HomeMy WebLinkAboutACFrOgCU1G9-D0sJBftV2hTUOHLm1C6gPb_tbKv...nJ75huz7LjITZECZC3Bd16Ww16q2t5PcBdaN4= Report of Inspection/Test
An n u a I N FA,72,
04/0,7/20,20 Conducted by:Jason DeFeudis,
Property FIRE
NORTH ANDOVER MIDDLE SCHOOL Impact Fire Services-Hudson 26 HanViNre DrIve,Hudson,14H 03051
(603),2934531
158039 261 Brooks StreeL'Wofcasler,MA 10 1 60$
Building#,-380679 (508)852-7227
495 MAIN STREET MM.GETFIREPROTECTION.COM
N 0 RTH AN D OVE R MA,0 1845
GREG ROBERTS
978-1994-6673
Inspection and Testing Form ,, wuarterly- N., Andover Middle Schoolm Mircom
FX 2000
Devices Tested this inspection Pass Fall Tested Not Total
YTD Tested
YTD
Exterior Notilfication Device 0 1 0 1
Strobe Device 23 23 0 23 0 23
Horn/Strobe Device 161 160, 1 161 01 161
Manual Station
Smoke Detector 0 0 01 0 86 86
Duct Detectors 0 0 0 0 8 8
Heat-Rate-of-Rise 0 0 0 0
Copyright 2020 Inspect Point Page 1 of 30
Report, of I nspection/Test
Annual NFlPA,72,
1 M PA Ic'T
04/07/2020 Conducted by:Jason DeFeudis FIRE
Propefty 26 HanipsWre Ddve,l Hudson,NH 0,31061
NORTH,ANDOVER MIDDLE SCHOOL Impaict,Fire Services,-Hudson (603)293-,7531
158039 261&ol ftaeL Mrcesler,FAA 01606
(5W)852-,7227
B u 1 Id 1 ng#.,,380679, VVWGETFIREPROTECTIORCOM,
495 MAIN STREET
NORTH ANDOVER MA 01845
,GREG ROBERTS
9178-9194-6673
Manitor"Ing Entity
Contact Name North Andover FD Telephone 978-6183-3168
--—--------
Type Transmission Radio Master Box
Approving Agency
Contact Name North Andover FD Telephone 978-683-3168
Email N/A Service Type Radio Box
System Type
Control Unit Manufacturer mircom Model Number FX 2000
Circutit Styles A Software Revision N/A.
Date Last Serviced N/A Last Date and Software+ r Configuration N/A
was Revised
Number of Circuits 4
Plower Supply
Main,Nomire all'Voltage N/A Main Nominal Amps N/A
Overcurrent Protection N/A Panel Board Location N/A
Disconnecting Means Location N/A Secondary Standby N/A
co
'Sto r agi tt ery Hour
,Amp Hr Rating N/A Calculated Capacity to o N
operate system /A
,Stoage Bla #
(Hours')
Engine-driven generator dedicated to mire, N/A Location of fuel storage N/A
alarm system,
Has Emergency System descrIbed in NFPA N/A Has Legally required standby described in N/A
70,Article 700 NFPA,70,Article 701
Has Optional standby system described in N/A
N�FPA 70,Article 702,which,also meets the
performance requirements of Article 700
or 701
Copyright 2020 Inspect Point Page 2,of 30
nf
Keport, of Inspection/Test
An�nual NFPA72
IMPACT
04/07/2020, Conducted by.,-Jason, DeFeudis, FIRE
Property aInVshlre Wye,Hudson,NH 030,51
NOR�TH ANDOVER MIDDLE SCHOOL Impact Fire Services,-Hudson (6�03)2934531
261 Brooks S"et Wxce 5 ter.MA 0 1606
1580319 (W)852-7227
Building#:3,80679 WMV.jGE,'TFIREPROTF-OTION.,COM,
49,51 MAIN STREET
NORTH AND OVER M 5
GREG ROBERTS
978-994-6673
NOTIFICATIONS MADE PRIOR TO,ANY TESTING Yes No N/A Who, Time
Buildin N.Andlover M.S,. 7:00AM
I :g Management E]
1 1:OOAM
AHJ Notified 0 11
Monitoring Entity El 0 ED
Building Occupants 0 N.Andover M.S. 7:00AM
Other(Specify) El 13 ED 1 11
SYSTEM.TESTS AND INSPECTIONS Visual Functional Paiss/Fail Comments
URS Power Test N/A N/A NI/A
Interface Equipment Yes Yes Pass
Other(Specify) N/A N/A N/A
Prerecorded Message Content N/A N/A N/A
La,mps/LEDS, Yes, Yes, Pass
Fire,Alarm to MNS Interface
Test Backuup Software N/A N/A N/A
Control Unit Yes Yes Pass
Sound Pressure Lev ell-Amint 'Yes, Yes Psis
System Intelligibility-CSI Yes Yes Pass
Isolation Modules Yes Yes Pass j
MNS to Fire Alarm Interface N/A
Sound Pressure Level-Alarm Yes Yes Pass
Reset/Power down Test Yes Yes Pass,
Trouble Signals 'Yes Yes Pass
System Intell1gibility-STI Yes Yes Pass
Disconnect Switches Yes Yes, Pass
Power Extender Panels Yes Yes Pass
Supervision Yes Yes, Pass
Software Backup Performed N/,A N/A N/A
G round-Fault Monitoring Yes Yes Pass
F
Yes Yes, ass unctional Test P
MNS to direct recipient MINIS N/A N/A N/A
Copyright 2020 Inspect Point Page 3 of 30
R,eport of' Unspection/Test
Annual NFPA 72
I M PAC :r
04/07/2020 Conducted'by:Jason DeFeud'is FIRE
Proplerty 26 HanVshlre Ddve,Hudson,NH 030SI
NORTH ANDOVER ID LE SCHOOL Impact Fire,Services,-Hudson (603)29,3.7531
158039 261 8moks Stme k Abricester,M,A 0 IM
(50)852.7227
Building#.:3806719 WNW.GETFIREPROTECTION.COM
495 MAIN STREET
NORTH ANDOVER MA 01845
GREG ROBERTS
978-994-6,673
CCU Security Mechanism N/A N/A N/A
Prerecorded Message Activation N/A N/A N/A
Fuses Yes, Yes Pass,
A
In-building,MNIS to wide area MN S N/A N/A N/A
Remote Annunciator Yes Yes Pass
Local Annunciator Yes Yes Pass
Pass
Primary Power Supply Yes Yes
SECONDARYPOWER, Visual Functional, Pass/Fall"I Comments
Load Voltage Yes Yes Pass
Battery Condition Yes Yes Pass
N/A N/A N/A
Remote Annunclators,
Charger Test Yes Yes Pass
Specific Gravity N/A N/A N/A
Discharge Test Yes Yes, Pass
Transient Suppressors N/A NI/A N/A
NOTIFICATION APPLIANCES Visual Functional Pass/Fa*I Comments
A
Speakers
of Clarity N/A N/A N/A
Visuial Yes Yes Pass
Audible Yes Yes Pass
EMERGENCY COS IC ION Visual Functional Pas Comments
EQUIPMENT
System Intelligibility N/A N/A N/A
System Audibility N/A N/A N/A
Phone Set N/A N/A N/A
Call-in Si',Ignal N/A N�/A N/A
A
To N/A Tine Generator(s) N/A N/A
Off-Hook Indicator N/A N/A N/A
Elevator Emer /A
gency Communication System N/A
Phone Jacks N/A N/A N/A
Copyright,2020 Inspect Point Plage 4 of 30
Keport of Inspection/Test
Annual NFPA 72 1 M PIA C T'
04/07/202O Conducted by:Jason DeFeudis FIRE
Property 26 HanVshire Ddve,Hudson,NH,03051
N I Impact,Fire Services Hudson (603)293-7531
ORTH ANDOVER MIDDLE SCHOOL 261113rooks$1rest M(cester,MA01606
1 58039 (508)$62.7227
Building#:380679, MM.GETFIREPROTEMO NI.
