Inspected to the State Adopted version of NFPA 25
ANNUAL DRY SPRINKLER INSPECTION
JOB : 1 1 7 DATE: 07/1 /20 1: o ITS EDT CUSTOMER ID:
SHIP To: BILL To:
NAME NORTH ANDOVER COUNTRY CLUB NAME NORTH ANDOVER COUNTRY Y CLUB
ADDRESS Soo GREAT POND ROAD ADDRESS Soo GREAT POND LOAD
CITY NORTH AND OVER STATE [VGA zip 01 ciTY NORTH Al D VER STATE MA zip 01845
CONTACT Jeff Isbell PHONE E 78)687-7414 EMAIL jisbell@northandoverce.com
osT POD#
TYPE OF SERVICE REGULAR id EMERGENCY ❑
START TIME END TIME VALVE LOCATION Basement
VALVE MAKE Reliable VALVE MODEL D VALVE SIZE 4" #of SYSTEMS 1
FIRE ALARM PANEL MAKE Silent KnIaht MONITORING YES 0 No U NIAU
Al Fire alarm panel in normal upon arrival"? YES Id NO❑ NIA❑
A2 1s the panel&riser accessible? YES Id NO❑ N/A❑
A3 Dry pipe-sprinkler system in normal condition upon arrival? YES 16 NO❑ N/A❑
A4 Alarm lire valve in open position upon arrival? Sealed YES Id NO❑ N/A❑
AS Quick opening device valves open upon arrival? Sealed U? Make/Model: YES ❑ NO❑ N/A I
A6 Air line valve in open position upon arrival?Sealed YES Id NO❑ NIA❑
A7 Sprinkler system air gauge reading before testing 48 psi Q.O.D. Reading before testing psi
A8 Has a full trip test been conducted in the last 3 years? YES id NO❑ NIA❑
A9 Date of last trip test 61612017 Partial ❑ Full
A10 System gauges in good concttlon Date on Guage 2016 YES &d No❑ NIA❑
All is hydraulic or pipe schedule placard attached and legible? YES ❑ NO W NIA U
Al2 All system signs,valve chart in place? YES U No Qd N/A❑
A 3 Spare sprinkler box properly supplied with heads&wrenches? YES id NO❑ N/A❑
A14 Low air pressure switch supervisory/trouble activated properly? In: N/A psi YES ❑ NO❑ N/A Id
A15 Static 110 psi residual 95 psi Size
A16 is residual main drain reading at base of riser at or above hydra lie demand-or re ious reading? YES Ad NO❑ NIA❑
A17 Tamper su erviso /trouble activated properly? YES ❑ NO❑ N/A I
A18 Time to ring alarm from water motor gong less than 5 minutes? YES LJ NO❑ N/A I
A19 Time to ring alarm from pressure switch to panel less than 60 seconds? YES id NO❑ N/A❑
A20 Exterior building alarms activated properly? YES ❑ NO❑ NIA Id
A21 D valve,associated trim,FDD,and air compressor free of damage'? YES 0 NO U NIA❑ :.
A22 Has air compressr oil been changed in the last 12 months? YES ❑ NO❑ ILIA Wr .:
A 3 All control valves accessible and exercised through full range of motion? YES Id NO❑ ILIA❑
A24 QOD Trip at psi seconds Time to restore pressure NIA
A25 All low points drained? How many 8 YES 46 NO EI N/A.
