HomeMy WebLinkAboutAnnural Wet Sprinkler Inspection - Inspection - 351 HOLT ROAD 12/13/2018 6 TRI STAT E ANNUAL WET SPRINKLER INSPECTION
d FIRE"PROTECTION,LLC Commonwealth of mass Sprinkler Contractor SC-210,059 Inspected to the State Adopted,Version of NFP,A 25
Trl State Fire Protection,LL mpshire Drive Hudson NH 03051 T,:603-29-3-7531 F:603-5,89-2051 geffireprotection.com ln,fdrajgetflreprofection.coilI
JOB#: 15591842 DATE.- 12/13/2018 0,8-00arn EST, 12/14/201 CUSTOMER ID:
SHIP TOE BILL TO:
NAME LI FOAM INDUSTRIES- NORTH ANDOVER NAME N I
ADDRESS 351 HOLT RD ADDRESS po BOX 774
CITY NORTH ANDOVER STATE MA ZIP 018,45 CITY F'R E E P 0 RT STATE IL ZIP,61032
CONTACT LON BARTOLI PHONE (775) 316-0016 EMAIL LON.BARTOLI @N EWELLCO'.CON,
CUST PO# 0045,257015,
.........................
TYPE OF SERVICE IMGULAR Id EMERGENCY L)
START TIME 8:OOAM END,TIME 4:010PM
VALVE MAKE VARIOUS VALVE MODEL VARIOUS VALVE SIZE 48 #OF SYSTEMS 10
FIRE ALARM PANEL MAKE NOTIFIE,R MONITORING YES e NO U N/A U
A 0.0 I's FRCP in norm at start of inspection? YES 161 NO LI N/A LJ
A 0.1 Is the panel&,riser accessible YES Id NO U N/A LJ
A 0.2 Total#of flow-switches tested: 10
A 0.3 Flow&w1whesoperatlonal? YES Ll NO Id NIA Ll
A 0.4 Total.#of tarnper switches,tested: '7
A 0.5 Tamper swit c'lies operational? YES id NO Ll NIA.Ll
A 0.6 Total#of inspection test valves:, 9 'YES LJ NO El N/A LI
A 0.7 Alarm line valves in proper position? YES Id NO LJ N/A LJ
A 1.1 Hydraulic name plate attached and legible? Pipe,Schedule System U?
A 1.2 Systeingauges in good condition at on Gauge 200912010 YES Q NO Idl N/A L)
A 1.3 Are all valves in the appropriate open/closed position? YES Ef NO L3 N/A L]
A 1.4 Static 150 psi Residual 135 psi, Size 2 (See 2nd page for additional waterflow test results),
.1. Has the residual reading one below 1 GO/*of original flow test(demand on hydraulic placard) YES LJ NO 0 N/A Ll
A 2j) All,control valves accessible? YES El NO, Ll N/A LI
A 2.1 Alarm valve,and trim free from damage? YES LJ NO Id N/A Ll
A 10 F.D.C.maintained,per NFPA 25? YES 0, NO Ll N/A Ll
A,4.0 Exterior alamis operational, YES Id, NO LJ
A 4.1 Time,to alann-, W.M.G. OK Floe-SWitCh_20,40 Press-switch NOT'rESTED
A5.0 All systern signs,valve chart,anti-freuc placard(Wapplicable)in place? YES,
A 6.0 Alarm line valve sealed in open position? All valves in,normal conditioti? YES 16 NO Ll N/A Ur
A 6.1 FACP left in nortnal condition? YES R1 NO L] N/A L1
A 6.2 Did monitoring company receive signal? YES El NO Q N/A LI
A 6.3 Has the tank been assessed for obstructions in the last 5 years YES L) NO U N/A Ef
A 6.4 Has an obstn,iction assessment been,pet-fon-ned in the last 5 years? YES LJ NO 16 EXEMPT Ll
A 6.5 Has the alarm i val%,e been assessed for obstructions in the last 5 years? YES L] NO 16 N/A J
A 7.0 Heads appear free of leaks and damage? YES El NO LJ N/A LJ
A 7.1 Heads free of foreign material? YES 1d NO Ll N/A Ll
A T2 Minimum.18"'clearance,from deflector to obstruction YES 16 NO Ll N/A Q
A 7.3 All proper escutcheon plates in place? YES Ll NO VJ N/A L)
A 7.4 Standard heads less than 50 years old? law: 2001 YES Ef NO L) N/A L)
A 7.5 Residential heads less than,20 years old? Date: YES LJ NO U N/A El
A 7.6 Are any dry he ad s 10+years old,? Date: 2017 YES L) NO 0 N/A Ll
A T7 Are apy.licads located in harsh environments? Date: YES Ll NO U N/A ki
A 8. used piping,and,hang ersjn gand condi(ion? YES Ef NO L] N/A L)
A 9.0 Fire Pump nianufadurer: S ize:
A 10.0 Last capacity test Date: Operational? YES LJ NO U N/A
A 11.0 Is the standpipe valve operational and lubed? YES LI NO 'Ll N/A Id
I
A 11.1 Ai1tifirceze tested'? Percentage Freeze Point Type Quantity Date: YES L] NO 'LIN/A Ef
A,11.2 Have any heads been tested? YES LJ NO LI N/A R1
1.0 Water#low'Pest Results Made During This Inspection:
k Sipe P�releus Si Static Residual
Test Pipe Test Static Residual Flow Test Pipe Test Flow
Location pipe Pressure Pressure Pressure Location Pipe Pressure PressurePressure
Explanation of"NCB'}answers
PLEASE SEE ADDITIONAL COMMENTS PAGE FOR LIST OF DEFICIENCIES.