COM
495 MAIN STREET
NORTH AND OVER MA 01845
GRE'G ROBERTS,
978-994-6673
Area of Refuge Communication System N/A N/A N/A
System Performance, N/A N/A N/A
Radio Communication Enhancement System N/A Ill N/A
Other(Specify) N/A N/A N/A
Amplif'ier(s) N/A INI/A. N/A
AUXILIARY FUNCTIONSANTERFACE Visual Functional Pass/Fail Comments
EQUIPMENT/SPECIAL HAZARDS
Door Unlocking N/A N/A N/A
Smoke Management./Smoke Control, N/A N/A N/A
Elevator Recall N/A N/A N/A
Smoke Damper Operation N/A N/A N/A
Fan Shutdown Yes Yes Pass
E �—
N/A N/A N/A levator Shunt-Trip
Smoke,Shutter Release N/A INI/A. N/A
MUS Override of FA signals N/A N/A N/A
Other(Specify) N/A N/,A
Door-Releasing Devices, Yes, Yes Pass
SUPERVISING STATION MONITORING Yes No N/A Who, Time
Alarm,Signal 0 9:30AM
'7—
Alarm Restoration 10 0 :100AM
Trouble Signals 0 E-1 94430AM
Supervisory Signal 0 0 9,630AM
Troluble Restoral 11 11 11 1:00AM,
Supervisory Restoration, El IE] ED "1,1.100AM
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Other(Specify) Cl 01
AHJ Notified 0 0 0 N.Andover Fire 1 1:00,AM
Dept.
Buildin Occupants INI.Andover M.S. 1 1:OOAM
I I g 10 01 0
Building Management 0 0 11 N.Andover M.S,. 11:00AM
Monitoring Agency A 0 0 91
Copyright 20210 Inspect Point, Page S of 30
K to"!port, of Inspection/Test
Annual NFPA 72 1
IMPAC r
04/07/2020 Conducted -,Jason DeFeudis FIRE
Property 26 HampshiraChive,Hudson,N H 005 1
Impact Fire Services-Hudson, (603:2913-7531
NORTH ANDOVER MIDDLE,SCHOOL
26! ceder,
Wooks Wee L Wxer,MA cat
606,
1,58039 (50)862-7227
Building#:380679 MM.GETFIREPROTECTIORCOM
495 MAIN STREET
NORTH ANDOVER MA 01845
GREG ROBERTS
9. 8-9,94-6673
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE, TESTS,AND INSPECTIONS
Address Locatinn Device,Type Factory, Measured Visual Functionall Pass/
Setting Setting FaH
Front Entrance Exterior Notification Yes Yes Pass
Device
20201)
Auditorium Front Exit Horn/Strobe Device Yes, Yes Pass
(04/07/
2020) 1
1
Auditorium Rear Exit Horn/Strobe Device Yes Yes Pass
2020)
Auditorium Rear Exit Horn/Strobe Device Yes Yes Pass
2020)
Auditorium Front Exit Horn/Stroble Device Yes Yes Pass
(04/07/
2020)
-- ------------
7
Auditorium by Stage Horn/Strobe Device Yes, Yes Pass,
Exit (04/07/
2020),
Auditorium by Stage Horn/Strobe Device 'Yes Yes, Pass
Exit (04107/
2020)
Hallway by Band Room Horn/Strobe Devic,le Yes 'Yes Pass
(04/07/
2020)
Band Room Exit, Horn/Strobe Device Yes Yes Pass
(04/071
2020)
J
Hall by Sprinkler Room, Horn/Strobe Device Yes Yes, Pass
Band Chorus Area
2020)
Staff Restroom Back Strobe Device Yes Yes Pass
Stage Hallway
2020)
Staff Restroom Back Strobe Device Yes Yes Pass
Stage Hallway
2020)
Music Classroom Horn/Strobe Device Yes Yes Pass
(04/07/
2020)
Copyright 2020 Inspect Point Page 6 of 30
,K coftport of Inspection/Test
Annual NFPA 72
'IMPACT
04/07/2020 Conducted by:Jason DeFeudis FIRE
Property 26 HanVshlre Ddve,,Hudson,NH 03061
NORTH ANDOVER MIDDLE SCHOOL Impact Fire Services-Hudson (603)2034531
2,61 Brock
o�s Stress Ww*ster'.MA 0 1606
1580319 (50) -7227
Building#.,,380679 VMWOETFIRE PROTECT 10N.COM
495 MAIN STREET
NORTH ANDOVER MA 01845
GREG ROBERTS
978-994-6673,
Address Location Device Type Factory Measured Visual Functional Fees/
Setting Setting Fail
Special Education Horn/Strobe Device Yes Yes Pass
Room
2020)
Hallway by Health Horn/Strobe Device Yes Yes Pass
Classroom (04/07,/
2020)
Hallway by Music and Horn/Strobe Device Yes Yes Pass
Hea Ith'C lass roo ms (0,4/07/
202,01)
Hall by Art Classroom Horn,/Strobe,Device Yes Yes Pass
20120)
Hall by.art Classroom Horn/Strobe Device Yes, Yes Pass
(04/07/
2020),
Art Classroom,RA1 01 Hoirn/St�robe Device Yes Yes Pass
(04107/
2020)
Hal I by Art Classro om Horn/Strobe Device Yes Y Pass
(04/07/
2020)
Ar lassroom RA102 Horn/Strobe Device Yes, Yes Pass,
(04/07/
20,20),
Stairwell A by Main Horn/St�roble Device Yes Yes Pass
Entrance
2020)
Hall by Room C1 03 Horn/Strobe Device Yes Yes IPass
2020)
Hall by Room C1 09 Horn/Strobe Device Yes Yes Pass,
(04/07/
2020)
Boy's Restr Strobe Device Yes Yes
Pass
(04/07/
2020)
Staff'Restroorn Strobe,Device Yes Yes Pass
(04/07/
2020)
irl's,Restroom Strobe Device Yes, Yes Pass
7/
202,0)
Hall by Stairwell A13 Horn/Strobe Device Yes Yes Pass,
2020)
Copyright 2020 Inspect Point Page'7 of 30
Report of Inspection/Test
Annual NFPA 72 IMPACT
04/07/2020 Conducted by:Jason DeFeudis FIR.E
Property 26 HanVstdro Nve,Hudson,NH 03051
NORTH ANDOVER MIDDLE SCHOOL Impact Fire Services-Hudson �(603)2934531
261 SmU$tre e'd,Vft.ce 3 W,MA 0,1 OW
15,8039 (W$)65ZT2,27
Building 3,80679 MM.GETFIREPROTECTION.COM
495 MAIN S�TREET
NORTH,ANDOVER M 5
GREG ROBERTS
978-994-6673
Address Location Device Type Factory Measured Visual Functional Pass/
Setting Setting Fall,
C1 01 Horn/Strobe Device Yes Yes, Pass
(04107/
2020)
H alth Office Horn/Strobe Device Yes Yes, Pass
Restr'oom (04/07/
2020)
Health Office Horn/Strobe Device, Yes Yes Pass
(04/07/
2020)
C1 09 Horn/Strobe Device, Yes Yes Pass
(04/0'71
2020)
C1 02 Horn/Strobe Device Yes Yes Pass
(04/071
2020)
C1 08 Horn/Strobe Device Yes Yes Pass,
1(04/07/
2020)
Cl 03 IHorn[Strobe Device Yes Yes Pass
2020),
C1 07 Horn/,Strolbe Device Yes, Yes Pass
2020)
C1 04 Horn/Strobe Device Yes Yes, Pass
(04/07/
20,20)
-7 1
C1 05, Horn/Strobe Device Yes Yes Pass
(04/07/
2020)
C11 06 Horn/Strobe Device Yes Yes Pass
(04/07/
20,20)
