Loading...
HomeMy WebLinkAboutAnnual NFPA 25 - Inspection - 351 HOLT ROAD 9/14/2020 Report of Inspection/Test e4 IMPACT FIRE Annual NFPA 25 26 Hampshire DR,Hudson,NH 2020-09-14 Conducted :Chris Toro 261 Brooks ST,Worcester,MA Property ( 08)852-7227 LIFOAM INDUSTRIES R NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers, MA 2517728 (978)304-150 Building#:7907771 1 HLT RD NORTH AND OVER MA 018 LON BAIT LI 77 - -001 Inspection Ref#: 19480766 Report o ink io /Test General. Questions OW N E R S ECTI is the building occupied? Yes Has the occupancy classification,hazard of contents, Yes and/or storage method remained the sane since the last inspection? Are all fire protection systems in service? Yes Has the system remained in service without Yes modification since the last inspection? Was the stern free of actuations of devices or alarms o since the last inspection.? FIRE DEPARTMENT-CONNECTION Has the interior of the FDC been inspected for Yes 1s the visible piping supplying the FDC undamaged? Yes obstructions?? If locking caps/plugs are in placer has an internal Yes Is the FD C plainly visible and easily accessible? Yes inspections been conducted? Is the FDC easily accessible? Yes Are the FDC swivels and couplings not damaged? Yes Are the FDC caps and plugs in place and undamaged? Yes Are the FDC gaskets in place? Yes Is the FDC check valve free of leaks? Yes is the clapper and automatic drain valve in place and Yes properly operating? Is the FDC identification sign(s)in place? Yes FRI N KLE.R H EADS Are there the proper number and type of spare Yes Are visible sprinklers in the proper position:upright, Yes sprinklers with a list in lace? pendent,sidewall p Are visible sprinklers free of corrosion and physical Yes Is there proper clearance below the sprinklers? Yes damage? Are ,risible sprinklers free of foreign materials including No Is there liquid in all visible glass bulb sprinklers? Yes foreign paint? Are there spare sprinklers and a sprinkler wrench Yes Is the information sign attached and legible? N/A Are all the sprinklers dated 1920 or later? Yes Fast response sprinklers o or more ears old replaced Yes sample or successfullyle tested within last 1 ears? P Standard response sprinklers 50 or more years old lies Standard response sprinklers 75 or more years old Yes replaced or successfully sample tested within last 10 replaced or successfully sample tested within last years? years? Dry-type sprinklers replaced or successfully sample NIA Have sprinklers subject to harsh environments been loll tested within last 10 years? replaced or successfully sample tested in the last years? Are the visible pipe and fittings in good condition with No Do visible pipe and fittings have no mechanical damage Yes no eternal corrosion7 or leak ? Copyright 2020 Inspect Point Page I of 1 Report of Inspection/Test Annual NFPA 25 26 Hampshire DR,Hudson,NH - -'14 Conducted y:Chris Toro I Brooks T,Worcester,MA Property (50 )852-7227 LIFOAM INDUSTRIES IES-NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA (978)304-1 06 2517728 Building#:7907771 51 DOLT RD NORTH AND OVER IAA 01845 L N BARTOLI 775- 1 - o1 Inspection If#: 19480766 Does visible pipe have no external loads? Yes Are visible pipe hangers and seismic braces not Yes damaged or loose? Is the pipe through freezers free if any ice blockage: N/A Has an internal investigation of the pipe been Yes performed in the last 5 years? if no,conduct investigation) CONTROL VALVE AR Are the control valves with electrical supervision in Yes Are the control valves with electrical supervision locked Yes correct(open or closed)position? or is supervision in place? Are the control valves with electrical supervision Yes Are the control valves with electrical supervision free Yes accessible? from any leaks? Are the control valves with electrical supervision have Yes Are the control valves with electrical supervision Yes the appropriate wrenches? properly Identified? Are the control valves supervised with seals in correct N/A Are the control valves supervised with seals locked or is N/A (open or closed)position? supervision in place? Are the control valves supervised with seals accessible? N/A Are the control varies supervised