HomeMy WebLinkAbout1984 Department Review I
NORTH ANEXHIER IFURE DEPART
n
CENTRAL FIRE HEADOUNRT
ialR Noo'U...'V AV'lld0vVr, Niviag"1b, 1IB4
4 May 1984
TO: North Andover Planning Board
From: Fire, Chief Dolan
RE: Jefferson Park
I have reviewed the site plan for Jefferson Park
and have the following omme a t
1 . Each buildinq must be fully protected by
an automatic sprinklersystem in accordance
with M. G.L. Chapter 148 See. 26 G.
. A fire alarm system for notification of the
occupants must be installed.
3. Both of the above systems must be connected
to the municipal firealarm, system.
. A sufficient icien number of fire hydrants should
be installed within the—park from the water
main on R,rs. 114 to provide, water for fire
Sri .
William Via'"; Dolano Chi 1
��uuy
em ("Are
wm1 u'H ni r�� flim,�
I
JlAmmLdv D.Nd ble,Jr, mRyrffwd J.^Oaftly®Chaliwiam'nam John P...T'hoinpgbru,Clerk
'roWN OF NORTH ANDOVER, MASS.
BOARDO
WATER, LR. PACK. PLAYGROUND ANDSCHOOL GROUNDS 0EPART E T
SMa'1WEMWiEMEM AND 1INGWEE!R
JO EPH J. BOR E ]
TELEPHONE ONE 687-79041
a 1'," u
�, r wni
r-
DO
Mr. Paul Hedstrom, Chairmat'i
Planning Board
120 MainStreet �.
North Andover, Ma. 01845
Dear Paul :
Pei,.-suant,'. to your request, we have reviewed the site plans for
Jefferson Park and have the followingrecommendations to make:
The water main shall be our eight inch ductile iron main ending
with a hydrant at the northerly building.
The sewer shall be 8" vitrified clny. The invert entering the
existing manhole shall be at elevation .." !. ,. No section of sewer
shall have less than four feet of cover below the finish grade .
Very u-mul yours ,
0 1 OF 1' IWORKS
0 It
JJ : Ib
JA�IYdra���r ,
J