--------------------------------
A26 Alarm line valve left sealed In open position? YES id No❑ NIA Ll
All All valves left in normal condition? YES NO❑ MIA❑
A28 QOD reset and normal' YES ❑ NO❑ NfA I
A29 Fire Department Connection in compliance?Hydrostatically tested In last 5 years? YES ❑ N046 N/A❑
A30 Has an obstruction assessment been performed In the last 5 years?Date: 911f16 Pass's Fail Q Flushed YES 0 NO Q NIA❑
31 Has a pneumatic leak test been performed in the last 3 years?Date: 616M7 Pass 6d Fail❑ YES 0 NO U NIA❑
A32 Has the tank been accessed for obstructions in the past 5 years' YES ❑ NO❑ NIA E
A32 Does fire pump appear to be in good working order? YES ❑ NO❑ NIA I
A33 Has fire pump undergone regular churns as required per NFPA YES ❑ NO❑ NIA lEf
A 4 Does customer own a copy of NFPA 25 and understand hisiher responsibllites,such as low point maintenance YES ja NO❑ NIA❑
p 012517
A3a Heads appear free of leaks and damage? YES Ild NO Q /A p
A36 Heads free of foreign material? YES Q NO46 N/A Ll
A37 Minimum 1 T#clearance from deflector to obstruction's YES Od NO Q N/A Q
A38 All proper escutcheon plates in place's YES Id NO El 1A L1
A39 Standard response sprinkler heads less than 50}years old? ate: YES 0 NO p NIA
A40 Quick response sprinkler heads less than 20 years old? Dante: 2007 YES 0 NO p NIA Ll
A41 rinkier heads less then 10 years old? Date: 2006 YES Ll NOO N/A Ll
A42 Sprinkler heads in harsh environments less than 5 years old? Date: YES U NO Ll NIA I
A43 Have any heeds been tested? Date: YES U NO G1 NIA Id
A43 Exposed piping and hangers in good condition's YES 0 NO 0 N/A Ll
A44 Has standpipe and hose valves been inspected and determined to be in complance in last 12 months? YES U NO Ll N/A Id
A45 Has standpipe been flow tested in last 5 years? YES L7 NO L) N/A 0
A46 Did monitoring compare reoei o signal? YES..L1 NO p NIA 19
47 FA P left in normal condition? YES Ll NO Ll N/A 0
For P react!on/Deluge systems that were operated during this inspection:
.13 1 Has valve been.operated via detections stem? YES Ll NO Ll NJA0
B 2 Has vavle been operated via manual release's YES Ll NOU 1A Id
B 3 Ha a open nozzles been flowed or internally Inspection In lest a ears? YES Q NO U N/A E
B 4 Please list make/model/quantity of devices used to trip solenoid
Results of trip test if performed during this inspection:
1 1 or Air PSI Water PSI Is Supply Air PSI at Time hater PSI Time for Time for Condition of Performance of
Valve before before Trip Valve Fully of Trip at I Valve to Water to Valve Interior Trip Test in
Location Trip Open? Time of Trip Trip reach 1TV and all Parts Compliance?
Dry Valve 48 110 4 Turns 14 110 47 PT Good Yes
D I Inspection Results: Passed U Passed With Deficiencies 6d Critical Deficiencies Bound U System Inoperable Q
PLEASE SEE ELECTRONIC WORK ACKNOWLEDGMENT, OR "ALERT TABS' OF
SERVICE E LINK(EMAILED TO CUSTOMERAT COMPLETION OF THE INSPECTION), FOR
DETAILS ON ANY CURRENT OFF PREVIOUSLY REPORTED RECOMMENDATIONS,
NS,
DEFICIENCIES, OR IMPAIRMENTS.**
E 1 GeneralComments:
Repair of feed side of air compressor replaced / " brass threaded check valve 1 3/4"X 02 nipple. 1 4" bail
valve. Total cost$350.00 per J.S.
F 1 list the changes In the occupancy hazard or fire protection equipment,as advised by the owner above:
1 Inspection and suggested improvements were discussed with the undersigned Owner or Owner's Representative: YESO NO U
**Customer signature nnay be found on electronic Work Acknowledgment in lieu of this report."
7/19/19 THIS IS NOT AN INVOICE
CUSTOMER'S I 1ATU E DATE CITY PART# DESCRIPTIONPENCE AMOUNT-
Annual Dry Spdnkler Inspeebon
CUSTOMER'S PRINTED NAME
- 1 1
TECHNICIAN SIGNATURE DATE
Joshua Whitney, Paul Rice 151038
TECHNICIAN PRINTED NAME LICENSE# 031 SPRINKLER SERVICE CALL
o o1 517