with seals free from N/A leaks? Are the control valves supervised with seals have N/A Are the control valves supervised with seals properly N/A appropriate wrenches? identified? Are the control valves with locks in correct(open or Yes Are the control valves with locks locked or is supervision Yes closed)position? in place? Are the control valves with locks accessible? Yes Are the control valves with lochs free from any leaks; Yes Are the control valves with locks have the appropriate Yes Are the control valves with locks properly identified? Yes wrenches? VALVE AREA Are the gauges on system showing normal water supply Yes Are the gauges on system operable and in good working Yes pressured I condition? is the hydraulic name plate(calculated systems) Yes Are Pressure reducing valves(sprinkler system)in open N/A attached securely to the riser and legible: position and not leaking? Are Pressure reducing valves sprinkler system)with N/A Are Pressure reducing valves in good condition including !A downstream per pressure the design? no handwheels brim P p g Have the mechanical waterflow alarm devices passed Yes Do valve supervisory switches indicate,movement? Yes tests by opening inspector's test connection/bypass connection with alarms actuating and flog observed? The electrical waterflow alarm devices passed test by Yes Have post'indicating valves been opened until spring or No opening Inspector's test connection/bypass connection torsion felt in the rod and then closed back 1 turn? with alarms actuating and flog observed? All control valves operated through full range and Yes Have pressure reducing valves passed partial flow test? N/A returned to normal position? AC KF.L11.PREVENTERS . Is relief port on RPZ device not discharging? NIA Have backflow devices passed forward flow test? Yes Copyright 2020 Inspect Point Page 2 of 1 r } } F Report of Inspection/Test Annual NFPA 25 IMPACT FIRE 6 Hampshire DR,Hudson,NH ( o ) -7 531 0-0 -14 Conducted by:Chris Toro 261 Brooks ST,Worcester,MA Property (508)852-722 LIFOA 1I INDUSTRIES-NORTH AND OVER impact Fire Services-Hudson 44 Garden ST,suite 1,Danvers,MA 251772 (978)304.150E Building :7907771 1 HLT R NORTH A #D VER MA 01845 LOB! KART LI 775-316-0016 Inspection Ref : 19480766 LAR Is the alarm valve free from physical damage? Yes Is the trim/valves in correct(open or closed)position? Yes Is there no leakage in the retarding chamber or drains? Yes Are alarms and supervisory devices not damaged.? Yes. Do low temperature alarms look k? /A MAINTENANCE. If a sprinkler failed a sample test were all the sprinkler I if sprinklers have been replaced,were they proper N/A represented by that sample replaced? replacements? Were marine systems normally having fresh water /A was heat tape inspected per the manufacturer's i drained and refilled twice if raw water got into the instructions? system? Have adjusted, repaired,reconditioned,or replaced /A Was a drain test conducted after opening any closed Yes components had proper tests/inspections performed? valve? Operating stern of all OS&Y valves lubricated,completely Yes Have sprinklers and spray nozzles protecting N/A closed and reopened? commercial cooing equipment and ventilating systems been placed annually Copyright 2020 inspect Point Page 3 of 1 Report of Inspection/Test e� Annual PA IMPACT , 26 Hampshire Doi,Hudson,NH 2020-09-14 Conducted by: Chris Toro 261 Brooks 5T,Worcester,MA Property (508)852-7227 LIF AM INDUSTRIES-NORTH ANDOVER Impact Fire Services-Hudson 44 Garden 5T,Suite 1,Danvers,MA 17728 (97 )304-1506 u 11 d i ng#;79777 1 HOLT PD NORTH ANDOVER MA 01845 LN BARTOLI 775- 1 6- 1 Inspection Ref#: 19480766 Report of I nspectio.n/Test for System Zone 1 ..... ..... FIRE DEPARTMENT CONNECT.1 l l Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 6/22/20 every 5 years? A Can antifreeze type be correctly identified? N/A Is the antifreeze listed? /A Is expansion tank pressure reading equal to 0%of /A supply? Report of Inspection/Test for System Zone FIRE DEPARTMENT E T CONNECTION .'.' Has the FDC been hydrostatically tested as required lies Date of the last FDC hydrostatic test? 6/22/2 every 5 years? ANTIFREEZE.:.::::.:... Can antifreeze type be correctly identified? N/A Is the antifreeze listed? ILIA Is expansion tank pressure reading equal to 9 9 f 1A supply? Reportof Inspection/Test for System Zone .3 .