HomeMy WebLinkAboutFire Alarm System Inspection - Inspection - 120 MAIN STREET 12/17/2019 i IMPACT FIFE SERVICES, LL
26 HAMPSHIRE [RIVE
I"UDS N NH 03051
0
. 603.293.7531
IMPACT F . 603.589.2051
FIR "WW.GETFIREPROTECTION.COM
FIRE ALARM SYSTEM INSPECTION MASTER ELECTRICIAN#:
Inspected to the state adopted version of NFPA 72 MA- 4 3A; NH- 13117 M
WORK ORDER�#: 17616248 DATE: 11 # 1 3: am EST C ST E I
BILL T : SHIP T :
TOWN OF NORTH Ai DOVE -DIVISION OF PUBLIC WORKS NORTH AND OVER TOWN HALL.
ATT :STEVE FOSTER FACILITIES DIRECTOR,384 OSGOOD STREET 120 MAIN STREET
NORTH AND OVER MA 01845 NORTH TH AND OVER MA 01845
Phone: 78)688-9516 Contact:STEPI EN FOSTER
Email: SFester@norkhandevra.gov Phone: 7 305-5850
ANNUAL SEMIANNUAL QUARTERLY SENSITIVITY
ARRIVAL TIME: :ooam DEPARTURE TIM.E*11:45am
PASS FAIL
A. PANEL CONFIGURATION:Notifer NFS 2-6040E
DETECTION CLASS; CLASS A: 0 CLASS B: El
SIGNAL. CIRCUIT CLASS: CLASS A: CLASS B; Ar ID ❑
PANEL LOCATION;Ma in Entrance
BATTERIES: .018) VOLTAGE NO LOAD:
B. QUANTITY: VOLTAGE LOAD::
1 %
C. ANNUNCIATOR TYPE:N/A C. Li
REMOTE TE PANEL TYPE:FCPS-24S8 Power Supply By Faop( 12v 7Ah batteries 1 )1 % +
TYPE;Mlreorn booster panel 2 1 V 1 Ah Batteries 1 1 % R1 El
D. C .
TYPE.
..E1
TYPE: ❑ ❑
E. PANEL GROUND; TERM: TO: READ:: E.
................................
TYPE F DEMOTE ❑ MASTED B # RADIO MASTER BOX 1
F. DIGITAL COMMUNICATOR: TIER: F.
COMMUNICATION ❑ I ❑
LG* OFF LINE TIME:3:0 a m!11:�4 ar REPORTS TO;North Andover F G. z E]
N LINE TIME, REPORTS TO.
SINGLE
C.O
PULLS ROFR FIXED SHIEST STATION .
DETECTORS SMOKE DETECTORS
TEST FAI L TEST FAI L TEST FAI L TEST PAIL TEST FAIL TEST FAIL TEST FAIL
CITY 10 0 51 1 0 2 1 0
........................
MINI OutsideHORN Horn/Strobe Speaker/strobe Visual OnlyAudible Onlytslde
STROBE Beason
TEST FAIL TEST FAIL TEST FAIL TEST FAIL TEST FAIL TEST FAIL TEST FAIL
CITY 38 0 12 0 1
Page 1 of 5
k
IMPACT FIRE SERVICES, LL
26 I AM PSH I E DRIVE
IMPACT0 03.293.7 31
F -603.589.2051
FIREV"".GETF IRE PROTECT ION.COM
FIFE ALARM SYSTEM INSPECTION MASTER ELECTRICIAN
MA Inspected[ tyre stafe adopted version f NFPA -2 23 �I- '� 11 I11�
WORK ORDER ; 17615248 DATE; 1 J / 08:00am EST CUSTOMER ID:
I- . Explanation of FailedDevices:
Need to troubleshoot horn strobes when tested the horns and strobes are out of sync.
IF
1. The inspector suggests that following necessary improvements. However, these suggestions
are not the result of an engineering survey. These are recommendations based on current code.
Nave
J. Adjustments or corrections made:
Replaced 1 v 12ah batteries in basement electric room booster panel.
