North Andover Health Department
Community and Economic Development Division
NORTH ANDOVER HEALTH DEPARTMENT
NOTICE OF NONCOMPLIANCE
July 14,2021
Dean Dynan
2 Suntaug Street
Lynnfield, MA 01940
RE: ORDER TO BRING CONSTRUCTION INTO COMPLIANCE
Final Construction Inspection-1010 Johnson Street, North Andover, MA
Issued in accordance with 310 Code of Massachusetts Regulations (CMR) 15.000
Dean Dynan:
Pursuant to 310 CMR 15.255(3), on July 6,2021 staff from the North Andover
Health Department and Mill River Consulting performed a Final Construction
Inspection on the septic system being installed by you at 1010 Johnson Street, North
Andover, MA. During part of the inspection, three areas around the system were dug
into and the septic sand that was used was inspected to check its composition and
quality. Concerns arose due to amount of staining and the amount of fine particles
observed. The North Andover Health Inspector and the Engineer from Mill River
Consulting are both DEP Certified Soil Evaluators and it was determined at that time to
send the sand in question out for mechanical analysis.
On July, 9, 2021 staff from the North Andover Health Department delivered a
sample of the sand obtained from the septic system being constructed at the
aforementioned address to Yankee Engineering &Testing, Inc. in Worcester,MA. On
July 13,2021 Yankee Engineering &Testing, Inc. sent the results of the sieve analysis
which showed that the sand on site did not meet Title 5 requirements in accordance
with 310 CMR 15.255(3). The sieve analysis (copy attached) determined that the sand
used to construct this system slightly exceeded the #100 Sieve Size and significantly
exceeded the #200 Sieve Size.
Page 1 of 2
North Andover Health Department
120 Main Street
North Andover, MA 01845
Phone: 978.688.9540 Fax: 978.688.8476
June 14, 2021 (cont'd)
As determined onsite by visual inspection by the North Andover Health
Department and confirmed by the sieve analysis performed by Yankee Engineering &
Testing, Inc. the sand installed within the septic system located at 1010 Johnson Street
does not meet 310 CMR 15.255(3).
Pursuant to 310 CMR 15.025(4) as the licensed septic installer on the permit of record
for this septic installation,you are hereby ORDERED to bring the construction into
compliance by removing all the sand installed for this septic system within seven (7)
days from receipt of this letter.
Please be advised that each day's failure to comply with this order shall
constitute a separate offense and may result in penalties, 310 CMR 15.026(6). Any
person aggrieved by such order may appeal to any court of competent jurisdiction as
provided for by the laws of the Commonwealth in accordance with 310 CMR 15.026(1).
Please note that the dwelling located on this property and served by this septic system
is inhabited so the North Andover Health Department considers this in an imminent
threat to public health and the environment and may require any other action it deems
necessary in accordance with 310 CMR 15.026(3) during the pendency of a hearing on
the order.
Once all the sand is removed, please schedule another bed bottom inspection at
your earliest convenience. This inspection must be performed prior to any additional
sand being replaced at this location. Please feel free to call the Health Department with
any comments, questions or concerns at the number listed below.
Sincerely,
Man J. L Grasse,
North Andover Director of Public Health
Delivered Via:
Certified Mail #
Regular First Class Mail
Email-Uploaded to Viewpoint Permit
CC: Homeowner, 1010 Johnson Street, North Andover, MA 01845
James Kavanaugh, Engineer
Stephen Casey, North Andover Health Inspector
Mill River Consulting
BOH File
Suzanne Egan,Town Counsel
Page 2 of 2
North Andover Health Department
120 Main Street
North Andover, MA 01845
Phone: 978.688.9540 Fax: 978.688.8476
ankcc Engineering
a Tcstng, Inc.
July 13, 2021
Mr. Stephen Casey Jr.
