HomeMy WebLinkAboutAnnual NFPA 25 - Inspection - 351 HOLT ROAD 9/14/2020 Report of Inspection/Test e4 IMPACT FIRE
Annual NFPA 25
26 Hampshire DR,Hudson,NH
2020-09-14 Conducted :Chris Toro 261 Brooks ST,Worcester,MA
Property ( 08)852-7227
LIFOAM INDUSTRIES R NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,
MA
2517728 (978)304-150
Building#:7907771
1 HLT RD
NORTH AND OVER MA 018
LON BAIT LI 77 - -001
Inspection Ref#: 19480766
Report o ink io /Test General. Questions
OW N E R S ECTI
is the building occupied? Yes Has the occupancy classification,hazard of contents, Yes
and/or storage method remained the sane since the
last inspection?
Are all fire protection systems in service? Yes Has the system remained in service without Yes
modification since the last inspection?
Was the stern free of actuations of devices or alarms o
since the last inspection.?
FIRE DEPARTMENT-CONNECTION
Has the interior of the FDC been inspected for Yes 1s the visible piping supplying the FDC undamaged? Yes
obstructions??
If locking caps/plugs are in placer has an internal Yes Is the FD C plainly visible and easily accessible? Yes
inspections been conducted?
Is the FDC easily accessible? Yes Are the FDC swivels and couplings not damaged? Yes
Are the FDC caps and plugs in place and undamaged? Yes Are the FDC gaskets in place? Yes
Is the FDC check valve free of leaks? Yes is the clapper and automatic drain valve in place and Yes
properly operating?
Is the FDC identification sign(s)in place? Yes
FRI N KLE.R H EADS
Are there the proper number and type of spare Yes Are visible sprinklers in the proper position:upright, Yes
sprinklers with a list in lace? pendent,sidewall
p
Are visible sprinklers free of corrosion and physical Yes Is there proper clearance below the sprinklers? Yes
damage?
Are ,risible sprinklers free of foreign materials including No Is there liquid in all visible glass bulb sprinklers? Yes
foreign paint?
Are there spare sprinklers and a sprinkler wrench Yes Is the information sign attached and legible? N/A
Are all the sprinklers dated 1920 or later? Yes Fast response sprinklers o or more ears old replaced Yes
sample
or successfullyle tested within last 1 ears?
P
Standard response sprinklers 50 or more years old lies Standard response sprinklers 75 or more years old Yes
replaced or successfully sample tested within last 10 replaced or successfully sample tested within last
years? years?
Dry-type sprinklers replaced or successfully sample NIA Have sprinklers subject to harsh environments been loll
tested within last 10 years? replaced or successfully sample tested in the last
years?
Are the visible pipe and fittings in good condition with No Do visible pipe and fittings have no mechanical damage Yes
no eternal corrosion7 or leak ?
Copyright 2020 Inspect Point Page I of 1
Report of Inspection/Test
Annual NFPA 25
26 Hampshire DR,Hudson,NH
- -'14 Conducted y:Chris Toro I Brooks T,Worcester,MA
Property (50 )852-7227
LIFOAM INDUSTRIES IES-NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA
(978)304-1 06
2517728
Building#:7907771
51 DOLT RD
NORTH AND OVER IAA 01845
L N BARTOLI 775- 1 - o1
Inspection If#: 19480766
Does visible pipe have no external loads? Yes Are visible pipe hangers and seismic braces not Yes
damaged or loose?
Is the pipe through freezers free if any ice blockage: N/A Has an internal investigation of the pipe been Yes
performed in the last 5 years? if no,conduct
investigation)
CONTROL VALVE AR
Are the control valves with electrical supervision in Yes Are the control valves with electrical supervision locked Yes
correct(open or closed)position? or is supervision in place?
Are the control valves with electrical supervision Yes Are the control valves with electrical supervision free Yes
accessible? from any leaks?
Are the control valves with electrical supervision have Yes Are the control valves with electrical supervision Yes
the appropriate wrenches? properly Identified?
