HomeMy WebLinkAboutReport of Inspection/Test - Inspection - 351 HOLT ROAD 2/26/2021 Report of Inspection/Test . __
Quarterly NFPA 25 1.TO,.1 A.C`i' Ff R f.,
26 Hampshire DR,Hudson,NH
(603)293-7531
2021-02-26 Conducted by:Spencer Morse 262 Brooks ST,Worcester,MA
Property (508)852-7227
LIFOAM INDUSTRIES-NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA
2517728 (978)304-1506
Building#:7907771
351 HOLT RD
NORTH ANDOVER MA 01845
LON BARTOL1775-316-0016
Inspection Ref#:20857050
Report of Inspection/Test General Questions
OWNER SECTION
Is the building occupied? Yes Has the occupancy classification,hazard of contents, Yes
and/or storage method remained the same since the
last inspection?
Are all fire protection systems in service? Yes Has the system remained in service without Yes
modification since the last inspection?
Was the system free of actuations of devices or alarms Yes
since the last inspection?
FIRE DEPARTMENT CONNECTION
Has the interior of the FDC been inspected for Yes Is the visible piping supplying the FDC undamaged? Yes
obstructions?
Is the FDC plainlyvisible and easily accessible? Yes Is the FDC easily accessible? Yes
Are the FDC swivels and couplings not damaged? Yes Are the FDC caps and plugs in place and undamaged? Yes
Are the FDC gaskets in place? Yes Is the FDC check valve free of leaks? Yes
Is the clapper and automatic drain valve in place and Yes Is the FDC identification sign(s)in place? Yes
properly operating?
CONTROL VALVE AREA
Are the control valves with electrical supervision in Yes Are the control valves with electrical supervision locked Yes
correct(open or closed)position? or is supervision in place?
Are the control valves with electrical supervision Yes Are the control valves with electrical supervision free Ycs
accessible? from any leaks?
Are the control valves with electrical supervision have Yes Are the control valves with electrical supervision Yes
the appropriate wrenches? properly identified?
Are the control valves supervised with seals in correct NIA Are the control valves supervised with seals locked or is NIA
(open or closed)position? supervision in place?
Are the control valves supervised with seals accessible? NIA Are the control valves supervised with seals free from NIA
leaks?
Are the control valves Supervised with seals have NIA Are the control valves supervised with seals properly NIA
appropriate wrenches? identified?
Are the control valves with locks in correct(open or Yes Are the control valves with locks locked or is supervision Yes
closed)position? in place?
Are the control valves with locks accessible? Yes Are the control valves with locks free from any leaks? Yes
Are the control valves with locks have the appropriate Yes Are the control valves with locks properly identified? Yes
wrenches?
VALVE AREA
Are the gauges on system showing normal water supply Yes Are the gauges on system operable and in good working Yes
pressure? condition?
Copyright 201 inspect Point Page o
Report of Inspection/Test J"1,J.,VA["1' I'f.RF`
quarterly NFPA25
26 Hampshire DR,Hudson,NH
(603)293-7531
2021-02-26 Conducted by:Spencer Morse 261 Brooks ST,Worcester,MA
Property (50B)852-7227
LIFOAM INDUSTRIES-NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA
2517728 (978)304-1506
Building#:7907771
351 HOLT RD
NORTH ANDOVER MA 01845
LON BARTOLI 775-316-0016
Inspection Ref##:20857050
Are Pressure reducing valves(sprinkler system)in open NIA Are Pressure reducing valves(sprinkler system)with NIA
position and not leaking? downstream pressure per the design?
Are Pressure reducing valves in good condition including NIA Have the mechanical waterflow alarm devices passed Yes
no handwheels broken? tests by opening inspector's test connection/bypass
connection with alarms actuating and flow observed?
BACKFLOW PREVENTERS
Is relief port on RPZ device not discharging? N/A
ALARMS
Is the alarm valve free from physical damage? Yes Is the trim/valves in correct(open or closed)position? Yes
Is there no leakage in the retarding chamber or drains? Yes Are alarms and supervisory devices not damaged? Yes
Do low temperature alarms look ok? N/A
MAINTENANCE
Have adjusted,repaired,reconditioned,or replaced N/A Was a drain test conducted after opening any closed Yes
components had proper tests/inspections performed? valve?