Hail by Cafeteria Hoar/Strobe Device Yes Yes Pass,
Entrance (04107/
2020)
Cafeteria Horn/Strobe Device No, No Fail
2020)
Cafeteria Side Exit 2 Horn/Strobe Device Yes Yes Pass
(04/07/
2020)
Cafeteria Side Exit 1 Hiorn/Strobe Device, Yes Yes Pass,
(04/071
2020
Copyright 2,020 Inspect Point Page 8 of 30
Keport of Inspection/Test
Annual NFPA72
I M ,�,���P C,T
04/07/2020 Clonducted.by,,jas,on, DeFeudis FIRE
Property 26 Hanipshke Wye,Hudson,NH 03051
Impact Fire Service�s-Huds ( ) 7 ion, 603 293-531
NORTH ANDOVER MIDDLE SCHOOL 261 Brooks Stmak WWcester,MA 016W
158039 (508)862-7227
Building#:380679 WAW.GETFIREPROTECTIMCOM
495 MAIN STREET
NORTH ANDOVER MA 018,45
GREG ROBERT'S
978-994-66713
Address Location Device Type, Factory Measured Visual Functional Pass/
Setting Setting Fail
Cafeteria Horn/Stroble Device Yes Yes Pass
(104/07/
2020)
Kitchen Food Serve Horn/Strobe Device Yes Y es Pass
Line 1 7/
2020)
Kitchen Service Exit Hoirn/Strobe Device Yes Yes Pass
(0:4107/
2020)
Kitchen Restroom Strobe Device Yes Yes Pass
(04/0711
20201)
Hall by Snack Room Horn/Strobe Device Yes Yes Pass
2020)
Restroom B Strobe Device Yes 'Yes Pass
7/
202,0)
Restroom,A Strobe Device "des Yes Pass
(04/07/
2020)
Hall by Cafeteria IHorn/St'robe Device Yes, Yes Pass
�Entranc�e
2020)
Kitchen Food Serve Horn/Strobe Device Yes Yes Pass
Checkout, (04/07/
2020)
Horn/Stirob!e,Device
Cafeteria Side,Exit, 'des Yes Pass
(04/07/
2,020)
Cafeteria Ho,rn/,Strobe Device Yes, Yes Pass,
(04/017/
20,20),
fCafinteriaExit to Horn/Strobe Device Yes Yes Pass
ssro%'o' ms
2020)
A 'Istant Pr* Yes
ss incipal Horn/Strobe Device Pass Yes (04107/
Office, 2020)
Conference F103- Horn/Strobe Device Yes Y s Pass
Resident Officer (04/071
2020)
Staff Restroom 1048 Strobe Device Yes Yes Pass
(04/07/
2020)
Copyright 2020 Inspect Point Page 9 of 30
Report of Inspection/Test
Annual N,FPA 72
I','M PA�C T
04/07/2020 Conducted by:Jason DeFeudis FIRE
Propert,y 26 HarVshire Ddva,,Hudson,NH 03061
NORTH ANDOVER MIDDLE SCHOOL, Impact Fire Services,-Hudson (603)293-753t
261 Bimoks Smoot Wxce ster,MA 0 1,606
1158039 (M)852-7227
Building#,, 380679 WAW.GETFIREPROTECTION40M
495 MAIN STREET
N 0 RTHAN D OVER MA 0 1 845
DREG,ROBERTS
978-994-6673
Address LocatelW DeviceType Factory Measured Visual Functional Pass/
Ing
Setting Seft' Fail
Side Exit by Stairwell Hoar,S,trobe Device Yes Yes Pass
13C ( /07/
2020)
Hall by Room,F1 06 Horn/Strobe Device Yes Yes Pass
(04/0,7/
2020)
Hall by Room F1.09 Horn/Strobe Device Yes, Yes Pass
(04/07/
20201)
Hall by Room,1111 Horn/S,trobe Device Yes Yes Pass
(04/07/
2020)
Hall by Stairwell C Horn/S,trobe Device Yes Yes Pass
(04/071
2,020)
Hall by Stairwell C,Exit Horn/Strobe Device Yes Yes Pass
2020)
Girl"s Room Strobe Device Yes Yes Pass,
(04/07,/
2020)
F1 07 Horn,/Strobe Dev"' pass
Ice Yes Yes
(04107/
2020)
F1 06 Horn/Strobe Device Yes Yes Pass
(04/07/
2020)
F1 05, Horn,/Strobe Device Yes, Yes Pass
(04/07/
2020)
F1 08 Horn/Strobe Device Yes, Yes pass
(04/0711
20,20)
F1 109, Horn/Strobe Device Yes Yes, Pass
(04/07/
2020)
F1 02 Hiorn/Strobe Device Yes Yes Pass
(04/0,7/
2020),
F110 Horn/Strobe,Device Yes Yes Pass
(04/07/
2020)
F111 Horn/Strobe Device Yes I Yes Pass
(04/07/
2020)
Copyright 2020 inspect Point Page 10 of:30
Report of I nspection/Test,
Annual NFPA 72 iI M P.A CT
04107/2020 Conducted!by:Jason DeFeudis FI'RE
Property 26 Hanigsbire Wva.Hudsion,NH 03051
NORTH ANDOVER MIDDLE SCHOOL Impact Fire,Services-Hudson, (603)2934531
261 B(ooks Streat Wwcester,MA 0,1606
158039 (608)852.7227
Building#:380679 WoMOETFIREPROTECTION.COM
495 IMAIN STREET
N ORTH AN DOVER MA 01845
GREG,ROBERTS
978-994-6673
Address Location Device Type Factory Measured Visual Functional Pass/
Setting Setting Fail
F1 01 Horn/Strobe Device Yes Yes Pass,
(04/07/
2020)
Hall,exit to Courtyard Horn/St.robe Device 'Yes, Yes Pass
(04107/
2O20)
Hall by Gymnasium Horn/Strobe Device 'Yes, Yes Pass
(04/07/
20201)
Hall by Gymnasium Horn/Strobe Device Yes Yes Pass
(04/07/
2,0,20)
Gymnasium Exit Horn./Strobe Device Yes Yes, Rays
(014/07/
2,020)
Yes Pass
Gymnasium Exit Hiorn/Strobe Device Yes
2020)
Gymnasium Exit, H rn/Strobe Device Yes Yes Pass
(04/07/
2020),
,Gymnasium Exit rn/Strobe Device Yes Pass
(014/07/
2020)
Faculty Room Horn/Str Device Yes Yes Pass
(04/07/
2,020)
Faculty Work Center Horn/Stro,be Device Yes Yes Pass
(04/07/
20,20)
Related Arts Offices Horn/Strobe Device Yes, Yes Pass
(04/07/
2020)
Gym,Laidles Restrolom Strobe Device Yes Yes Pass
(104/07/
2020)
Gym,Girls Locker Strobe Device 'Yes Yes Pass
Room, (04/07/
2020)
Gym Girls Locker Horn/Strobe Device Yes Yes Pass
Room (04/0'7/
2020)
Gym Girls Locker Strobe Device Yes Yes Pass
Room
2020)
Coplyrilght.202,0 Inspect Point Page 11 of 30
Report, of Inspection/Test
Annual NFPA 72
I M,PA C
4722 Conducted by:Jason DeFeudis FIRE
Property 26 hanVsWe Ddve,Hudson,,14H 030,51
DDL
NORTH ANDOVER MIE SCHOOL Impact Fire Services-Hudson (603)293-7531
261 Brooks Street Womaiator,,MA 0 1 W
158039 (5W)852.7227
Building#:1 380679 MMGETFIREPROTECTIORCOM
495 MAIN STREET
NORTH ANDOVER MA 01845
GREG ROBERTS
978-994-6673
Address Location Device Type Factory Measured Visual, Functional Pass/
Setting Sett'i ng Fail
Main Office Hall Horn/Strobe Device Yes Yes Pass
(04/07/
2020)
in Office Hall Horn,/Strobe Device Yes Yes Pass
(04/07/
2020)
Main Office,Hall Horn/Strobe Device Yes Yes Pass