Are the control valves supervised with seals in correct N/A Are the control valves supervised with seals locked or is N/A
(open or closed)position? supervision in place?
Are the control valves supervised with seals accessible? N/A Are the control varies supervised with seals free from N/A
leaks?
Are the control valves supervised with seals have N/A Are the control valves supervised with seals properly N/A
appropriate wrenches? identified?
Are the control valves with locks in correct(open or Yes Are the control valves with locks locked or is supervision Yes
closed)position? in place?
Are the control valves with locks accessible? Yes Are the control valves with lochs free from any leaks; Yes
Are the control valves with locks have the appropriate Yes Are the control valves with locks properly identified? Yes
wrenches?
VALVE
AREA
Are the gauges on system showing normal water supply Yes Are the gauges on system operable and in good working Yes
pressured I condition?
is the hydraulic name plate(calculated systems) Yes Are Pressure reducing valves(sprinkler system)in open N/A
attached securely to the riser and legible: position and not leaking?
Are Pressure reducing valves sprinkler system)with N/A Are Pressure reducing valves in good condition including !A
downstream per pressure the design? no handwheels brim
P p g
Have the mechanical waterflow alarm devices passed Yes Do valve supervisory switches indicate,movement? Yes
tests by opening inspector's test connection/bypass
connection with alarms actuating and flog observed?
The electrical waterflow alarm devices passed test by Yes Have post'indicating valves been opened until spring or No
opening Inspector's test connection/bypass connection torsion felt in the rod and then closed back 1 turn?
with alarms actuating and flog observed?
All control valves operated through full range and Yes Have pressure reducing valves passed partial flow test? N/A
returned to normal position?
AC KF.L11.PREVENTERS
.
Is relief port on RPZ device not discharging? NIA Have backflow devices passed forward flow test? Yes
Copyright 2020 Inspect Point Page 2 of 1
r
}
}
F
Report of Inspection/Test
Annual NFPA 25 IMPACT FIRE
6 Hampshire DR,Hudson,NH
( o ) -7 531
0-0 -14 Conducted by:Chris Toro 261 Brooks ST,Worcester,MA
Property (508)852-722
LIFOA 1I INDUSTRIES-NORTH AND OVER impact Fire Services-Hudson 44 Garden ST,suite 1,Danvers,MA
251772 (978)304.150E
Building :7907771
1 HLT R
NORTH A #D VER MA 01845
LOB! KART LI 775-316-0016
Inspection Ref : 19480766
LAR
Is the alarm valve free from physical damage? Yes Is the trim/valves in correct(open or closed)position? Yes
Is there no leakage in the retarding chamber or drains? Yes Are alarms and supervisory devices not damaged.? Yes.
Do low temperature alarms look k? /A
MAINTENANCE.
If a sprinkler failed a sample test were all the sprinkler I if sprinklers have been replaced,were they proper N/A
represented by that sample replaced? replacements?
Were marine systems normally having fresh water /A was heat tape inspected per the manufacturer's i
drained and refilled twice if raw water got into the instructions?
system?
Have adjusted, repaired,reconditioned,or replaced /A Was a drain test conducted after opening any closed Yes
components had proper tests/inspections performed? valve?
Operating stern of all OS&Y valves lubricated,completely Yes Have sprinklers and spray nozzles protecting N/A
closed and reopened? commercial cooing equipment and ventilating systems
been placed annually
Copyright 2020 inspect Point Page 3 of 1
Report of Inspection/Test e�
Annual PA IMPACT ,
26 Hampshire Doi,Hudson,NH
2020-09-14 Conducted by: Chris Toro 261 Brooks 5T,Worcester,MA
Property (508)852-7227
LIF AM INDUSTRIES-NORTH ANDOVER Impact Fire Services-Hudson 44 Garden 5T,Suite 1,Danvers,MA
17728 (97 )304-1506
u 11 d i ng#;79777
1 HOLT PD
NORTH ANDOVER MA 01845
LN BARTOLI 775- 1 6- 1
Inspection Ref#: 19480766
Report of I nspectio.n/Test for System Zone 1
..... .....
