HomeMy WebLinkAboutReport of Inspection/Test - Inspection - 4/30/2021 Report of Inspection/Test
Annual NFPA 25 TlazdjL"_
FIRE PROTECTION
2021-04-30 Conducted by:Jim O'Sullivan CO.,tic AENAVNRNNANAENMENmmoomm
Property Manchester#W481
1060 Osgood Street MA Lie#SJ-001 500
TIA001
1060 Osgood Street Hampshire Fire Protection Co.,LLC
North Andover MA 8 North Wentworth Avenue
David Sarnuels Londonderry NH 03053
Print Date: 2021-04-30 603-432-8221
jsnowde n @ham pshirefire.com
Report of Inspection/Test General Questions
OWNER SECTION
Has the occupancy classification and hazard of contents 2 yes Are all fire protection systems in service? Yes
remained the sarne since the last inspection? 0 No El No
0 NA El NA
Has the system(s)remained in service without modification 0 Y(,s Was the systern(s)free of actuations of devices or alarms 2 Yes
since the last inspection? [A No since the last inspection? E) No
0 NA 0 NA
FIRE DEPARTMENT CONNECTION
Is the FDC plainly visible? L"I Yes Is the FDC easily accessible? B Yes
C3 No El No
Ll NA E3 NA
Is the FDC swivels and couplings not damaged? 0 YOS Are the FDC caps and plugs in place? B Yes
El No 0 No
El NA Ej NA
Are the FDC gaskets in place and in good condition? 0Yes Is the FDC check valve drip free? 0 Yes
El No ❑ No
El NA L1 NA
Is the clapper and automatic drain valve in place and 2 Yes Is the FDC identification sign(s)in place? Ed Yes
properly operating? El No El No
0 NA El NA
SPRINKLER HEADS
Are visible sprinklers free of corrosion and physical 2 Vag Is there proper clearance below the sprinklers? Rl Yes
damage? U No E) No
El NA El NA
Are visible sprinklers free of foreign materials including 2) Yes Is there liquid in all visible glass bulb sprinklers? R) Yes
paint? El No 0 No
0 NA 0 NA
Are all the sprinklers dated 1920 or later? (D Yes Have sprinklers Subject to harsh environments been El Yes
El No replaced or successfully sample tested in the last 5 years? El No
El NA Z NA
Are all escutcheons properly in place and free of damage? 0 Yes Are all standard response sprinkler heads less than 75 RI Yes
R) No years old or successfully sample tested within last 5 years? 171 No
El NA El NA
Are all standard response sprinklers less than 50 years old 0 Yes Are all dry-type sprinkler heads less than 10 years old or El Yes
or successfully sample tested within last 10 years? El No Successfully sample tested within last 10 years? 0 No
El NA Rl NA
Are all fast response sprinkler heads less than 20 years old EJ Y11 Are there the proper number and type of spare sprinklers 2 Yes
or successfully sample tested within last 10 years? n No and head wrench? 0 No
0 NA 0 NA
Copyrig lit 2021 Inspect Point Page 1 of 9
Report of Inspection/Test
Annual NFPA 25 QM�0�-
FIRE PROTECTION
2021-04-30 Conducted by:Jim O'Sullivan CM.18C MONNNNFAMMOOMMMOMMERNW
Property Manchester#W481
1060 Osgood Street MA Lie#SJ-001 500
TIA001
1060 Osgood Street Hampshire Fire Protection Co.,LLC
North Andover MA 8 North Wentworth Avenue
David Samuels Londonderry NH 03053
Print Date:2021-04-30 603-432-8221
jsnowdcn@hampshirefire.com
Are visible sprinklers in the proper position:upright, 0 Yes
pendent,sidewall,recessed,etc.? LJ No
[I NA
PIPES
Is the visible pipe in good condition with no external 2 yes Does visible pipe have no mechanical damage or leaks? 2 Yes
corrosion? 0 No El No
Lj NA El NA
Does visible pipe have no external loads? 0' Yes Are visible pipe hangers and seismic braces not damaged RI Yes
Ll No orloose? 0 No
0 NA ❑ NA
VALVE AREA
Is the hydraulic name plate(calculated systems)attached 0 yes Have the mechanical waterflow alarm devices passed tests [a Yes