(04/07/
2020),
Main Office Horn/Strobe Device Y6s' Yes Piss
(04/07/
2120)
Hallway It by Art Hiorn/Strobe Device Yes Yes Pass
Rooms (04/07/
,2020)
Stairwell D Side Ext Ho Yes Passrn/Strobe Device Yes (04/07/
2020)
Lockers Wing, Horn/Strobe Device Yes y6s Pass
(04/07/
2020)
Hall,by Room S103 Horn/Strobe Device Yes Yes Pass
(04/07/
2020)
Ha ll by Room S 105 Horn/Strobe Device, Yes Yes Pass
(04/07/
2020),
Hall by,Room 5101 Horn/Strob ice Yes Yes Pass
(0410,7/
2020)
S10,5 Florn/Stroble Device Yes Yes Pass
(04/07/
2020)
S106 Horn/Strobe Device Yes, Yes Pass
(04/07/
2020)
S104 Horn/Strobe Device Yes Yes Pass
(04/071
2020)
—7S107 Horn/Strobe,Device Yes Yes Pass
(04/07/
2,020)
5103 Horn/Strobe Device Yes Yes Pa,ss
(014/071/
2020)
Copyright 2020 Inspect Point page 13 of 30
Keport of Inspection/Test
Annul NFPA 7'2,
IMPACT
04/07/2020 Conducted byi-Jason DeFeudis FIR'E
Property 26 Hampstire Dive,Hudson,NHI 03051
NORTH ANDOVER MIDDLE SCHOOL Impact Fire Services- Hudson (603)2934531
261 BroAs Street Worcester,MA01606
1580139 (508),852-7227
Building#A.i 380679, VffiWiGETFIREPROTECTION-COM
495 MAIN STREET
NORTH ANDOVER,MA Oil 845
GREG ROBERTS
978-994-6673
Address Location Device Type Factiory Measured Visual Functional Pass,/
Setting Setting Fail
S1 08 Horn/Strobe Device Yes Yes Pass,
2020)
S102 Horn/Strobe Device Yes Yes Pass
1(04/07/
2020)
S110 Hoirn/Strobe Device Yes Yes Pass
(04/07/
2020)
Sil 09-Con fe re nice Horn/Strobe Device Yes Yes Pass
(04,107.1
2020)
S1111 Horn/Strobe Device Yes Yes Pass
(04/071
2020)
S11101, Horn/Strobe Device Yes Yes Pass
(04/07/1
20,20)
Stairwell CD Hoirn/,Strobe Device, Yes Yes Pass
(04/07/
2020),
Rear Main Entrance Horn/Strobe Device, Ye's Yes Pass
(04/07/
2020)
Hall by Re strop ms- Horn/Strobei Device Ye's Yes Pass
Rear Main Entrance
2020)
Staff Restroorn by Rear Strobe Device Yes es Pass
Main Entrance, (04/07/
2020)
Girl's Po by Rear Horn/Strobe,Device Yes Yes Pass
Main Entrance
20,20)
Boys Room by Rear Horn/Strobe,Device Yes Yes Pass
Main Entrance (014/07.1
2020),
Project Room Horn/Strobe Device Yes Yes Pass
(04.1071t
2020)
Court a,rd Horn/Strobe Device Yes 7Yes Pass
(04/07/
2020)
Courtyard Horn/Strobe Deice Yes s Pass
(04/07/
rrrrrrrrrrrrr.--
Copyright 2020 Inspect Point Pale 14,of 30,
Report of Inspection/Test
Annual NFPA.72 IMPAC1"
014/07/'2020 Conducted,by:jason, DeFeudis IFIRIE
Property 276HanVsNre Chive,Hudson,NH 03061
NORTH ANDOVER MIDDLE SCHOOL Impact Fire Services-Hudson (603)293-7531
26 1 Brooks Sbv et'Wo(ce sler.MA 0 1606
158039 (M),852-7227
Building#: 380679 WNW.GETFIREPROTECTIORCOM
495 MAIN STREET
NORTH ANDOVER MA 01845
DREG ROBERTS
978-994-6673
Address Location Device Type, Factory Measured7 Visual, Functional Pass/
Setting Setting Fall
Hall by Project Room Horn/Strobe Device Yes, Yes Pass
(04/071
2020)
Basement By Boilers Horn/Strobe Device Yes Yes Pass
(04/07/
2,020)
Basement Electrical Horn/Strobe Device Yes, `es Pass
Room, (04/07/
2020)
Basement Hall Horn/Strobe Device 'des Yes Pass
(104/07/
2020)
end Floor Hall'by Stair Horn/Strobe Device Yes Yes, Pass
A (04/07/
2020)
2nd Floor,Hall by Rm Horn/Strobe,Device Yes Yes Pass
C201 (014/07/
2020)
2nd Floor Hall b, Rm,C Horn/Strobe Device Yes Yes Pass
2,20 y (04/0711
1 2020)
2nd FloorHall by Rm Horn/Strobe,Device Yes Yes Pass
C204 (04/07/
2020)
2nd Floor Hall by Hoirn/Strobe D ice Yes Yes Pass
Stairwell AB (04/07/
2020)
J
,2nd Floor Room by Horn/Strobe Device Yes Yes Pass
Stairwell
2020)
2ndl Floor C201 Horn/Strobe Device Yes Yes Pass
(04/07/
20201)
2nd Floor C21 0 Hor,n/St�robe Device Yes Yes Pass
(0,4/07/
2020)
2nd Floor C2019 Horn/Strobe Device Yes Yes Pass
(04/07/
2,02,0)
2nd,Floor C,202 Horn/Strobe Device Yes, Yes Pass
(04/07/
20120)
2nd Floor C208 Horn/Strobe Device Yes Yes Pass
(04/07/
2020)
Copyright 2020 Inspect,Point Page 15 of 30
Insanction/Test
Kcpwrlwt 1i
Annua] NFPA 72 IMPACT
04/07/2020, Cmducted by:Jason DeFeudis F-KIRE
Property w 26 HanVshire Ddve,Hudson,INH,03051
Impact�Fire Services-Hudson (603)293-7531,
NORTH,ANDOVER MIDDLE SCHOOL, 261 BmoXs Street Vftcsslor,?AA 0 1 W
158039 (606)852'.7227
Building#:380679 AWW.GETF IRE PROT ECTION-COM
495 MAINSTREST
NO'RT HAN DOVER MA 01845
GREG ROBERTS
978-994-6673
Address Location Device Type, Factory I Measured Visual l Functional Pass/1 1
Setting Setting Fail
2nd Floor C203 Horn/Strobe Device Yes Yes Pass
(014/07/
2020)
2nd Floor C204 Viorn/Strobe Device Yes Yes Pass
(04/07/
2020)
2nd Floor C207 Horn/Strobe Device Yes Yes Pass
(014/07/'
2020)
Yes Yes Pass
2nd Floor Boy's Room Strobe,Device
(04/07/
2020)
2nd Floor Staff Strobe,.Device Yes Yes IPass
Restroom
2020)
2nd Floor Girl's Room Strobe Device Yes Yes, Pass
2020)
Main Courtyard To Horn/Strobe Device Yes Yes Pass,
Cafeteria Entrance, (04/07/
2020)
2 nd Floor all by Horn/Strobe Device Yes Yes Pass
Room F205
2020)
2nd Floor Hall b Horn/Strobe,Device Yes Yes Pass
Room F206 (04/07/
2020)
2nd Floor Hall by Horn/Strobe Device Yes Yes Pass
Room F208, (04/07/
2020)
2nd Floor By Stair C Horn/Strobe Device, Yes Yes pass
(04/07/
2020)
2nd Floor F204 Horn/Strobe Device Yes, Yes Pass
(04/07/
202,0)
2nd Floor F205 Horn/Str be Device Yes Yes Pass
(04/07/
2020),
2nd Floor F206 Horn/Strobe Device 'Yes Yes Piss
(04/07/
,2020)
2nd Floor F207 Horn/Strobe Dievice Yes Yes Pass
(04/071
2020)
Copyright 2020 Inspe,ct Point Page 16 of'30
!