FIRE DEPARTMENT CONNECT.1 l l
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 6/22/20
every 5 years?
A
Can antifreeze type be correctly identified? N/A Is the antifreeze listed? /A
Is expansion tank pressure reading equal to 0%of /A
supply?
Report of Inspection/Test for System Zone
FIRE DEPARTMENT E T CONNECTION .'.'
Has the FDC been hydrostatically tested as required lies Date of the last FDC hydrostatic test? 6/22/2
every 5 years?
ANTIFREEZE.:.::::.:...
Can antifreeze type be correctly identified? N/A Is the antifreeze listed? ILIA
Is expansion tank pressure reading equal to 9 9 f 1A
supply?
Reportof Inspection/Test for System Zone .3 .-
....
FIDE DEPARTMENT.CONNECTION
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 6f22/2
every 5 years?
ANTI
Can antifreeze type be correctly identified? ILIA is the antifreeze listed? VIA
Is expansion tank pressure reading equal to 90%of N/
supply?
Repo.rt.of.. s io T for System Zone 6. -
FI E.- EPA TME T CON N ECTI ON
Has the FDC been hydrostatically tested as required No Date of the last FDC hydrostatic test? 7/22/2
every 5}rears?
Can antifreeze type be correctly identified? N/A Is the antifreeze listed? ]/A
1s expansion tank pressure reading equal to %ofN/A
suppler?
41
Copyright 2020 Inspect Point Page 4 of 1
Report of Inspection/Test C
TFIRE
Annual NFPA 25
26 Hampshire DR,Hudson,NH
(603) 93-7531
2020-09-14 Conducted y: Chris Toro 261 Brooks ST,Worcester,MA
Property (508)852-7227
LIFOAM INDUSTRIES-NORTH AND OVER Impact Fire Services- Hudson QA Carden ST,Suite 1,Dangers,MA
51772 (9781 0 -1506
Building#;77771
51 DOLT PD
NORTH AND OVER MA 01845
L N BAI T LI 77 - 1 - o1
Inspection If #: 19480766
Report Inspection/Test for System - Zane 7
FIRE DEPT. ENT.C.0 N N.E.
Has the FDC been hydro tatical[r tested as required No Date of the last FDC hydrostatic test? /22/20
every 5 years?
ANTIFREEZE ...
Can antifreeze type be correctly identified? N/A Is the antifreeze listed? N/A
Is expansion tank pressure reading equal to 90 of /A
supply
Repo'.rt of Inspection/Test r System Zone .'.8
FIRE DEPAITMET. ETI .I .
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 1222
every 5 years
ANTIFREEZE
Can antifreeze type be correctly identified? N/A Is the antifreeze listed? NIA
Is expansion tank pressure reading equal to 6 of N/A
supply;
Report f Inspection/Test for System Zon.e.9
FILE.DEPARTMENT CONNECTION....
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? /22/20
eve ry 5 year �
AN T1 F RE EZE.. ......
Can antifreeze type be correctly identified? N/A Is the antifreeze listed? /A
Is expansion tank pressure reading equal to 90%of l
supply?
Re port .of I r s pecti .fay ste ms _ Zo n e
.4 . .'
FIRE DEPARTMENT
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? f2 / o
every 5 years?
ANTIFREEZE'
Can antifreeze type be correctly identified? NIA Is the antifreeze listed? N/
Is expansion tank pressure reading equal to 90 NIA
supply?