- .... FIDE DEPARTMENT.CONNECTION Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 6f22/2 every 5 years? ANTI Can antifreeze type be correctly identified? ILIA is the antifreeze listed? VIA Is expansion tank pressure reading equal to 90%of N/ supply? Repo.rt.of.. s io T for System Zone 6. - FI E.- EPA TME T CON N ECTI ON Has the FDC been hydrostatically tested as required No Date of the last FDC hydrostatic test? 7/22/2 every 5}rears? Can antifreeze type be correctly identified? N/A Is the antifreeze listed? ]/A 1s expansion tank pressure reading equal to %ofN/A suppler? 41 Copyright 2020 Inspect Point Page 4 of 1 Report of Inspection/Test C TFIRE Annual NFPA 25 26 Hampshire DR,Hudson,NH (603) 93-7531 2020-09-14 Conducted y: Chris Toro 261 Brooks ST,Worcester,MA Property (508)852-7227 LIFOAM INDUSTRIES-NORTH AND OVER Impact Fire Services- Hudson QA Carden ST,Suite 1,Dangers,MA 51772 (9781 0 -1506 Building#;77771 51 DOLT PD NORTH AND OVER MA 01845 L N BAI T LI 77 - 1 - o1 Inspection If #: 19480766 Report Inspection/Test for System - Zane 7 FIRE DEPT. ENT.C.0 N N.E. Has the FDC been hydro tatical[r tested as required No Date of the last FDC hydrostatic test? /22/20 every 5 years? ANTIFREEZE ... Can antifreeze type be correctly identified? N/A Is the antifreeze listed? N/A Is expansion tank pressure reading equal to 90 of /A supply Repo'.rt of Inspection/Test r System Zone .'.8 FIRE DEPAITMET. ETI .I . Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 1222 every 5 years ANTIFREEZE Can antifreeze type be correctly identified? N/A Is the antifreeze listed? NIA Is expansion tank pressure reading equal to 6 of N/A supply; Report f Inspection/Test for System Zon.e.9 FILE.DEPARTMENT CONNECTION.... Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? /22/20 eve ry 5 year � AN T1 F RE EZE.. ...... Can antifreeze type be correctly identified? N/A Is the antifreeze listed? /A Is expansion tank pressure reading equal to 90%of l supply? Re port .of I r s pecti .fay ste ms _ Zo n e .4 . .' FIRE DEPARTMENT Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? f2 / o every 5 years? ANTIFREEZE' Can antifreeze type be correctly identified? NIA Is the antifreeze listed? N/ Is expansion tank pressure reading equal to 90 NIA supply? Copyright 2020 inspect Point Page 5 of 1 Report of I Annual NFPA 25 b Hampshire DR,Hudson,NH (603}293-75 1 0 0- -14 Conducted y:Chris Toro 261 BrooksST,Worcester,MA Property ( 0 )85 -72 7 LIF A II INDUSTRIES IE -NORTH AND OVER Impact Fire Services Hudson 44 Garden 5T,SuRe 1,Danvers,MA 2517728 1978)304-1506 Building ;7907771 1 MOLT R FORTH AlDVR MA 01845 LON BAITLI 5- 1 - 1 Inspection Ref##: 19480766 Report ofor System Zone 5 FIRE D E PART Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? /2 /2 every 5 years? ANTI F R ..................... Can antifreeze type be correctly identified? N/A is the antifreeze listed? N/A Is expansion tank pressure reading equal to 9 ofN/A supply? Report-of ln.specti.o.n/Test for System Wall hydrant FIRE DEPARTMENT CONNECTION Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? /22/2 every 5 years? ANTIFREEZE.-.'.... Can antifreeze type be correctly identified? /A is the antifreeze listed? N/A Is expansion tank pressure reading equal to 90 of 1A supply' MAI ND RAI N .SLOW TESTS System Initial static Residual static Seconds to Flow Are results Return to Observed? comparable Initial Static to previous test? Zone 1 155 140 155 instant Yes Yes Zone'? 