Copyright 2021 Inspect Point Page 2 of 10
Report of Inspection/Test
Quarterly NFPA 25 )T`i1.;1 A'C"J'
26 Hampshire DR,Hudson,NH
(6031 293-7531
2021-02-26 Conducted by:Spencer Morse 261 Brooks ST,Worcester,MA
Property (508)852-7227
LIFOAM INDUSTRIES-NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA
2517728 (978)304-15C6
Building#:7907771
351 HOLT RD
NORTH ANDOVER MA 01845
LON BARTOLI 775-316-0016
Inspection Ref#:20857050
Report of Inspection/Test for System - Zone 1
FIRE DEPARTMENT CONNECTION.
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 2020
every 5 years?
Report of Inspection/Test for. System . Zone 2
FIRE DEPARTMENT CONNECTION
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 2020
every 5 years?
Report of Inspection/Test for System - Zone 3
FIRE DEPARTMENT CONNECTION
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 2020
every 5 years?
Report of inspection/Test for System - Zone 6
FIRE DEPARTMENT CONNECTION.
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 2020
every 5 years?
Report of Inspection/Test for System -Zone 7
FIRE DEPARTMENT CONNECTION
Has the FDC been hydrostatically tested as required Yes Fof the last FDC hydrostatic test? 2020
every 5 years?
Report of Inspection/Test for System.. Zone 8
FIRE DEPARTMENT CONNECTION
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 2020
every 5 years?
Report of Inspection/Test for System - Zone 9
FIRE DEPARTMENT CONNECTION
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 2020
every 5 years?
Report of Inspection/Test for System Zone 4
FIRE DEPARTMENT CONNECTION
Copyright 2021 Inspect Point Page 3 of 10
Report of Inspection/Test
Quarterly NFPA 25 �. 1'd'�_(s`.f' 1.`_( i.I;
26 HampSEllre DR,Hudson,NH
(603I293-7531
2021-02-26 Conducted by:Spencer Morse 261 Brooks ST,Worcester,MA
Property (508)B52-7227
LIFOAMINDUSTRIES-NORTHANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA
2517728 (978)304-1506
Building#:7907771
351 HOLT RD
NORTH ANDOVER MA 01845
LON BARTOLI 775-316-0016
Inspection Ref#:20857050
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 2020
every 5 years?
Report of Inspection/Test for System - Zone 5
FIRE DEPARTMENT CONNECTION `
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 2020
every 5 years?
Report of Inspection/Test for System Wall hydrant
FIRE DEPARTMENT CONNECTION
Has the FDC been hydrostatically tested as required Yes Date of the last FDC hydrostatic test? 2020
every 5 years?
MAIN DRAIN FLOW TESTS
System Initial static Residual Static Seconds to Flow Are results
Return to Observed? comparable
Initial Static to previous test?
Zone 1 145 120 145 <2 seconds Yes Yes
Zone 2 145 120 145 <2 seconds Yes Yes
Zone 3 145 120 145 <2 seconds Yes Yes
Zane 6 145 120 145 <2 seconds Yes Yes
Zone 145 120 146 <2seconds Yes Yes
Zone S 145 125 145 <2 seconds Yes Yes
Zone9 150 130 150 <2seconds Yes Yes
Zone 4 150 130 150 <2 seconds Yes Yes
Zones 150 130 150 <2seconds Yes Yes
Wall hydrant 145 125 145 <2 seconds Yes Yes
INSPECTORS TEST CONNECTION
System 7 Location Description Time Reported? Smooth Easily Signs? Pass?
to Orifice Accessible
Alarm
(seconds)
Zone 1 By shipping door 9 Ball valve :40 Yes Yes Yes Yes Yes
seconds
Zone 2 outside wall of Ball valve :55 Yes Yes Yes Yes Yes
bldg.location is seconds
marked
Copyright 2021 Inspect Point Page 4 of 10
Report of Inspection/Test
Quarterly NFPA 25
26 Hampshire 0R,tiudsan,Nk!
(603}293-7531
2021-02-26 Conducted by:Spencer Morse 261 Crooks ST,Worcester,MA
(508)852-7227
Property
44
LIFOAMINDUSTRIES-NORTHANDOVER Impact Fire Services-Hudson (97813en5T,Suite l,Danvers,MA
978i304-1506
2517728
Building#:7907771
351 HOLT RD
NORTH ANDOVER MA 01845
LON BARTOLI 775-316-0016
Inspection Ref#:20857050
INSPECTORS TEST CONNECTION
System Location Description Time Reported? Smooth Easily Signs? Pass?