Copyright 2020 inspect Point Page 5 of 1
Report of I
Annual NFPA 25
b Hampshire DR,Hudson,NH
(603}293-75 1
0 0- -14 Conducted y:Chris Toro 261 BrooksST,Worcester,MA
Property ( 0 )85 -72 7
LIF A II INDUSTRIES IE -NORTH AND OVER Impact Fire Services Hudson 44 Garden 5T,SuRe 1,Danvers,MA
2517728 1978)304-1506
Building ;7907771
1 MOLT R
FORTH AlDVR MA 01845
LON BAITLI 5- 1 - 1
Inspection Ref##: 19480766
Report ofor System Zone 5
FIRE D E PART
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? /2 /2
every 5 years?
ANTI F R .....................
Can antifreeze type be correctly identified? N/A is the antifreeze listed? N/A
Is expansion tank pressure reading equal to 9 ofN/A
supply?
Report-of ln.specti.o.n/Test for System Wall hydrant
FIRE DEPARTMENT CONNECTION
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? /22/2
every 5 years?
ANTIFREEZE.-.'....
Can antifreeze type be correctly identified? /A is the antifreeze listed? N/A
Is expansion tank pressure reading equal to 90 of 1A
supply'
MAI ND RAI N .SLOW TESTS
System Initial static Residual static Seconds to Flow Are results
Return to Observed? comparable
Initial Static to previous test?
Zone 1 155 140 155 instant Yes Yes
Zone'? 15 140 15 instant Yes Yes
Zone 3 150 140 150 instant Yes Yes
Zone 5 145 140 145 instant Yes Yes
Zone 7 155 130 155 instant Yes Yes
Zone 8 160 130 160 instant Yes Yes
Zone 9 150 130 150 instant Yes Yes
Zone 4 160 130 160 instant Yes Yes
Zo e 5 165 130 165 instant Yes Yes
Wall hydrant 145 130 145 instant Yes Yes
Copyright 2020 Inspect Point Page 6 of 12
r
i
Report of Inspection/Test
Annual NFPA 25
26 Hampshire DR,Hudson,NH
(60 )293-7531
} -09-14 Conducted by:Chris Too 261 Brooks ST,Worcester,MA
Property (508)852-7227
LI F AM INDUSTRIES-NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA
51 (978)304-150
Building#:7907771
351 H LT RD
NORTH AND OVER IAA 01845
LON BAT LI77 -31 - o1
Inspection Ref#: 19480766
INSPECTORS TEST..CONNECTI N.
System Location Description Time Reported? Smooth Easily Signs? Pass?
to Orifice Accessible
Alarm
(seconds)
Zone 1 By shipping door 9 Ball valve 60 Yes Yes Yes Yes Yes
Zone 2 Outside wall of Bail valve 60 Yes Yes Yes Yes Yes
bldg.location i
arced
Zone 7 Near receiving Ball valve 45 Yes Yes Yes Yes Yes
door office
Zone 9 At Zone 9 riser Test and drain 30 Yes Yes Yes Yes Yes
Zone 6 Zone 6 area front Ball valve 45 Yes 'des Yes Yes Yes
wall
Zone 5 Under the stairs Ball valve 55 Yes Yes Yes Yes Yes
on far end of Bldg
Zone 8 Zone 8 back wall Globe 20 Yes Yes Yes Yes Yes
Zone 3 Front of building Ball valve 35 Yes Yes lies Yes Yes
under stairwell
near break room
Zone 4 Near front of Ball valve 55 Yes Yes Yes Yes Yes
building under
stairwell rear
break room
Wall hydrant Riser Test and drain 20 Yes Yes Yes Yes Yes
Tam
Valve ope Easll Stems Flow per
System Descriptlon Location Type Size Secured n Acces1le Signs Exercised Lubricated Pass Pass
Zone 5 Control Zone 5 riser Wall Post 6" Locked Yes Yes Yes Yes Yes Pass Pass
valve
Zone 6 Control Riser Butterfly Monitored Yes Yes Yes Yes Yes Pass Pass