K, inspection and suggested improvements were discussed with the undersigned Owner or
Owner's Representative. X Yes F-1 No
12117/19 THIS IS NOT AN INVOICE
' OM-ER'S SIGNATURE DATE QTY PART## DESCRIPTION PRICE AMOUNT
12Y 1 ah
Battery Disposal Fee
CUSTOMER'S P ED12/17/19
r
•
VWcPN G RE DATE
Iho1 Rich, Ross dad
ev
TECBMCIAN PRINTED NA LICENSE##
❑ BILLING ADDRESS CONFIRMED
Page 2 of
IMPACT"FIRE SERVICES,LLC
26 HAMPSHIRE DRIVE
HUbSON NH 03051
IMPACT
O :603.293.7531
F:603.589.2051
ADDITIONAL SERVICE WWWGETFIREPROTECTION.COM
FIRE INFO/INSPECTION COMMENTS MASTER ELECTRICIAN#:
DEVICE INSPECTION REPORT MA-20423A; NH- 13117 M
Page 3 of 5
WORK ORDER#: 17615248 DATE' 12117l2019 08:00am EST CUSTOMER ID:
DEVICE MODEL LOCATION ZONE NOTES/COMMENTS: PASS FAIL
TYPE
BASEMENT ❑ ❑
Smoke ELEVATOR MECH ROOM HALL 1 U005 Q
Smoke ELEVATOR MACH ROOM HALL 1 D003 Q ❑
Smoke ELEVATOR MECH ROOM HALL 1 D002 Q ❑
Smoke ELECTRIC ROOM 007 1DQ07 RIEl
Smoke ELEVATOR MECH ROOM HALL 1D001 Q ❑
Pull ELEVATOR MECH ROOM HAC.I. 1 MU12 Q✓ ❑
Smoke STAIRS BY ELEVATOR 2M008 Q✓ ❑
Smoke OUTSIDE RESTROOMS 2M008 ✓Q ❑
Pull STAIRS BY ELEVATOR 2M008 Q ❑
Smoke STORAGE 2M008 ❑✓ ❑
Smoke STORAGE 2M008 ✓� ❑
Stroke ELECTRIC ROOM 2M008 Q✓ El
Smoke NEAR ELECTRIC ROAM 2M008 ❑✓
Smoke INSIDE STAIRS BY ELECTRIC ROOM 2M008 +❑ ❑
Smoke INSIDE!7 ROOM 2M008 Z El
Smoke OUTSIDE COMPUTER ROOM 2M008 ❑✓ ❑
Pull OUTSIDE SENIOR CENTER DOOR 2M008 ✓Q ❑
Pull BOILER ROOM 1 M013 ✓Q ❑
Smoke BOILER ROOM 1 D006 Li
Smoke INSIDE COMPUTER ROOM 2M008 ❑✓ ❑
1ST FLOOR ❑ El
Smoke ABOVE FACP 1 D026 ❑✓ ❑
Pull MAIN ENTRANCE BY FACP 1 M034 Q ❑
Smoke MAIN LOBBY 1 b023 z El
...............
Smoke OUTSIDE TOWN CLERKITREASURY 2M009 �✓ ❑
❑ BILLING ADDRESS CONFIRMED
CUSTOMER'S SIGNATURE-DATE TECHNICIAN'S SIGNATURE-DATE
wCUSTOMER'S PRINTED NAME
� IMPACT FIRE SERVICES,LLC
28 HAMP5HIRE DRIVE
t tiURSON H 03051
IMPACT O: 603.293.7531
F: 603.589.2051
ADDITIONAL SERVICE WWW-G7FIFtEPROTECTION.COM
FIR E INFO/INSPECTION COMMENTS MASTER ELECTRICIAN#:
DEVICE INSPECTION REPORT MA-20423A; NH-13117 M
Page 4 of 5
WORK ORDER#: �7615248 DATE' CUSTOMER ID:
'12/17/2019 08:OOam EST
DEVICE MODAL LOCATION ZONE NOTES/COMMENTS: PASS FAIL
TYPE
Smoke OUTSIDE MAIL ROOM 1D024 Z El
Smoke LOBBY REAR 1 D025 Q ❑
Pull OUTSIDE STAIRS BY ELEVATOR 2MQ09 Z El
Smoke OUTSIDE STAIRS BY ELEVATOR 2M009 ❑✓ ❑
Smoke NEAR RESTROOMS 2M009 21 El
Smoke BY COPY F200M 2M009 Z El
Smoke INSIDE STAIRWELL BY COPY ROOM 2M0O9 z El
Pull INSIDE STAIRWELL BY COPY ROOM 2M009 ❑✓ ❑
Smoke TOWN CLERKS OFFICE 21M009 R1 EJ
...........................p--------------------------------------------
Smoke TREASURER OFFICE 2M(}a9 ❑ ❑
Pull HALL OUTSIDE SENIOR CENTER 2M009 Q✓
Smoke OUTSIDE PLANNING/BUILDING OFFICE 1D021 Q✓ ❑
Smoke OUTSIDE PLANNING/BUILDING OFFICE 1C7020 ❑✓ El
Smoke PLANNING/BUILDING OFFICE 1D019 R1 El
Smoke COMMUNITY DEVELOPMENT 'ID(}31 �✓
Smoke COMMUNITY DEVELOPMENT 1D032 ❑✓ ❑
Smoke COMMUNITY DEVELOPMENT 1D009 ❑✓
Smoke COMMUNITY DEVELOPMENT 1 D017 ❑ Li
Smoke HALT.BY WORK SPACE 107 1 D018 ✓❑ El
2ND FLOOR ❑ ❑
Smoke OUTSIDE CNE DEVELOPMENT 1 D012 �✓
Smoke OUTSIDE SUPPLY ROOM 9D015 ❑✓ Li
Smoke STORAGE CLOSET 1C3013 RI El
Smoke IT CLOSET 1 D014 Q✓
Smoke OUTSIDE RES7F200M 1D016 Q ❑
Pull OUTSIDE STAIRS BY ELEVATOR 2M010 ------------
�✓ ❑
BILLING ADDRESS CONFIRMED
CUSTOMER'S SIGNATURE-DATE TECHNICIAN'S SIGNATURE-DATE
CUSTOMER'S PRINTED NAME