to Orifice Accessible
Alarm
(seconds)
Zone 7 Near receiving Ball valve AS Yes Yes Yes Yes Yes
door office seconds
Zane 9 At zone 9 riser Test and drain :35 Yes Yes Yes Yes Yes
seconds
Zone 6 Zone 6 area front Ball valve :50 Yes Yes Yes Yes Yes
wall seconds
Zone 5 Under the stairs Bail valve 1:00 Yes Yes Yes Yes Yes
on far end of bldg minute
Zone 8 Zone 8 back wall Globe :25 Yes Yes Yes Yes Yes
seconds
Zone 3 Front of building Ball valve :30 Yes Yes Yes Yes Yes
under stairwell seconds
near break room
Zone 4 Near front of Ball valve :40 Yes Yes Yes Yes Yes
building under seconds
stairwell near
break room
Wall hydrant Riser Test and drain :34 aYes Yes Yes Yes Yes
VALVES
Tam
valve ope Easily Stems Flow per
System Description Location Type Size Secured n Accessible Signs Exercised Lubricated Pass Pass
Zone 7 Zone#7 At riser Butterfly B. Monitored Yes Yes Yes Yes NIA NIA Pass '..
control valve '..
Zone 5 Zone#5 At riser Wall Post 6" Locked Yes Yes Yes Yes NtA NtA NIA
control valve
Zone 4 Zone 4 At riser Wall Post 61 Locked Yes Yes Yes Yes NIA NIA NIA
control valve
Zone 8 Zone 48 At riser Butterfly 4' Monitored Yes Yes Yes Yes NtA NtA Pass
control valve
Zone 6 Zone 46 At Riser Butterfly 8, Monitored Yes Yes Yes Yes NIA NtA Pass
control valve
Zone Zone#1 Al riser Wall Post 8" Padlock Yes Yes Yes Yes NIA NIA NIA
control valve
Zone 7 Zone 47 outside at Post indicator 6" Locked Yes Yes Yes Yes NIA NIA i NIA
control valve riser
Copyright 2021 Inspect Point Page 5 of 10
Report of inspection/Test ! TM.1-1 ' ra,i, )'IR
Quarterly NFPA 25
26 Hampshire DR,Hudson,NH
1603)293-7531
2021.02.26 Conducted by:Spencer Morse 261 Brooks ST,Worcester,MA
(508)852-7227
Property 44
LIFOAM INDUSTRIES-NORTH ANDOVER Impact Fire Services-Hudson (978)3 enSi,Suite l,Danvers,Mn
978)304-1506
2517728
Building#:7907771
351 HOLT RD
NORTH ANDOVER MA 01845
LON BARTOLI 775-316-0016
Inspection Ref#:20857050
VALVES
Tam
Valve Ope Easily Stems Flow per
System Description Location Type Size Secured n Accessible Signs Exercised Lubricated Pass Pass
Zane 8 Zone 48 Outside wall Post indicator 6" Locked Yes Yes Yes Yes NIA NIA NIA
control valve
Zone 2 Zone#2 At riser Wall Post 8" Padlock Yes Yes Yes Yes NIA NIA NIA
control valve
Zone 3 Zone#3 At riser Wall Post 8" Padlock Yes Yes Yes Yes NIA NIA NIA
control valve
Zone 1 Main Piv In front of Post Indicator 6" Locked Yes Yes Yes Yes NIA NIA NIA
building
Zone 6 Outside wall In front Post Indicator 6" Locked Yes Yes Yes Yes N/A N/A NIA
Undear In front Postlndicator 6" Locked Yes Yes Yes Yes NIA NIA NIA
what riser
In front Near front Post Indicator 6" Locked Yes Yes Yes Yes NIA NIA NIA
door
In front Nearentrance Postindicalor 6" Locked Yes Yes Yes Yes NIA NIA NIA
Outside In front Post Indicator 6° Locked Yes Yes Yes Yes NIA NIA NIA
riser 4,5,9
(Wall Bask of Post Indicator 6" Locked Yes Yes Yes Yes NIA NIA NIA
hydrant)Nor building
mat closed
City side of At backflow OS&Y 10, Monitored Yes Yes Yes Yes Yes NIA Pass
backflow preventer And Locked
control valve
System side At backflow OS&Y 10" Monitored Yes Yes Yes Yes Yes N/A Pass
of backflow preventer And Locked
control valve
DRAIN VALVES
System Description Location Drain Aux Drain Drained Water Flow Observed
Zone 1 Z'Main drain Riser 1 Globe Valve Yes Yes