C1.0
D1.0 The inspe for suggests the foitowing n ec essary iniprovem nts. However,th e se suggestions are riot t1ie result ofan e n gin Bring sure y.
SPK- Recommend meind installing bleeder valve under low pressure switch on Risers# , 2, 3, 4, 5, 6, 7, 8 in order to
test device without draining system.
ELO Did the system Pass: Passed U Passed With Deficiencies U Criticat Deficiencies Found El System Inoperable U
LO General Comments:
1.0 fist the changes in the occupancy lia and or fire protection equipment,as advised by the owner above
H1.0 Inspection and suggested improvements *ere discussed Nvith the undersigned Owner orOwner's Representative: YES Y NO U
1 /1 -1 1 3 THIS IS NOT AN INVOICE
OUST fER'S SIGNATURE DATE TY PART DESCRIPTION PRICE AMOUNT
10 WET SPRINKLER ANNUAL AL INSP
1 BACKIFLOW ANNUAL INSPECTION
CUS` OiN'IE 'S PRINTED NAME 13 PIVANNUAL INSP
(PLEASE SEE UPLOADED FOR PIV INFO)
12113-14/18
_YWCHIRDICIAIN SIGNATURE DATE
Joe Sousa, are Tray SJ3993
TECHNICIANPRINTED A IE ACEN E#� � 1SPRINKLERSERVICE CALL
SWS012517
Gifford, Lancaster,Nashua,Hudson& TRI STATE, FIRE PROTECTION, LLC ADDITIONAL SERVICE
Newington,NH Remit too COMMENTS
Telephone:(6,03)293-7531
Fax:(1603)589-2051 26,Hampshire!Drive
Hudson,NH 51
Comm.of Mass.Sprinkler Contractor SC-2 10059
030
ITIONAL SERVICE, I IIIID, / NFPA 13 REFERENCES
WORK.ORDER#: 15,591842 DATA: 12/13/2018 08 goo am EST', 12/14/2018 CUSTOMER 1113:
BILL TOM NEWELL BRANDS SHIP TO: LIFOAM INDUSTRIES-,NORTH ANDOVER
PO BOX 7'74 351 HOLT RD
FREEPOR, T IL, 61032 NORTHANDOVER MA 01845
Phone". Cont'act-
(777)316-0016
Email- __Phonle
.................
peA2
SPK Zone 1, 2, 3, 8 sprinkler valve trim assembly has components that are corroded and must be replaced r III 5,
SPK Sprinkler systems for Zones 1, 2, 3,41 &5 are Pipe Schedule Systems and therefore should have placard's indicatin this on,each riser
as required per FP 25.
SPK-,The following systems are over 5 years old and have no visual records of a or obstruction assessment as required every 5,
years per NFPA 25-Zone 1 (1969),,Zone 2(1969),Zone 3(1969),Zone 8(1985),Zone 4(1974), Zone 5 .
q
,SPKZone,8&9 are missing hydraulic placards,as re wire per NFPA 25,on any system that was not d'es,igned per the Pipe Schedule
Method. Customer provided me with,a flash drive that should have the cabs for Zone 9.
SPKSpare head box for riser#8 and for risers 4, 5, &9 are empty. Per NFPA 25, there needs to be at least 6 spare,sprinklers and
associated wrench.Scissor lift will be needed to determine make,model, response,and temperature of sprinklers installed on these risers.
SPK Ply'that presurnably supplies Zones 1, 2, &3 has a broken wrench that FM Global demands be replaced.
SPK Main PIV that supplies backfiow prev enter,
enter s seized.Valve should be repaired or replaced as required per !FPA 25.
SPK-Waterflow pressure switch on Zone 3,riser did not report.to panel as required per NFPA 25. Recommend plugging off and replacing with
8"piaddleflow switch.
SPK There is no inspector's test station for Zone 5. In order to test"pressure switch in a manner that complies,with NFPA 25, recommend
extending pipe off low point valve under mezzanine stairs,outside.
SPK-The following sIgnage is,missing as required'.per NFPA 25.1- Bo flow 1(2-MAIN CONTROL),Zone 1 (MAIN DRAIN,Zone 2 (MAIN
DRAIN)J Zone 3 (MAIN DRAIN), Zone 4,(MAIN DRAIN),Zone!5(MAIN DRAIN),Zone 8(CONTROL VALVE, MAIN DRAIN),Wall Hydrant
Shotgun(CONTROL VALVE,TEST& DRAIN),Zone 9(CONTROL VALVE).
SPK-There are a total of 13 PIVs/VVPIVs that we had'to cu1 locks off of due to no one having the key.We also had,to cut the lock on the
backflow chain.Customer would like a quote for replacement locks.Approximately 20 of chain will also be needed for the WPIVs., Lt. on Pert
would prefer breakaway,locks to be installed.,
SPK-missing escutcheon plates in,the following areas-
11 room to the right of main entrance ,Globe chrome
4 in break room, Globe chrome
I downstairs office area to the right when entering warehouse,, Globe chrome
,2 restroom area to the right,when,entering warehouse, Globe chrome
1 by test valve P,white concealed V380,2
.2 in upstairs,office area to the left when entering warehouse, Star chrome recessed style