securely to the riser and legible? El No by opening inspector's test connectionibypass connection 0 No
0 NA with alarms actuating and flow observed? El NA
The electrical waterflow alarm devices passed test by 2 Yes [lave post indicating valves been opened until spring or El Yes
opening inspector's test connection/bypass connection with El No torsion felt in the rod and then closed back 1/4 turn? El No
alarms actuating and flow observed? [I NA RI NA
All control valves operated through full range and returned 0 Yes Are all control valves(including backflow preventer isolation R Yes
to norrnal position? 0 No valves)in the correct(open or closed)position? El No
n NA El NA
Are all control valves(including backflow preventer isolation 0 Yes Are all control valves(including backflow preventer isolation Fv Yes
valves)properly supervised(electrically monitored,locked El No valves)accessible? El No
or sealed)? El NA 0 NA
Are all control valves(including backflow preventer isolation R Yes Are all control valves and check valves externally Ov Yes
valves)free from leaks? (:] No inspected,operating properly,and are in good condition? 171 No
E) NA 0 NA_
Are main drain and auxiliary valves in good condition and 2 Yes Are all pressure gauges on system in good condition and 0 Yes
identified with proper signage? D No showing normal water and air pressures? 0 No
[I NA [I NA_
ALARMS
Is the alarm valve free from physical damage? 2 Yes Is the Win in correct(open or closed)position? R) Yes
El No 0 No
El NA El NA_
Is there no leakage in the retarding chamber or drains? 2) Yes Are alarms and supervisory devices riot damaged? Cl Yes
El No El No
0 NA 0 NA
MAINTENANCE
Operating stem of all OS&Y valves lubricated,completely ED Yes
closed and reopened? 0 No
El NA
Copyright 2021 Inspect Point Page 2 of 9
Report of InspectionlTest
Annual NFPA 25 ULiQWzV1.-4
FIRE PROTECT101M
2021-04-30 Conducted by:Jim O'Sullivan CO.,lie MMENSIMMENNEWMENNOMM
Property Manchester#W481
1060 Osgood Street MA Lic#SJ-001500
TIA001
1060 Osgood Street Hampshire Fire Protection Co.,1.1-C
North Andover MA 8 North Wentworth Avenue
David Samuels Londonderry NH 03053
Print Date:2021-04-30 603-432-8221
jsnowden@liampshirefire.com
MISCELLANEOUS
Has visual inspection of all sprinklered areas of the building ❑ Yes Date of last annual walk-through(visual inspection): 4/28/2021
performed within last year? ❑ No
❑ NA
Copyright 2021 Inspect Point Page 3 of 9
Report of Inspection/Test
Annual NFPA 25 ZMWMJl
FIRE PROTECTION
2021-04-30 Conducted by:Jim O'Sullivan CO,,11C AIMNMMWffAVEREMMONOffMWMMW
Property Manchester#W481
1060 Osgood Street MA Lic It SJ-001 5,00
TIA001
1060 Osgood Street Hampshire Fire Protection Co.,LLC
North Andover MA 8 North Wentworth Avenue
David Samuels Londonderry NH 03053
Print Date:2021-04-30 603-432-8221
jsnowden@harnpshireflre.com
Report of Inspection/Test for System - Wet 1
5 YEAR
If due,size of lift needed: NIA
INTERNAL PIPE INSPECTION
Date of last 5-year internal pipe inspection? 5/20/2019 Date of next 5-year internal pipe inspection? 5/20/2024
Is system up-to-date with a scheduled 5 year internal pipe 2 Yes Are all gauges under 5 years old? 2 Yes
inspection? 0 No EJ No
Ej NA 0 NA
Are areas protected by the wet system properly heated? R Yes
El No
0 NA
MAIN DRAIN FLOW TESTS
System Initial static Residual Static Seconds to Flow Did waterflow Are results
Return to Observed? alarm operate? comparable
Initial Static to previous
test?
Wet 1 95 85 95 2 Yes Yes Yes
INSPECTORS TEST CONNECTION
Systern Location Description Time Reported? Smooth Easily Signs? Pass?
