HomeMy WebLinkAbout1992-12-22 Department Review NORTH AND OVER FIRE DEPARTMENT
CENTRAL FIRE HEADQUARTERS
•.a;:�.` ,Ut' 124 Main Street
" s�CHUS Norlh Andover, Mass. 0164
WILLIAM V, DOLAk
Chief of Department Tel, (50$) 686- 81
E. A. GRALIA
CONSTRUCTION CO. , 'IN .
00 NORTH MAIN ST.
EAST LONGMEADOW, MA 01028
November 19 , 1992
Mr. Gralia,
I have reviewed the September 3 , 1985 , order of conditions issued b
the Planning Board to the then iDwners of the Osgood Mill Complex.
The fire department requires or is submitting .information on the
following:
Page 2 Item 2 .
a. We believe that all the underground tanks have been
removed fron the site and if any are to be imtalled the
fire department must be contacted. Please note the attached
letter fro-m then DEQE regarding contamination on the site .
This location is Still prosent on the site list as a
Location To Be Investigated (L.T.B. 1) .
2c, Copies of the completion certificates for asbestos removal
should be forwarded to the fire department.
Page 3 Item 5
a. The main bridge, noted in item 4 was rebuilt and designed
to earn, the weight of fire apparatus . It is acceptable as
designed and con8tructed.
The second lower cement bridge was to be reconstructed but
was not.
You have stated that the former parking area for the '}Olde
Osgood Mill" office building would not be used and that the
area formerly used for that purpose would be utilized for
recreation , tennis r-ourt etc.
Whoever owns the office building must have sufficient fire
department access , in accordance with 527 CUR 25 . 00 relating
to Obst,uctions _ and Hazardz in cer� .,j,�.... B►�ildirxc�s and on
"SMOKE Dt=TECTOR AVF- LIMES"
Public and Private Ways particularly 25. 05 Co
In lieu, of reconstructing this bridge the department
requests that the bridge be certified as to its load
capacity, and a copy of that certification suit to the fire
department. In addition, the. present access way leading
from the courtyard across the bridge and to the rear of the
office building should be maintained as a fire access ,
through whatever means the Planning Board deems appropriate.
This fire access road should be as wide as the bridge ,
twelve feet, and be constructed to support the weight of the
fire apparatus. it should begin at the courtyard and
terminate at the bridge. The access road surface does not
have to be hot top.
The maintenance of this fire access would not prevent
the proposed recreational uses.
That agreement will insure present or future owners of the
property, that fire personnel will have access to this
unusual building in time of a fire or emergency.
5b. it is my understanding that the entire water main has not
been installed or acoepted by the DPW. fence the water main
is installed and is acceptable to the DPW the fire
department's request will be satisfied.
50 . The fire hydrants were installed but will need to be
tested and the DPW will have to ver;ly if they are properly
connected.
5d. Automatic fire sprinkler systems are required to be
installed in accordance with Mass . General Law Chapter 148
section 26 1 . These systems shall comply with National Fire
Protection Association Standard 13R within the residential
areas . The cellar area shall have a system installed that
is in compliance with NFPA 13 . This was how the original
building was to be equipped but the work never completed.
By completing these installations with some mod,itioations
they will be acceptable. The fire department will work the
the sprinkler contractor to bring about these modifications.
Some of those modifications are:
1. All the installations must be inspected and tested
to see if the flows will be adequate. This will be
dame in cooperation with the fire ' department.
. The connection tax' !3prinkler systems protecting the
units and adjacent halls shall be corrected by the
removal of the separate sprinkler shut off. There shall
he only one shut off . When the shut off is activated
bath the domestic and sprinkler Muter shall be off .
3 . A water flow switch shall be installed in the
sprinkler piping which shall activate an audio visual
alarm outside the unit being protected.
4 . The sprinkler contractor shall review the entire
sprinkler protection system with the Fire Chief prior
to the start of any work an any existing or new
systems.
5e. The dry - fire hydrant is to be maintained by the property
owners. it needs to be tested and the fire department would
assist with that. The adapter required for its use was
stolen and in its current condition the department cannot
connect to the existing pipe.
5f . The automatic sprinkler system used to protect the storage
area on the lower floors would be installed in accordance
with NFPA 13 and would require a fire department connection.
This connection is also required under 780 CMR (Mass .
Building Code) Section 1004 . Water Sprinkler Systems.