�
04/07/2020 Conducted by:Jason DeFeudis FIRE '
|
Report of Inspection/Test
An,nual NFPA 72 '1 M PA�C"r
014/072020 Conducted by-,Jason DeFeudis E
Property 26 HanVsNre Ddve,Hudson.NH 0,3051
2913-7,53
NORTH AN VER MIDDLE SCHOOL Impact Fire Services,- Hudson (6W) 1
1581039 26 J Brooks,Steak Wwws 1,0 r.FAA 0 1606
(60)662-72,27
Building#:380679 V%UM.,G E,TFIR E PROTECT 10N.COM,
4195 MAIN STREET
NORTH ANDOVER MA 01845
GREG ROBERTS
978-9194-6673
Address, Location Device Type Factory Measured Visual Functional Pass/
Setting Setting Fal I
2,nd Floor S202 Horn/Strobe Device Yes Yes Pass
(04,107it
2020)
2mid Floor S208 Horn/Strobe Device Yes Yes Pass
(04/017/
2020)
2nd Floor S203 Horn/Strobe Device Yes Yes Pass
(04/07.1
2020)
2nd Floor S207 Horn/Strobe Device Yes Yes Pass
(04/07/
2020)
2mid Floor S204 Horn/Strobie,Device Yes Yes Pass
(04/07/
2020)
2nd Floor S206 H rn/Strobe Device, Yes Yes Pass
(04/07/
2020)
2n,d Floor 5205 Horn/Strobe Device, Yes Yes Pass
(04/07/
2020)
L5,D45 Cafe corridor Smoke Detector Not Tested Not Tested NiotTested Not Tested Not
i
Tested,
L5D44 Cafe coirridior Smoke Detector Not'TeStred Not Tested Not Tested Not Tested Not
Tested
L5,D461 Cafe corridor Smoke Detector Not Tested Not Tested Not Tested I Not Tested Not
Tested
L5D47 Cafe coirridor Smoke Detector NotTesteld NON otTested Not Tested Not,Tested Not
I Tested
1_41348, Cafe corridor Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
Te sited
L51D49 Cafe corridor Smoke Detector Not Tested! Not Tested Not Tested: Not Tested Not
Tested
L5D1 1 House 1 vestibule Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
Tested
L5D,1 0 House 1 corridori Smoke Detector Not Tested, Not Tested Not Tested Not Tested Not
Tested
L5DO1 House 1 corridor Smoke Detector of Tested NotTested Not Tested Not Tested Not
Tested
L5,DO,2 House 1 corridor Smoke Detector Not Tested Not Tested N Te ot st Not Tested Not
Tested
Copyright,2020 Inspect Point Page 18 of 30
Report of Inspection/Test
Annual NFPA 7'2, IMP,ACT
041/07/2020 Conducted,by:Jason.DeFeudis E
ry
26 Hampshire Drive,Hudson,NH 0301
NORTH ANDOVER MIDDLE SCHOOL Impact Fire,Services-Hudson (603)2934531
261 woks Street,AVcoster,MA 01606
158039, (�O8)852.72,27
Building#:380679 V�NM,43E,TFIIREPROTECT'ION.C,OM
495 MAIN STREET
NORTH ANDOVER MIA 01845
GREG ROBERTS
978-994-6673
Address, Location Device Type Factory Measured Visual Functional Pass/
Setting Setting Fail
L5D03 House 1 corridor Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
'Tested
L5D04 House 1 corridoir Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
Tested
L5,D,05 House 1 corridor Smoke Detector Not Tested Not Tested: Not Tested Not'Tested Not
Tested
L5DO6 House 1 corridor Smoke,Dietiector Not Tested Not Tested Not Tested Not Tested Not
Tested
lL5DO9 House 1 stairs Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
Tested
L15D1 5 House 1 entry Smoke Detector Not Tested' Not Tested Not Tested Not,Tested Not
Tested
L2DO5 Corridor multipurpose Smoke Detector NotTested NotTested Not Tested I Not Tested Not
room t Tested
M03 Corridor multipurpose 1 Smoke Detector Not Tested Not Tested Not TO sted Not Tested Not
room Tested
L2D102 Corridor multipurpose Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
room 'Tested
Staff mens Rm.1075 H eat-Ra,te- Rise Not Tested Not Tested Not Tested Not Tested Not
Tested
L2D,01 Corridor multipurpose Smoke,Detector Not Tested NotTes,ted Not Tested Not Tested. Not
room Tested
L2D30 House 3 stair 1086 Smoke Detector Not Tested Not Tested Not Tested N t Tested Not
Tested
BD25 Auditorium ramp to, Smoke Detector Not Tested riot Tested Not,Tested Not Tested Not
house 3 Tested
L,3D78 Auditorium ramp Smoke,Detector blot Tested Not Tested Not Tested Not Tested Not
Tested
Smoke Detector Not Tested Not Tested
LZD22 House 3 stairway 1099 Not'Tested NotTested Not
'Tested
L2,D,23 House 3 stairway 1099 Smoke Detector Not Tested, NotTested Not Tested Not Tested Not
Tested
L2D24 House 3 stairway 10919 Smoke Detector Not Tested Not Tested Not Tested of Tested Not
Tested!
N
L,2D25 House 3 stairwayl 099 Smoke Detector Not Tested Not Tested Not Tested Not Tested otTested
L2D26 House 3 stailrWay 10,82 Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
T ested
Copyright 2020 Inspect Point Paige 19 of 30
Report OT inspection/Test
Annual NFPA 72
I M P,A C;T
04/07/2020 Conducted Jason DeFeudis, IW"FIRE
Property, 26 HanVshirs No,Hud!so�n,NH,03061
�NIORTH ANDOVER MIDDLE SC'HOOL Implact Fire Servic,e's,-Hudson (603)293.7531
261 Brooks StreeL ceder,MA 01W
15,8039 (608)852-7227
Building MI:380679 WMOETFIREPROTECTIONCOM
4,95 MAIN STREET
NORTH ANDOVER MA 01845
GREG,ROBERTS,
978-994-166,73
Address, Location Device'Type Factory Measured Visual Functional Pass/
I � Setti ng Setting I Fail
L2D29 House 3 lobby Smoke Detector Not Tested Not Tested Not Tested Not.Tested Not
Tested
L2D45 Ramp.AdminJ library Smoke Detector Not Tested NotTested NotTested NotTested Not
Tested
L2D44 Ramp.Admin./library Smoke,Detector Not Tested Not Tested Not Tested Not Tested Not
Tested
L2D51 Adm,in./library Smoke Detector, Not,Tested Not TO,sted Not'Testecl Not Tested Not
c o "dor Tested rri
L2D50 AdmInJ library Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
corridor Tested
L2D49 Admin./library, Smoke Detector Not Tested Not Tested, Not Tested, Not Tested Not
corridor Tested
1-2048 Admin./library Smoke Detector Not Tested Not Tested Not.Tested Not Tested Not
corridor Tested
L2D47 AdmInJ library Smoke Detector, Not Tested Not Te s tle d, Not Tested Nat Tasted Not
corridor Tested
'L2D55 Admin./library Smoke,Detector Not Tested Not Tested Not Tested riot T ested Not
corridor Tested
L,2D54 Admin./library Smoky Detector Not Tested NotTasted Not Tasted of Tasted Not
Corridor Tested
orn
L2D46 Admin./library Smoke Detector Not Tested Not Tested' Not Tested' Not Tested Not
corridor Tested
L3D24 Auclitorium ramp, Smoke Detector, Not Tested Not Tested Not Tested Not Tested Not
Tested
L3
Tested Not Tested Not Not Tested Not D37 Auditorium viestIbule Smoke Detector N o�t T e Tested
L3D,316 Auditorium corridor Smoke Detector Not Tested Not Tasted Not Tested Not Tested Not
Toted
UD35 Auditorium corridor Smoke Detector Not Tested N lot Test�ed' NotTasted Not T ested Not
Tested
M34 Auditorium corridor Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
'Tested
L3D33 Auditorium corridor Smoke Detector Not Tested Not Tested Not Tested Not T Osted Not
Tested
L3D31 diitorium. corridor Smoke Detector Not Tested NotTested Not Tested Not Tested Not
Tested.