valve
Zone 7 Control Zone 7 riser Butterfly 8" Monitored Yes Yes Yes Yes lies Pass Pass
valve
Zone 8 Control miser Butter€ly 4" Monitored Yes Yes Yes Yes Yes Pass Pass
valve
Zone 4 Control Riser 4 Wall Post 6" Locked Yes lies Yes Yes lies Pass Pass
valve
Zone 1 Closet Inside Zone 1 riser Null Post Padlock Yes Yes Yes Yes Yes Pass Pass
Zone 8 In back outside wall Post Indicator Locked Yes Yes Yes Yes Yes Pass Pass
Zone 7 blear riser Outside Post indicator 6'" Locked Yes Yes lies Yes Yes Pass Pass
Zone Z Closet inside Zone 2 riser Wall Past 8" Padlock Yes Yes Yes Yes Yes Pass Pass
Copyright aspect Point Page of 12
Report f Inspection/Test
Annual NFPA 25
26 Hampshire DR,Hudson,HUH
2020-09-14 Conducted by:Chris Toro 261 Brooks ST,Worcester,MA
Property (5G ) 5 -7 2
LIFOAM INDUSTRIES-NORTH ANDOV R Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA
177 (978)304-1506
Building##:7907771
51 HOLT R
NORTH AOVR VIA 0 1845
LON BARTOL.I 775- 15-001
Inspection Ref##: 19480766
Tarim
Valve Ope FaMsily Sterns Flow per
system Description Location Type Size Secured n Accessible SIgns Exercised Lubricated Pass Pass
Zone 3 Closet inside Zone 3 riser Wall Post Padlock Yes Yes Yes Yes lies Pass Pass
Zone 1 Main Piv In front of Post Indicator Locked Yes Yes Yes Yes Yes Pass Pass
building
Zone 6 Outside wall In front Post Indicator 16'" Locked Yes Yes Yes lies Yes Pass Pass
Unclear In front Post In d I cato r 6" Locked Yes Yes Yes Yes Yes Pass Pass
what riser
In front dear front Post Indicator 6n Locked Yes Yes Yes Yes Yes Pass Pass
doer
In front Near entrance 6 kk Locked Yes Yes Yes Yes Yes Pass Pass
Outside In front Fast Indicator 6" Locked Yes Yes Yes Yes Yes Pass Pass
riser 4,5,9
Normal Rack of Post Indicator a Locked Yes Yes Yes Yes Yes Pass Pass
closed building
DRAIN VALVES
System Description Location Drain Aux Drain Drained later Flog Observed
Zone 6 Z"main drain Riser 6 Globe Valve Yes Yes
Zone 1 2t Main drain Riser 1 Aube Valve Yes Yes
Zone 2 2"Main drain Riser 2 Globe Valve Yes Yes
Zone 3 2q main drain Riser 3 Globe Valve Yes Yes
Zone 9 "main drain Riser& Globe halve Yes Yes
Zone 9 Z"main drain Riser 9 Globe Valve Yes Yes
Zone 4 2w Main drain Riser 4 Globe Valve Yes Yes
Zone 7 "main drain Riser T Globe Valve Yes Yes
Zone 5 Main drain Riser 5 Globe Valve Yes Yes
Wall hydrant Test f drain Near riser 8 Test And Drain lies Yes
Copyright 2020 inspect Point Page 8 of 12
,. Report of Inspection/T
26 Hampshire Dot,Hudson,Nei
( 03)2 -7531
, 9-14 Conducted by,Chris Toro 261 Brooks ST,Worcester,MA
Property (508)55 -7 27
LIFOAM INDUSTRIES TRIE -NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,suite 2,Danvers,MA
1772 ( 78)304-1506
Building#:7907771
1 HOLTRD
NORTH A DOVER MA 01845
LOB! BA TOLI 77 - 1 -O01
Inspection Ref#: 19480766
Questions with Photos.and Notes
Zone 7-Date of the last FDC hydrostatic test? 7222
Notes:
Failed FDC test
Zone 6-Date of the last FDC hydrostatic test? 7/22/20
Dotes:
Failed FDC test
Copyright 2020 Inspect Point Page 9 of 12