The fire department connections are also required on the
standpipe systems required for this building. some of those
standpipes were installed and some were not. Most, if not
all , were never completed_ These standpipes -must No
installed in accordance with 780 CNR 1012 standpipe Systems.
The fire department will work in conjunction with your
contractor to insure that the- proper adapters and threads
are installed on these devices.
5g. The field stone building has a fire sprinkler system in
in and the system must be maintained in a ready condition.
changes in use of the building will require fire department
review for required fire protection systems and alarm
systems.
Yalu stated that this building is temporarily intended to
be utilized as a storage and maintenance building for the
complex. Fire protection and alarm systems will be in
compliance with Mass. General Law Chapter 148, 527 C R Fire
Prevention Regulations, 780 CMR the State Building Code and
the ,americans with Disabilities Act (AD ) for the use to
which it is utilized.
5h. The existing fire alarm box, located on the old mill shall
be removed. The pedestal fire alarm box for the courtyard
was never installed and need not be installed. A new fire
alarm box and remote annunciator shell was installed at the
far right corner of the existing old mill . This fire alarm
box and remote annunciator shall service all the fire alarm
devices in the residential complex.
The main fire alarm control panel for the complex shall be
located in the stairwell adjacent to the fire alarm Lox.
S. The majority of the fire alarm system components have Loen
installed but are not working. These need to be inspected,
tested and be in compliance with Mass. General Law Chapter
148 Section 26 S and Section 26 D, 527 CMR 24, 780 CMR 1017 ,
1018 and the ADA. The fire department will work with the
selected fire alarm contractor in attaining compliance with
these systems .
Items 6a through 6d are still applicable, and are part
of the requir8ments stated in the laws and regulations
above.
7, The -fire alarm control panel, as stated in 5h above, shall
be located .
B . A water flow alarm for each k@rinkler system shall be
installed as stated in 5d. These alarms will not activate
the master fire alarm box. The system protecting the
storage area Shall have its flow Switch connected to the
main control panel and the activation of that flow switch
will trip the master fire alarm box-
mbg fire department is eager t0 Work with you to complete this
project while providing for the fire safety of the future rekidentn of
the Town.
if there any questions regarding this matter please contact -me.
-
William V. Dolan
Fire Chief
cc: Lt. Ken Gong
G. Pi=a, DPW
£. Bradley . Town planner
K. P. Nelson, Cam. De«.
'r 01 W N 0 F N 0 RTITT A N D 0 V E R, M A,5 5 A C 1-1 LJ 5 E I-TS
DVVISRON OF PUBLIC WORKS
304, q'FRFTJ,, 01045
VWLUAM A. CYR TnEpmow 6H7 7964
MMMU mmom FAX: f500) 603 930
December 1, 1992
Mr. George Perna, Chairperson
Planning Board
120 Main Street
North Andover, Ma 01845
Re : Osgood Mill
Dear Mr. Perna :
The Division of Public Works has reviewed the September 1985
Special Permit and various construction Eand site plans of the
Osgood Mill Complex, Based on the review of available information
we have compiled the following list of outstanding issues which
need to be addressed.
1 . PTovide a plan for construction of adequate vehicular and
pedestrian access to both Main Street and High Street .
The plan should consider the potential future access to
Sutton St . The plan should be based on. ona updated
traffic study and should address our concerns regarding
flow and site distance in the direction of and at the
intersection with Main St.
2 . Connect the new watermain on the Osgood Mill site to the
recently installed water main on the North Andover Mills
property. Abandon aU unlined on site water mains to be
used for domestic purposes . Hydrants should be installed,
in accordance with sheet C-4 of the, 1987 plan, or as
required by the Fire Department .
3 . Tne water installations must conform to 310 CM R 2222
regarding cross-connections . 1:11an,8 showing proposed
installation of back. flow err ev8ntia,11 devices must be
submitted to VE. P . for review and approval .
4 . The sewage pumping station and collection system should
conforin to the appropriate regulations and specifications
of the Division of Public Works . A sewer connection
permit must be obtained from the Division of Water
Pollution Control of the Mass Division of Environmental
Page 2 .
Protection , The existing Pumping station along
Cochic£ewicE Brook should be £edisigned to reflect future
Site use .
5 . Provide an interim as-Built plan prior t0 Continuing
con8t£2ction 0n Site and a final as-built when
construction is Completed.
Very tr Ioursi /
J. William Smnrciak, P . E .
Assistant Director
JWHijm