Zone 2 2'Main drain Riser 2 Globe Valve Yes Yes
Zone 3 2'main drain Riser 3 Globe Valve Yes Yes
Zone 6 2"main drain Riser 6 Globe Valve Yes Yes
Zone 8 2"main drain Riser 8 Globe Valve Yes Yes
Zone 9 2"main drain Riser 9 Globe Valve Yes Yes
Zone 4 2'Main drain Riser 4 Globe Valve Yes Yes
Zone 7 2'main drain Riser 7 Globe Valve Yes Yes
Zone 5 Main drain Riser 5 Globe Valve Yes Yes
Copyright 2021 Inspect Point Page 6 of 10
Report of Inspection/Test ��_ , , ,E_, . , x
Quarterly TVFPA 25 �:� !I�l�.�..( f �:�`.1);J..a
26 Hampshire DR,Hudson,NH
(603)293-7531
2021.02-26 Conducted by:Spencer Morse 261 Prooks 51,Worcester,MA
Property (508)852-7227
LIFOAM INDUSTRIES-NORTH ANDOVER Impact Fire Services-Hudson 44GardenST,Suite 1,Danvers,MA
(918)304-1506
2517728
Building#:7907771
351 HOLT RD
NORTH ANDOVER MA 01845
LON BARTOLI 775-316-0016
Inspection Ref#:20857050
Wall hydrant Test f dram Near riser 8 Test And Drain Yes Yes
Copyright 2021 Inspect Paint Page 7 of 10
Report of Inspection/Test 6 ' _ a:;, ..I:-i 1' ----
J..
Quarterly NFPA 25 . !? , .;
26 Hampshire DR,Hudson,NH
(603)293-7531
2021-02-26 Conducted by:Spencer Morse 251 Brooks ST,Worcester,MA
Property (5081 852-7227
LIFOAM INDUSTRIES-NORTH ANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA
(978)304-1506 _
2517728
Building#:7907771
351 HOLT RD
NORTH ANDOVER MA 01845
LON BARTOLI 775-316-0016
Inspection Ref#:20857050
Deficiencies-General Questions
None
Deficiencies-General Wet System Questions
None
Deficiencies=Zone 1
None
Deficiencies-Zone 2
None
Deficiencies-Zone 3
None
Deficiencies-Zone 6 ..
None
Deficiencies-Zone 7 .
None
Deficiencies-Zone 8
None
Deficiencies-Zone 9
None
Deficiencies-Zone a
None
Deficiencies-Zone 5
None
Deficiencies :Wall.hydrant'
None
Deficiencies-Inspectors Test Connection
None
Deficiencies-Valves
None
Copyright 2021 Inspect Point Page 8 of 10
Report of inspection/Test his J.tjt.l'f1.G'1
Quarterly NFPA 25
26 Hampshire AR,Hudson,NH
{603)293-7531
2021-02-26 Conducted by:Spencer Morse 261 brooks ST,Worcester,MA
(508)952-7227
Property
LIFOAM INDUSTRIES-NORTH ANDOVER Impact Fire Services-Hudson ( Garden sT,suite 1,Danvers,MA
97&)3£34-1506
2517728
Building#:7907771
351 HOLT RD
NORTH ANDOVER MA 01845
LON BARTOLI 775-316-0016
Inspection Ref#:20857050
Deficiencies- Drain Values
None
Copyright 2021 Inspect Point Page 9 of 10
Report of Inspection/Test 6
Quarteriy NFPA 25
26 Hampshire DR,Hudson,NH
(603)293-7531
2021-02-26 Conducted by:Spencer Morse 261 Brooks ST,Worcester,MA
Property (508)852-7227
LIFOAMINDUSTRIES-NORTHANDOVER Impact Fire Services-Hudson 44 Garden ST,Suite 1,Danvers,MA
2517728 (978)304.1506
Building#:7907771
351 HOLT RD
NORTH ANDOVER MA01845
LON BARTOLI 775-316.0016
Inspection Ref#:20857050
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection,and all equipment tested at this time was left in
operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
Spencer Morse 2021-02-26
Client Signature
I state that the information on this form is correct at the time and place of my inspection,and all equipment tested at this time was left in
operational condition upon completion of this inspection except as noted.
Client Name Signature Date Completed
Darren 2021-02-26
r
Copyright 2021 Inspect Point Page 10 of 10