HomeMy WebLinkAboutReport of Inspection/Test - Inspection - 166 SUTTON STREET 10/14/2020 Report of Inspection/Test
Annual N FPA 96 17 17A,,Annual Exit Signs
6 Hampshire DR,Hudson,NH
(603) 93-75 1
2020-10-14 Con d u ted by:Justin Farrington 261 Brooks ST,Worcester,MA
Property MA CC-0057 5 (50 )852-7 27
ra's Kitchen Mesta ur nt- Ando er Salem NH 1802 44 Garden ST,Suite 1,Danvers,MA
3173408 MA -0000 9 ( 75)304-1506
Building 4: 11508393
166 Sutton Street Impact Fire Services-Hudson
North Andover MA 01845
Tony Fadel(978) 55- 5 7
Inspection Ref : 19651651
Rep - -
orb o fInspection/Test for..Asset : 02 R102
. . .
Kitchen I ormation
... .. . . ... ..
f
Manufacturer R1 02 Model 110
Location of Pull Station right of rear Fine[Shutoff 0
exit door
Number of Links 3@450 Number ber of 360 F Links 3
Number of 450 F Links 0 Fuse Link 450 F
Feel Shut Off Electric True Fuel Shut Off Gas True
T 10 N S.
All appliances properly covered w/correct nozzle? Yes Duct and plenum covered w/correct nozzles? Yes
Check positioning of all nozzles. Yes System installed in accordance w/MFG UL listing? Yes
Flood/duct penetrations sealed w/►,geld or UL device? Yes Check if sears intact,evidence of tampering Yes
Pressure gauge in proper range If gauged)? /A Check cartridge weight if applicable) Yes
Inspect cylinder and mount Yes Operate system from terminal link Yes
Test for proper operation from remote Yes Check operation of gas valve Yes
Are the proper nozzle covers in place Yes Replaced fuse links with new calendar year links? Yes
Check travel of cable nuts/S-hooks Yes Piping&conduit securely bracketed? Yes
Exhaust fain in operating order? Yes Fuel shut-off in on position? Yes
Manual&remote settseals in place Yes Replace systems corers Yes
System operational&seals in place? lies Slave system operational? N/A
Personnel Instructed in manual operation of system? Yes Service&Certification tag on system? Yes
Is this system I.Q.L.300 compliant? Yes Does the makeup air shut down? Yes
System interlocked,with building fire alarm? Yes Proper separation between fryers and flame? Yes
Fan warning sign on Mood? Yes K class fire extinguisher in cooking area? yes
Suppression system is compliant? PASS
Exit Sign.)ns e ion list.7. 1 RE:EXIT.:S1 G N.6 RO.U.P.,::
Locat . CIF. at T Pr ... -.Notes
' ..:. ::..:...:. p...:
Copyright 2020 Inspect Point Page 1 of