M32 Auditorium,corridor Smoke Detector Not Tasted Not Tested Not Tested Not Tested Not
'Tested
Copyright 2020 Inspect Point Page 20 of 30
fl
Meport of I Ilon/Test
Annual NFPA 172 Conducted by:Jason DeFeudis IIIMP,ACT
04/07/20,20 FIRE
Property 26 Ho nVthlta Ddve,,Hudson,N H 03051
NORTH,ANDOVER MIDDLE SCHOOL Impact Fire Services Hudson (OW)2 7 1
261 Bm�$Stm, et,WWce Merl 1AA 0 1606
158039 (508)02-7227
Building#',,,38,0679, WAW,,OETFIRE,PROTE,C,'TIONICOM
495 MAIN STREET
NORTH ANDOVER MA 01845
GREG RO,BE,RT,S
91718-994-66173
Measured Visual Funictional Pass/
Address Location Device Type Factory A Paid
Setit" 9 Setting
Niot'Tested Not Tested Not Tested NotTestied Not
L3D,30 Auditorilum,corridor Smoke Detector, Tested
Not Tested 7 Not'Tested, Not,Tested Not Tested Not
BD29 Auditorium corridor Smoke Detector Tested
Custodian closet'l 107 Not Tested Not Tested Not'Tested Not Tested Not
Tested
Smoke Detector, Not Tested Not Tested Not—Tested Not Tested Niot
BD28 Auditorium corridor Tested
BD27 Auditorium corridor Smoke Detector Not Tested' Not Tested Not Tested Not Tested Not
Tested
L2D26 Auditorium corridor Smoke Detector Not Tested Not Tested Not Tested Not Tested Not,
Tested
L3,DO,9 House 2 lobby Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
Tested
L3D1 01 House 2 lobby Smoke Detector NotTestedi Not Tested Not Tested Not Tested Not
'Tested
—7
BW 1 House 2 lobby Smoke,Detector Not Tested Not Tested Not Tested NotTested Not
Tested
L3D0,7 House,2 stairs 1002 Smoke Detector, Not Tested Not Tested Not Tested Not Tested No t
Tested
grid Smoke Detector Not Tested Not Tested Not'Tested Not Tested Not
L31302 House 2 corn Tested
--7
BD03 House 2 corridor Smoke Detector Not Tested Not Tested Not Tested, Not T estd Not,
Tested
BD05 House 2 corridor Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
Tested
L31306, House 2 corrid r Smoke De tector No t Tested Not Tested Not Tested N Notot Tested Tested
7
L3D7'7 Exit by C1 05 Smoke Detector NON otTested Not Tested Not Tested Not Tested Not
11 Tested
L5D25 Kitchen corridor Smoke Detector Not,Tested NON otTested Not Tested Not Tested Not
Tested
L5D43 Cafe corridor Smoke Detector Not Tested Not Tested, Not Tested Not Tested Not
Tested
Tested Not Tested Not
L5D42 Cafe corridor Smoke Detector Not Tested Not Tested Not
Tested
D042 Rtu-1 0 ad min office Duct Detectors Not Tested Not Tested Not Tested Not Tested Not
Tested,
Copyright.2020 Inspect Point Page 21 of 30
sr
Report, of Inspectelon/Test
Annual NFPA 72
I M PA C T
04/07/2020, Conducted by:Jason DeFeudIs FIRE
Property 26 Ha,rVshtro Ddve,Hudson,,NH 005t
NORT H ANDOVER MI DDLE SCHOOL Impact Fire Services-Hudson. (603)2934531
261&ooks SVee L V*(ce ster,MA 0 1606
158,039 (508)852.7227
Buflcling#,*380679 WNW.GETFIREPROTECTION.COM
495 MAIN STREET
NORTH ANDOVE R M,A 01845
GREG ROBERTS
978-994-6673
Measured Pass/
Address, Location Device Type Factory Visual Fu,nctional
Setting Sevin I F al"I
D095 Ahu-1 0 admin office Duct Detector's Not Tested Not Tested Not Tested Not Tested Not
Tested,
D043 Rtu-8 admin office Duct Detectors Not Tested Not Tested Not Tested Not Tested Not
Tes1te
D072 Ahu-6 h�ouse 2 Duct Detectors Not Tested Not Tested' Not Tested NotTested Not
T ested
D073 Ahu-S,House 2 Duct Detectors Not Tested Not Tested Not Tested Not Tested Not
Tested
D035, Ahu-1 2 kitchen Duct Detectors Not Tested Not Tested, Not Tested Not Tested'! No t
F Tested
D041 Rtul-6 house 3 Duct Detectors Not Tested Not Tested Not Tested Not Tested Not
'Tested
D079 Duct smoke 2nd floor, Duct Detectors Not Tested Not Tested Not Tested Not Tested Not
me h.Boon Tested
M112 1 st flr house 2 Manual Station Not Tested Not Tested Not Tested Not Tested Not
vestibule Tested
113 1 st fl r corridor east, Manua�l Station Not Tested Not Tested NotTested Not Tested Not
house 2 Tested
M139 Auditorium stage area Manual Station Not Tested Not Tested Not Tested Not Tested Not
I 'Tested
M138 Auditorlurn rarnip Manual Station Not Tested Not Tested Not Tested Not Tested Not
Tested
M140 Auditorium stage area Manual Station Not Tested Not Tested Not Tested Not,'Tested Not
Tested
M 1 1 Auditorium vestibule Manual Station Not Tested Not Tested Not Tested Not Tested Not
Tested"
M131 1 st,fir house 3 Manual Station loot T ested riot Tested Not Tested' Not Tested Not
stairway door Tested
M120 1 st fir house 3 Manual Station Not Tested' Not Tested Not Tested Not Tested Not
stairway Tested
Ml 3 5, 1 st fir house 3 corridor Manual Station Not Tested blot Tested Not Tested Not Tested Not
Tested
M1133 House 3 stairway door Manual Station Not Tested Not Tested Not Tested Not Tested Not
1086 Tested
M134 1 st fir house 3 entry Man l Station Not Tested NotTested Not Tested Not Tested Not
Tested
M132 1 st fl r st a it ! 1 Manual Station Not Tested, Not Tested Not Tested Not Tested Not
Tested
Copyright 2,020 Inspect Point Page 22 of 3 ,
'rt oT Inspection/Test
Annual N,FPA 72,
IMIPA,.CT
04/07/2020 Conducted by:Jason, DeFeudis FIR.E
Proplerty 26 Harpstire W,ve,Hudson.NH.10305 1
NORTH AND,O�VER MIDDLE SCHOOL Impact Fire Services-Hudson (603)293-7531
261 Sm�s Street,Wmaster,MA 01W
158039 (60),85,2.7227
MWGURREPROTECTM-COM
Building#j:3,801679
495 MAIN STREET
NORTH ANDOVER MA 01845
GREG ROBERTS
978-994-66,73
,Address Location, Device Type Factor,y Measured Visual Functional Pass/'
Setting Setfing F a
M198 2nd fir house 3 Manual Station Not Tested Not Tested Not.Tested loot Tested Not
stairway 2040 Tested
M199 House 3 stairway 2046 Manual Station Not Tested Not Tested Not Tested allot Tested Not
'Tested
M11 09 Stage door Manual Station Not Tested Not Tested Not Tested blot Tested Not
Tested
M106 Multipurpose rm Manual Station Not Tested Not Tested Not Tested Not Tested Not
south door Tested
Ml 07 Multipurpose rm east Manual Station Not Tested Not Tested Not Tested Not Tested Not
door Tested
Mi 08 Multipurpose west Manual Station Not Tested Not Tested, Not,Tested Not T ested Not
door Tested
M
,ill Gym northwest door Manual Stati on Not Tested Not Tested Not Tested Not,Tested Not
'Tested
Ml,13 Gym northeast door Manual S,t tion, Not Tested Not Tested Not Tested Not Tested Not
Tested
M 117 1 st it house 1 corridor Manual Station Not Tested. Not Tested Not Tested N Notot Tested 'Tested
east
Nil 1,8 1st f1r horse l stair Manual Station Not Tested Not Tested Not Vested Not Tested Not
Tested
M11 19 1 st fir house 1 Manual Station, Not Tested blot TO s te d Not Tested Not Tested Not
vestibule 'Tested
M138 2nd flr house 1 Manual Station Not Tested Not Tested Not Tested Not Tested Not
stairway Tested
Ml 39 2nd fir house,1 Manual Station Not Tested Not Tested blot Tested Not Tested Not
stairway Tested
M1 52 Cafe kitchen a south Manual Station Not Tested Not Tested Not Tested, blot Testecl Not
Tested
M153 Cafe kitchen.A north Manual Station Not Tested loot Tested Not Tested Not Tested Not
Tested
M154 Kitchen by storage rm Manual Station Not Tested Not Tested Not Tested Not Tested Not
109 1 1 1 Tested
Ml 5,0 Kitchen b south Manual Station Not Tested Not Tested Not Tested Not Tested Not
Tested!
