE TEST REQUIRED TEST DATE TEST FLUID Hydro PRESSURE(psi] '1 . DURATION(minutes] 30 min METHOD of DETECTION PASJEAIL RETEST PASSIFAIL TEST TECHNICIAN ID# SUPERVISOR SIGNATURE Revision 04 1 l l ( 16 Unison Solutions, In . We(d Inspection Document Jon-Code Vessels/Filters F R JECT 2 3 -GLSD SERIAL. �.M '1 7 W ,r V-243- 1 P&ID DESIGNATOR: LT-3 2 INSPECTOR .� WELDER WELD TYPE 1001% NO VISUAL, PRIMARY INSPECTION REINSPECTION VISUAL VERIFIED FILLETI II OUTSIDE NOTES INSIDE OUTSIDE INSPECTION P O OU PASSIFAIL PA FAIL PASSIFAIL PA IFAIL INSIDE OUTSIDE 1 I ( I [ID ] (ID#) [P I F1 (P F1 JP I F1 [P!F1 JOINT 1A J (NT I B \. JOINT _ 1 _ JOINT 1D .JOINT 1 f JOINT 1 F JOINT 1GhL JOINT 11H JOINT 11 JOINT 1J JOINT 1I JOINT 1L JOINT 1M 7 411 JOINT IN JOINT 1 JOINT 1P ry JOINT 1 JOINT 1 R 1 .. x :JOINT 1 S _ JOINT 1 `fir #-f Y^{ {`�� � `.f n}• :f? JOINT 1 JOINT 1V _ t. �..'. Revision 04 12/281201 2,430000--mO01 fHe ii r (N;�"RY W S i- c P Sanitary D'Istrict FLT-363 Sij foxarie 'Vessel .. 18-88 w. i m////,.md/ r oo,, ri ri/ /i /ii0✓ r doA/P/p////r /3/ // ro iii prr� off or So pirr i S 0 L U T 11 0 N S I 5451 Chavenelled Dubuque, 1A 52002 VYWA *Un1 s,o ri S 0 1 Ll tion" s,co Wald Inspection DOCLII[neflt Ion-Code Vessels/Filters "��-/r Ni...i,�,,R�,6mw�"RWvNMFN�iEM,'d✓v'✓.,w.��nPo!'l'^�FT,J �,�r��lt£ !�r�f�.M/���//�"Nt imp.�.rrMv";�M�i'Ym^,f..f8.�'YYM_.._�'c'-'m_vf"J..��uE.,e/M�ALiv➢(k w Ji.�"d/dal�i i9.1 J��„lU.�+.'r�:e i2�iyRG�i 4V"�.e"tpNIIC.,fmtivltldf'NN"A'uUlu.'h'MW�M144ti�WC"riuWWYW$91�'"%"i»'""Y�`YM�NIY.9d!l!,Wi1 IW1A:'&NK.If/WOD.WA9A�IN.�i1,1"?l/�.... �*4' I R0 EG : 2 G S SERIAL NUMBER:, '11 III"IS ,C. I W E L D E RWELD TYPE 100% NO V I S U AL PRIMARY ARY INSPECTION REINSPECTI NCI _.,VISUAL VERIFIED � INSIDE OUTSIDE INSIDEOUTSIDE� 'E E FILLET �, ��d= I� INSPECTION "� �E� I ' � � I_ ������IL ��a w_ I CAII �; I � OUTSIDE AID (IE1 j (P F [P I F (P FI, (PI,I q JOHIIII,IT 1 A I0IIT .1 JOINT IC yl a I O I NIT I D r r JOIN_ I r, Lof f 1 �M i JOINT .I 1 1 1,. I G ; /lit , p JOINT I a JOINT 1!I JOINT IJ JOINT lK JOINT III- r P,w r J 0,1 ICI T .11 NI m, I jouwr , I JOINT I 4j JOINT I JOINT 10 10 I ICI T 1, I � " , a �T ry D W iJOINT 'IS � - � ICI I I..Iro -M..WHO RIMINI ap, JOINT II. III r A c I I N T I N unkso'll solutions, Ine. lNeld Inspoction, DoUlinent Nori-Cocle Vessels/Filters P R 0 J'E C T 243 -GLSD 1SERIAL N U NJ B,, E R -6 2 4 3-2"1 FILT-363 Wjl/G V �P&ID DESIGNATOf I M 3 P1=1 C`F0 R VVELDER WEI-D I­YPE 100% NO VISIUAI PRIMARY INSPEC FION R,E1M,5P,ECTfM4 VISUAL VERIFIED INSIDE MJTSIDE INSIDE OUTSIDE GROOVE FIL.�LET 013PECTION PROCEDURE, P,,,,%S.5iFAlL PASS�FAIL OT E s PASSIFAIL PASSIFAIL INSIDE OUTSIDE 1XI (XI (I D it] pois: (Pr FI; (P I'F) [P I Fj I (P)F1 ,JOINT W/ JOI IT 'I X 10 11 IN]T "I Y Y JOHNIT IZ J 0 1 NT IA A JOINT IAB JOINT -JAC j J,01 iN,T 1 A D JOINT I AE JOINT lAF JOINT 1AG ,,j5I,NT 1AH JOINIT I .................- PRESSURE TEST SECTION PRESSURE,TEST REQUIRED rEs r DA rF- TEST FLUID Hyd ro PRESSURE,(ps,i) 1,5.6 DURATION 30 m, i i i METI-10D of DETECTION PASS&AIL RE'rEs"r 10,'ASS)FAQ. rE,ST TECHNICIAN ID 4 SUPERVI,SOR,SIGNATURE Revision 04, 2,12,8 12 0,16