HomeMy WebLinkAboutSeptic Denial Letter - Correspondence - 288 FOSTER STREET 10/27/2021 North Andover Health Department
(nmmmnity and Economic D�evml!mpment Division
October 27,2021
V'ladi.rn.ir°Neniche:nok
Merrimack Engineering Services
66 Park Street;
Andover,MA 01810
12e: Subsurface Sewage Disposal System Plan ft)r 288 Foster Street{Ma ) 104,1),I,ot,(i)
Dear Mr.Neinchenok:
The proposed wastewater system design plan for the above site dated October 8, 2021. has been reviewed.
i nfortunately, the plan cannot be approved until the fbIlowinl itenis are corrected, The specific section it)Title 5:
310 C,MR 15.000,or North Andover regulation that is not arret by this design hallows each ite¢n where applicable.
➢. Provide the brand and model ofthe proposed effluent filter(15.227 and NA 3.2)
2. Clarify,the conflicting notes regarding the plaacement of manhole covers to finished grade over glee pump
(15.231)
:3. Note the requirement f:arr a high-water alarm to be located within the building and to be powered on a
separate circuit from the puarap(15.231)
4, provide: the puanp performance curve(15.2.20)
5. Provide notation regarding the watertightness ofthe pura:ap tank(15.221)
6. C'hirify the required perforated leach pipe size to be 3/ -5�8" diauleter(15.251)
Please fee] free to contact the office;or Mill Diver C:'onstilting at 978-282-0014 with any questions you in ay have.
e look formird to working with you to obtain a wastewater treatment.and dispersal system which will be in
compliance with all regulations and assure,protection of°public health and the environment of`North Andover,
Sincerely,
Stepdacn .ascy 1r.
lleaalth Inspector
cc: Owner
File
Page I< caf Il.
North Andover Health Department, Town Hall, 120 Main Street,
North Andover, l'w471 0 1845 hone: 7 ,6 8., 540 Fax, 9 78.688. 9542