15 140 15 instant Yes Yes Zone 3 150 140 150 instant Yes Yes Zone 5 145 140 145 instant Yes Yes Zone 7 155 130 155 instant Yes Yes Zone 8 160 130 160 instant Yes Yes Zone 9 150 130 150 instant Yes Yes Zone 4 160 130 160 instant Yes Yes Zo e 5 165 130 165 instant Yes Yes Wall hydrant 145 130 145 instant Yes Yes Copyright 2020 Inspect Point Page 6 of 12 r i Report of Inspection/Test Annual NFPA 25 26 Hampshire DR,Hudson,NH (60 )293-7531 } -09-14 Conducted by:Chris Too 261 Brooks ST,Worcester,MA Property (508)852-7227 LI F AM INDUSTRIES-NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA 51 (978)304-150 Building#:7907771 351 H LT RD NORTH AND OVER IAA 01845 LON BAT LI77 -31 - o1 Inspection Ref#: 19480766 INSPECTORS TEST..CONNECTI N. System Location Description Time Reported? Smooth Easily Signs? Pass? to Orifice Accessible Alarm (seconds) Zone 1 By shipping door 9 Ball valve 60 Yes Yes Yes Yes Yes Zone 2 Outside wall of Bail valve 60 Yes Yes Yes Yes Yes bldg.location i arced Zone 7 Near receiving Ball valve 45 Yes Yes Yes Yes Yes door office Zone 9 At Zone 9 riser Test and drain 30 Yes Yes Yes Yes Yes Zone 6 Zone 6 area front Ball valve 45 Yes 'des Yes Yes Yes wall Zone 5 Under the stairs Ball valve 55 Yes Yes Yes Yes Yes on far end of Bldg Zone 8 Zone 8 back wall Globe 20 Yes Yes Yes Yes Yes Zone 3 Front of building Ball valve 35 Yes Yes lies Yes Yes under stairwell near break room Zone 4 Near front of Ball valve 55 Yes Yes Yes Yes Yes building under stairwell rear break room Wall hydrant Riser Test and drain 20 Yes Yes Yes Yes Yes Tam Valve ope Easll Stems Flow per System Descriptlon Location Type Size Secured n Acces1le Signs Exercised Lubricated Pass Pass Zone 5 Control Zone 5 riser Wall Post 6" Locked Yes Yes Yes Yes Yes Pass Pass valve Zone 6 Control Riser Butterfly Monitored Yes Yes Yes Yes Yes Pass Pass valve Zone 7 Control Zone 7 riser Butterfly 8" Monitored Yes Yes Yes Yes lies Pass Pass valve Zone 8 Control miser Butter€ly 4" Monitored Yes Yes Yes Yes Yes Pass Pass valve Zone 4 Control Riser 4 Wall Post 6" Locked Yes lies Yes Yes lies Pass Pass valve Zone 1 Closet Inside Zone 1 riser Null Post Padlock Yes Yes Yes Yes Yes Pass Pass Zone 8 In back outside wall Post Indicator Locked Yes Yes Yes Yes Yes Pass Pass Zone 7 blear riser Outside Post indicator 6'" Locked Yes Yes lies Yes Yes Pass Pass Zone Z Closet inside Zone 2 riser Wall Past 8" Padlock Yes Yes Yes Yes Yes Pass Pass Copyright aspect Point Page of 12 Report f Inspection/Test Annual NFPA 25 26 Hampshire DR,Hudson,HUH 2020-09-14 Conducted by:Chris Toro 261 Brooks ST,Worcester,MA Property (5G ) 5 -7 2 LIFOAM INDUSTRIES-NORTH ANDOV R Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA 177 (978)304-1506 Building##:7907771 51 HOLT R NORTH AOVR VIA 0 1845 LON BARTOL.I 775- 15-001 Inspection Ref##: 19480766 Tarim Valve Ope FaMsily Sterns Flow per system Description Location Type Size Secured n Accessible SIgns Exercised Lubricated Pass Pass Zone 3 Closet inside Zone 3 riser Wall Post Padlock Yes Yes Yes Yes lies Pass Pass Zone 1 Main Piv In front of Post Indicator Locked Yes Yes Yes Yes Yes Pass Pass building Zone 6 Outside wall In front Post Indicator 16'" Locked Yes Yes Yes lies Yes Pass Pass Unclear In front Post In d I cato r 6" Locked Yes Yes Yes Yes Yes Pass Pass what riser In front dear front Post Indicator 6n Locked Yes Yes Yes Yes Yes Pass Pass doer In front Near entrance 6 kk Locked Yes Yes Yes Yes Yes Pass Pass Outside In front Fast Indicator 6" Locked Yes Yes Yes Yes Yes Pass Pass riser 4,5,9 Normal Rack of Post Indicator a Locked Yes Yes Yes Yes Yes Pass Pass closed building DRAIN VALVES System Description Location Drain Aux Drain Drained later Flog Observed Zone 6 Z"main drain Riser 6 Globe Valve Yes Yes Zone 1 2t Main drain Riser 1 Aube Valve Yes Yes Zone 2 2"Main drain Riser 2 Globe Valve Yes Yes Zone 3 2q main drain Riser 3 Globe Valve Yes Yes Zone 9 "main drain Riser& Globe halve Yes Yes Zone 9 Z"main drain Riser 9 Globe Valve Yes Yes Zone 4 2w Main drain Riser 4 Globe Valve Yes Yes Zone 7 "main drain Riser T Globe Valve Yes Yes Zone 5 Main drain Riser 5 Globe Valve Yes Yes Wall hydrant Test f drain Near riser 8 Test And Drain lies Yes Copyright 2020 inspect Point Page 8 of 12 ,. Report of Inspection/T 26 Hampshire Dot,Hudson,Nei ( 03)2 -7531 , 9-14 Conducted by,Chris Toro 261 Brooks ST,Worcester,MA Property (508)55 -7 27 LIFOAM INDUSTRIES TRIE -NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,suite 2,Danvers,MA 1772 ( 78)304-1506 Building#:7907771 1 HOLTRD NORTH A DOVER MA 01845 LOB! BA TOLI 77 - 1 -O01 Inspection Ref#: 19480766 Questions with Photos.and Notes Zone 7-Date of the last FDC hydrostatic test? 7222 Notes: Failed FDC test Zone 6-Date of the last FDC hydrostatic test? 7/22/20 Dotes: Failed FDC test Copyright 2020 Inspect Point Page 9 of 12