Town of North Andover
120 main Street
North Andover, MA 01845
RE: MA.310 CMR Septic Fill (Title 5) Soil Gradation Analyses
1010 Johnson St—Title V Septic Sand
North Andover,Massachusetts Project # 2021-59
Dear Mr. Casey:
Presented herein are the results from one (1) gradation analyses, performed on a sample (L-30241A) of
proposed "Title 5" Septic soil, submitted July 9, 2021 and stated to represent the above source. The
sample, weighing about 5 lb., was tested in accordance with ASTM D-422 washed sieve methods,
yielding the following summarized results:
L-30241A: 1010 Johnson St.N. Andover—Title 5 Septic Fill Soil
USCS Soil Classification = SP-SM: brown f/m sand trace silt trace gravel
Sieve Percent MA 310 CMR Septic(Title V)Soil Sieve Total Sand
Size Passing Gradation Limits(%Passing) Size %Pass %Pass
2" 100 100%By Weight of Total Sample 2" 100 100
1" 100 no gradation limits 3/4" 100 100
1/2" 100 no gradation limits #4 96 100
#4 96 1 55%-100%By Wt.of Total Sample #8 92 96
#16 86 90
#30 74 77
#50 52 10%-100%By Wt.of Sand Fraction # 050 52
#100 20.2* 0%-20% By Wt.of Sand Fraction # 19.4 20.2*
#200 8.5* 0%-5% By Wt.of Sand Fraction dr:#2!0:0:
8.1 1 8.5*
As can be seen above, and on the attached "sand fraction" (100% < #4) gradation curve, the submitted
sample did NOT satisfy the MA. State gradation requirements(listed above) for"Title V"septic fill soil
as it was too fine(too silty) on#100 and#200 sieves.
Should you need additional information, or require further soil testing services,please do not hesitate to
contact me at our Worcester office.
Regards,
colt M. Mensen, P.E., P.G.
Director of Testing Services
10 Mason Street Worcester Massachusetts 01609
Tel(508)831-7404 Fax(508)831-7388
CONSTRUCTION INSPECTION&MATERIALS TESTING
www.yankeeengineering.com
Particle Size Distribution Report
C = O O O
O O O O O O VC)
100 MA Title V(septic)Sand Fraction
I I I I I I I I I I I I I I
90
I I I I I I I I
so I \
I I I I I I I I \ I I I I I
I I I I I I I I \ I I I1 I I I
�o
I I I I I I I I \ I I1 I I I
z 60 I I I I \\ I I
z 50 1 I I 1 1 1 I I
U
40 I I I
30
I I I I I I I I I \ I I I
20
I I I I I I I I I I\\ I I I I
10 I I I I I I I I I I I I I
I I I I I I I I I I I I I
0
100 10 1 0.1 0.01 0.001
GRAIN SIZE - mm.
%+3" %Gravel %Sand %Silt %Clay
0.0 0.0 91.5 8.5
SIEVE PERCENT SPEC.' PASS? Material Description
SIZE FINER PERCENT (X=NO) Brown f/m sand trace silt trace gravel
#4 100.0 100.0 Shown results exclude 4%gravel(no stone>3/4")
#8 96.2
#16 90.0
#30 76.7 Atterberg Limits
#50 51.8 10.0- 100.0 PL= NP LL= NV P1= NP
#100 20.2 0.0-20.0 X Coefficients
#200 8.5 0.0-5.0 X D85= 0.8662 D60= 0.3633 D50= 0.2890
D30= 0.1914 D15= 0.1237 D10= 0.0885
CU= 4.10 Cc= 1.14
Classification
USCS= SP-SM AASHTO= A-3
Remarks
Sample submitted by client on 07/09/21
Close to MA Title V Septic Sand Fraction gradation limits
See letter dated 07/13/21 for additional information
MA Title V(septic)Sand Fraction
Sample No.: L-30241A Source of Sample: 1010 Johnson St-N.Andover MA Date: 07/12/21
Location: Proposed Title V Septic Soil(sand fraction) Elev./Depth: submitted
YANKEE ENGINEERING Client: Town of North Andover
Project: Town of North Andover
j Various Projects/Sites
& TESTING, INC. Project No: 2021-59
Tested By: RIM Checked By: SMM