M 151 Kitchen b north Manual Station Not Tested Not Tested Not Tested Not Tested Not
Tested
M155 i Ktchen coirridor b Manual Station Not Tested Not Tested Not Tested Not Tested iOL
door Tested
Copyrig,ht,2020 Inspect Point Page 23 of 30
Report ot i c ion/Test
Annual NFPA 172
IMPACT
04/07/2020 Conducted by:,Jason D�eFeudis F'IIRE
Property 26 anV Hshlra Dfive,Hudsm,NH 03061
NOR MID
TH ANDOVER DLE SCHOOL Impact Fire Services-Hudson, (M)293-7531
'261,Sroo�s Sirest AWc*S(ef,PAA01606
158039 (508)852.7227
Building#1:38,10679 WhWOETFIRE PROT,ECTION.00M
495 MAIN STREET
NORTH ANDOVER MA 01845
GREG ROBERTS
9,78-994-6673
7 —7
Measured Visual Functional Pass/
Add,ress Location Device,Type Factory IF al"I
Setting Sletting I
-7ested Not Tested Not
M11 33, Kitchen stairway Manual Station. NotTested Not Tested Not T 'Tested
M1 68 2nd fir house 2 Manual Station Not Tested NotTested Not Tested Not Tested Not
stairway 2009 Tested
M 1,67 2n,d fir house 2 Manual,Station Not Tested Not Tested Not Tested Not Tested Not
sta i rway 2 0 02 Tested
M1 16 1 st fir house 1 entry Manual Station Not,Tested Not Tested Not Tested Not Tested Not
Tested
BASEMENT Manual Station Not Tested Not Tested Not Tested Not Tested Not,
Tested
BASEMENT Smoke Detector Not Tested Not'Tested I Not Tested Not Tested Not d
Teste
BASEMENT Smoke Delector, Not Tested Not Tested Not Tested N ot Te,ste d Not
Tested
BASE,ELEC ROOM, Smoke,Detector Not Tested Not.Tested Not Tested Niot Tested Not
Tested
BASE GENERATOR 'Smoke Detector Not Tested Not,Tested Not'T ested Not Tested Not
ROOM Tested
STAIRS TO BASEMENT Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
'Tested
MAIN ENTRANCE Manu�al,Station Not Tested Not Tested Not Tested Not Tested Not
Tested
HALL NEAR PANEL Manual,Station Not Tested NotTested Not Tested Not Tested Not
Tested
TOP OF AND FLOOR, Smoke Detector Not Tested Not Tested pilot Te s te d Not Tested Not
TAIRS Tested
S
NEAR ELEVATOR 2ND Manual Station Not Tested Not Tested Not Tested Not Tested Not
FLOOR Tested
OUTSIDE S206 Smoke Detector Not Tested Not Tested Not'Tested Not Tested Not
Tested
OUTSIN 207 Smoke,Detector, Not Tested Not Tested! Not Tested Not Tested Not
Tested
OUTSIDE S,208 Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
Tested
Not
Not Tested Not Tested Not Tested
OUTSIDE�S2,0,9 Smoke Detector NotTestied: Tested
Not Tested Not Tested Not Tested No of Not
NEAR WEST STAIRS Manual Cation Tested
2ND FL. J
Copyright 2020 Inspect Point Page 24 of 30
Report of Inspection./Test
Annual NFPA 72 IMP,ACT
04/07/2020 Conducted by:Jason DieFeudis FIRE
Property 26 HanVshlro Dfive,Hudson,,NH 0306t
NORTH ANDOVER MIDDLE SCHOOL Impact Dire Services-Hudson (603)293-7531
158039 26 1,Wooks SUv st cede(,MA 0 IM
(5N),852-7227
V�".GETFIREPROTECT]09COM
Building#:1 380679
495 MAIN STREET
NORTH ANDOVER MA 01845
GREG ROBERTS
978-994-6673
-7
Address Location Device,Type Factory Measured Visual Functional Pass/
Setting Setting Fail
WE
Not Tested Not Tested Not Tested Not ST STAIRS 2ND Smoke Dietector Not Tested T,ested
FLOOR
NEAR F205 Smoke Detector Not,Tested Not Tested Not Tested Not Tested Not
Tested
NEAR F205 Manual Station Not Tested Not Tested Not Tested NotTested Not,
Tested
NEAR F2016 Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
Tested
NEAR F208 Smoke Detector Not Tested Not Tested Not Tested Not Tested Not
Tested
N EAR F201, Smoke,Detector Not Tested Not Tested Not Tested Not Tested Not
Tested,
STAIRS NEAR F201 Smoke Detector Not Tested Not Tested Not Tested Not,Tested Not
Tested
STAIRS NEAR 1`201 Manual Station Not Tested Not T ested Not Tested Not Tested Not
Tested,
STAIRS NEAR C206 Smoke Detector NotTested NotTested N ot.Te s te d Not Tested Not
Tested
STAIN S N EAR C206 Manual Station
Not Tested Not Tested Not Tested Not Tested Not
Tested
NEAR C207 Smoke,Detector Not Tested Not Tested NON ot Test ed Not,Tested Not
Tested
NEAR C2,03 Smoke Detector Not Tested Not Tested Not Tested Not Tested, Not
Tested
NEAR C20,9 Smoke Detector Not Tested Not Tested N!ot,TO s te d Not,Tested Not
Tested
NEAR C21 0 Smoke Detector Not Tested Not Tested N o t T e,site, Not Test
Not
Tested'
STAIRS NEAR C21 0 Smoke Detector Not Tested NON otTested Not'Tested Not,Tested Not
'Tested
STAIRS NEAR C21 0 Manual station, Not Tested Not Tested Not Tested Not Tested Not
Tested'
2-195 2rid floor house 3 stair Manual Station Not Tested Not Tested Not Tested Not,Tested Not
2040 Tested
2,-199 2nd fir house 3stair Manual Station Not Tested Not Tested Not Tested Not Tested Not
2046 Tested
2-120 1 st fir house 3 stair Manual Station Not''Tested Not Tested Not Tested Not Tested Not
Tested
Copyright 2020 Inspect Point Page 25 of 30
Report olf Inspection/Test
Annual NFIPA 72
I PA C T
0,4/07/20,20 Conducted by","Jason DeFeudls 'F'IRE
Property a HamipsWre Wile,Hudson,NA 03051
NORTH ANDOVER MIDDLE SCHOOL Implact Fire Services-Hudson (603)293-7531
261 Brook s Stre e k WWce slef.MA 0,1 M
158039 (508)852-7227
Building#,:380679 MKOSTFIREPROT,ECTMCOM
495 MAIN STREET
NORTH ANDOVER MA 01845
GREG ROBERTS,
978-994-6673,
Address Location, Device Type Factory Measured Visual Functional Pass/
is ol F al"I
Setting Settling
2,-131 1 st fl r house 3 stal r Manual Station Not Tested Not Tested Not Tested Not Tested Not
Tested
door
2- rrid NtTested Not Tested NoTested Not
135 1stfirhous Test ed
2,-133 1 st fir house 3 stair Manual Station Not Tested Not,Tested Not Tested Not Tested Not
d,00r1086 Tested
Not Tested I Not Tested Not
2-1�34 1 st fir house 3 entry Manual,Station Not Tested Not Tested Tested
32 1 St fl rl house 3 sta"Ir Manual Station, Not Tested Not Tested Not Tested Not Tested N ot
Tested
1086 —7 1
2-107 multipurpose room Manual,Station Not Tested Not Tested Not Tested Not Tested N ot
"
Tested
east,door
2-106 multipurpose room Manual Station Niot'Tested Not Tested, Not,Tested Not Tested Not
i Tested
South do6r
--I— I - Not,
2-108 multipurpose,room Manual Station Not Tested NotTested NotTelsted Not Tested. Tested
west door
ion Not Tested 'Not Tested Not,TO Ste d Not'Tested Not
Tested
,ym northwest door Manual Sta,t'
2-111 9l
2-1,13 gyrn north,east door Manual Station Not Tested Not T ested NotTested Not Tested No t
Tested
st,ed -7 Not
2-112 gym team roorn door Manual Station Not Tested Not Tested Not Teste:d NotTe Tested
—7
2-110 gym.team room door Manual Station NotTested Not Tested Not Tested Not Tested Not
Tested
5- uI Sttt , Nt Tested t Tst Not Tested Not Tested Not
11 1st floor h
Tested
entry
5-1,17 '1 1st floor h ou sle Manual Station Not Tested Not Tested Not,Tested Not,Tested Not
Tested
corridor
5-118 1 sst floor house 1 sta I r Manual Station Not Tested Not Tested Not Tested Not Tested Not Tested
Not
Not Tested Not Tested
5-119 1 sty'loo,r house 1 Manual Station Not Tested Not Tested 'Tested
vestibulle
5-1,318 2nid floor house 1, stair Manua]Station Not Tested Not Tested No t Tested Not Tested NotTested
tTested Not Tested Not
5-139 2ndf Iloor house,1 stair Manual,Station Not Tested Not Tested No Tested
....... .......