to Orifice Accessible
Alarm
(seconds)
Wet I 2nd floor AFS ITV 60 Yes Yes Yes Yes Yes
space(directly
above riser room)
VALVES
Flow/
of Tern
valva Easily Steins Turn per
System Description Location Type Size Secured Open Accessible Signs Exercised Lubricated s Pass
wet I System Rearriser OS&Y 4" Monitored Yes Yes Yes Yes Yes 3 Pass
control valve room
DELETE DELETE Sectional N/A NIA N/A N/A N/A NIA
ENTERED ENTEREDIN
IN ERROR ERROR
DRAIN VALVES
systern I Description Location Drain Aux Drain Drained Water Flow Observed- I I
Copyright 2021 Inspect Point Page 4 of 9
Report of Inspection/Test
Annual NFIPA 25 ULU991M�
FIRE PROTECTION
2021-04-30 Conducted by:Jim O'Sullivan CO..11C NAVEMONERINSUNKINENNUff
Property Manchester#W481
1060 Osgood Street MA Lic#SJ-001500
TIA001
1060 Osgood Street Hampshire Fire Protection Co., LLC
North Andover MA 8 North Wentworth Avenue
David Samuels Londonderry NH 03053
Print Date: 2021-04-30 603-432-8221
jstiowden@hampshirefire.coni
Wet 1 Main drain At riser Angle Valve NfA Yes
Copyright 2021 Inspect Point Page 5 of 9
Report of Inspection/Test
Annual NFPA 25 ML6Q�
FIRE PROTECTION
2021-04-30 Conducted by:Jim O'Sullivan CO.,UC AIMMMEMMIMMERMENMEMEM
Property Manchester#W481
1060 Osgood Street MA Lic#SJ-001500
TIA001
1060 Osgood Street Hampshire Fire Protection Co., LLC
North Andover MA 8 North Wentworth Avenue
David Samuels Londonderry NH 03053
Print Date:2021-04-30 603-432-8221
jsnowden@hampshirefire.coni
Deficiencies -General Questions
Copyright 2021 Inspect Point Page 6 of 9
Report of Inspection/Test
Annual NFPA 25
FIRE PROTECTION
2021-04-30 Conducted by:Jim O'Sullivan Co.,11C MEMMOMEMENEWOMMENSM
Property Manchester#W481
1060 Osgood Street MA Lic#SJ-001 500
TIA001
1060 Osgood Street Hampshire Fire Protection Co., 1.1-C
North Andover MA 8 North Wentworth Avenue
David Samuels Londonderry NH 03053
Print Date:2021-04-30 603-432-8221
jsnowden@hampshirefire.com
Are all escutcheons properly in place and free of damage? No
Slatus:Novi CHUcaI
Notes:
Missing outoroscutchoons;center stairwell(xl),former advanced fuel solutions space(xl).HP TAX&accounting space(xl).Martial arts studio(xl
Reliable model G screw on outer escutcheon)
AM
----------
1f
Copyright 2021 Inspect Point Page 7 of 9
Report of InspectionlTest
Annual NFPA 25 zla�
FIRE PROTECTIOM
2021-04-30 Conducted by:Jim O'Sullivan CO"tic
MLUMMOMMMENWAMMaimm
Property Manchester#W481
1060 Osgood Street MA Lic#SJ-001500
TIA001
1060 Osgood Street Hampshire Fire Protection Co., LLC
North Andover MA 8 North Wentworth Avenue
David Samuels Londonderry NH 03053
Print Date:2021-04-30 603-432-8221
jsnowden ,hampshiretire.com
I
Deficiencies -General Wet System Questions
None
[Deficiencies -Wet 1
None
Deficiencies-Inspectors Test Connection
None
Deficiencies-Valves
None
Deficiencies -Drain Valves
None
Copyright 2021 Inspect Point Page 8 of 9
Report of InspectionlTest
Annual NFPA 25
FIRE PROTECTION
2021.04-30 Conducted by:Jim O'Sullivan CO"fie MMESHIMMMIMMOMMMMUMM
Property Manchester#W481
1060 Osgood Street MA Lic#SJ-00 1500
TIA001
1060 Osgood Street Hampshire Fire Protection Co., LLC
North Andover MA 8 North Wentworth Avenue
David Samuels Londonderry NH 03053
Print Date:2021-04-30 603-432-8221
jsnowderi@harnpshirefire.com
Inspector Signature
I state that the information on this form Is correct at the time and place of my inspection,and all equipment tested at this time was left in operational
condition upon completion of this inspection except as rioted.
Inspector Name Signature Date Completed
Jim O'Sullivan 2021-04-30
Client Signature
I state that the information on this form is correct at the tirne,and place of my inspection,and all equipment tested at this time was left in operational
condition upon completion of this inspection except as rioted.
Client Name Signature Date Completed
Dave-Covid 19 2021-04-30
Copyright 2021 Inspect Point Page 9 of 9