5-153 cafe kitchen A north Manual Station Not Tested Not Tested Not Tested NotTested Not Tested
Copyright 2020 Inspect Point Page,26 of 3,10
Report of Inspection/Test,
Annual NFPA 72
A.CT
0,4107/2020 Conducted by:,Jason DeFeudis FIRE
Property 2,6 HanVsNire Chive,Hudson,NH 03051
NORTH ANDOVER MIDDLE SCHOOL Impact Fire Services-Hudson, (603)293-7531,
61 Bmhs$bree t,'"Woesliar,MA 0 1606
158039 (506)852-7227
Building#:380,679 YffiW.GETF1REPR0TECTt0N.00M
495 WIN STREET
NORTH ANTE R MA 01845
GREG ROBERTS
978-994-6673
Address Location, Device,Type Factory Measured Visual Functional Pass/
Setting Settling Fail
5-152 cafe kitchen A south manual Station Not,Tested Not Tested Not Tested Not Tested Not
Tested
5-154 cafe kitchen by storage M,anua.1 Station NotTested Not Tested, Not Tested N of Tested Not
room 1091 Tested
5-1,5,0 cafe kitchen B south Manual Station Not Tested. Not Tested Not Tested I Not Tested Not
Tested
5-1,51 cafe kitchien B north Manu�al Station Not Tested Not Tested NON otTested Not Tested Not
Tested
51-155 cafe kitchen corridor b, Manual Station Not Tested Not Tested NotTested Not Tested Not
door Tested
5-133 cafe kitchen stair Manual Station Not Tested Not Tested Not Tested NotTested Not
Tested
31-168 2nd floor house 2 stair Manual Station, NON otTested Not Tested Not Tested Not Tested Not
Tested
2009
3-1 i67 2nd floor house 2 stair, Manual Station Not Tested Not Tested Not Tested Not Tested Not
2002 Tested,
3-113 1,st floor house 2 Manual Station NON otTes,tad NotTasted —7 Not Tested Not Tasted Not
corridor east Tested
orn
3-112 1 st floor house 2 Manual Station Not Tested Not Tested NON iotTasted Not Tested Not
vestibule Tested
3-1 1 auditorium,vestibule Manual Station Not Tested Not Tested Not Tested Not Tested Not
Tested
3-1,35 auditorium ramp Manual Station Not Tested Not Tested Not Tested Not Tested Not
Tested,
-1 '1 basement house 2 Manual Station Not Tested Not T ested, Not Tested Niot Tested Not
stair Tested
Copyright 2020 Inspect Point Page 2,7 of 30
Report of Inspection/Test
An�nual NFA 72
IMPACT
04/07/2020 Coriducted by:Jason DeFeudis 1 E
1
F�"I R
Property 26 HafVsNro Ddve,Hudson,NH 03,051
NORTH ANDOVER MIDDLE SCHOOL Impact Fire Services-Hudson (603)293-7531
2�61 Bmks Stre st center,M,A 0 1606
158039, 852-7227
Building#:,,38�06,79 WWWOETFIREPROTECTION-COM
495 MAIN STREET
N 0 RTH AN DOVE R MA 0 1 845
GREG ROBERTS
978-994-6,673
Control Panel and, Batter y R.ea,aings
Location:Front Entrance,
Manufacturer,: Wircom
Model:FX-2000
Dia,ler Phone Number:N/A
Alternate Phone Number,: N/A
Dact Test:N/A
Primary Pho n e,Test: N/A
Scary Phone Test: I .
AC Power Supply Volts DC Power Supply Volts, Load Test W Battery w/Chairger Battery w/Out
AC DC Charger
N/A N/A N/A
Battery Date AC Loss Causes DC Loss Ca ses Battery Voltage&AH Ground Fault
u
Trouble Trouble Rating
N/A N/A N/'A N/A No
Battery VoItage AEI Battery Voltage,AH Battery,Voltage AEI Battery Voltage,&AH
W
Rating Rating w/Charger Rating w/Out Charger Rating Under Load
N/A
Second Battery
AC Power Supply Volts DC Power Supply dolts Load Test W Battery w/Charger Batte ry W/O U L
AC DC Charger
—7
N/A N/A N/A N/A N/A
Battery Date AC Loss Causes DC Loss Causes, Battery Voltage&AEI
Trouble Trouble Rating
N/A N/A N/A N/A
Battery Voltage AH Battery,Voltage AH Battery V ltage AH Battery Voltage&AH
Rating Rating w/Charger, Rating w/Out Charger Rating,Under Load
N/A N/A N/A N/A
Comments
------------
Copyright,2020 Inspect Poinl Page,28 of 30
nu
Report of Inspection/Test
' ,Annual NFPA 72 "T
I M PA C
04/07/2020 Conducted by:Jason DeFeudis, `F!I RE
Property w
26 H s hire Me,Hudson.NH 030611
NORTH ANDOVER MIDDLE SCHOOL Impact,Fire Services-Hudson (603),293,7531
158039 261 mks Street,Mtoester,MAO 16%
460�852-72,27
Building*1 380679 W".GETFIREPROTECTO&COM
495 MAIN STREET
NORTH ANDOVER MA 01845
GREG ROBERTS
978-994-66173
Deficiencies-Quarterly-N.Andover Middle School,-Mircom FX 2,000
Horn/Strobe Device-Cafeteria
Status,Fail
Notes-,
This device failed during inspection per technician Mike St.Aubi,n.,(Outside Cofeteria Serve Line)
Copyright 2020 Inspect Point Page 29 of 30
KUport of Inspection/Test
Annual NFPA 72
IMPACT
04/07/2020, Conducted by.-ijason udis FIR'E
Property 26 HwVshlre,Drive,Hudson,NH 03051
FORTH ANDO�VER MIDDLE SCHOOL Impact Fire Services-Hudson (603)293-7531
1,58039 261 Brooks$",at W*:e seer,MA 0 1606
(50)852-7227
Building#:380679 WNW.GETFIREPROTECTION.COM
495,MAIN STREET
N 0 RTH AN D OVE R MA 0`1845
GREG ROBERTS
978-1994-6673
Inspector Signature
I state that the information on this form is correct at the time and place of my Inspection,and all equipment tested at this time was left in
,operational condition u�pon completion of this inspection except as noted,
Inspector Name Signature Date Completed
Jason DeFeudis 2,0120-04-107
Copyright 2,020 Inspect Point, Page,3,0 of 30