HomeMy WebLinkAboutField Inspection & Service Report - Title V Inspection Report - 45 BRIDGES LANE 2/16/2023 0�\�Ca I 9
Ou
� Mcallroe •71 o
16002 West 1101'Street, Lenexa, KS 66219, Phone 913-422-0707, Fax 913-422-0808
e-mail:onsite@biomicrobics.com,www.biomicrobics.com,800-753-FAST(3278)
MASSACHUSETTS FIELD INSPECTION & SERVICE REPORT
For Bio-Microbics FAS7*Systems
42277
INSTALLATION AUTHORIZED SERVICE PROVIDER
Installation Address: 45 Bridges Lane Name: Wastewater Treatment Services,Inc.
North Andover,MA 01845
Owner Name: Michael Fox
Mail Address: 45 Bridges Lane Mail Address: 44 Commercial Street
North Andover,MA 01845 Raynham,MA 02767
Phone: Fax: e-mail: Phone: (508)880-0233 Fax: (508)880-7232 e-mail:
INSTALLATION INFORMATION
Model No. Serial No, atartup Date Date of last pump out
MicroFAST.5 24751 5/17/2005 526/2022
Approval Typg O General O Provisional O Piloting (x)Remedial O General Denite
Seasonal Residence ()Yes (x) No
EQUIPMENT YES NO MAINTENANCE PERFORMED AND COMMENTS
Electrical Panel(s)
Visual Alarm Operating x
Audio Alarm Operating x
(if present)
Blower(s)
Air Inlet Filter Clean x
Blower Hood Vents Clear x
Excessive Noise x
Excessive Vibration x
Treatment unit(s)
Unusual Odor x
Settleable Solids Test Performed
Pump out Required x
Primary Settling Zone Sludge Depth 12"
Aerobic Treatment Zone Sludge Depth 14"
Thickness of Scum Layer 1"
Sludge Level Distance to Outlet
Depth of Ponding Within SAS
Visual Observation Comments:
Measurement Comments:
EFFLUENT LIMIT RESULT
Estimated Daily Flow 440 gpd
pH(Standard Units) 6 to 9 7.8
Turbidity <40 NTU l0
Dissolved Oxygen >2 Mg/L 4.66
Color Clear Clear
Temperature
Odor Not Septic Earthy
Effluent Solids (x)None ()Some
Effluent Samples Taken:
Influent: ()pH ()BOD ()CBOD ()TSS ()TKN ()Nitrate ()Nitrite ()Total Nitrogen()Phosphorus()Spec.Cond. ()Ammonia ()Alkalinity
O Oil/Grease OVOC ()Fecal Coliform
Effluent: ()pH ()BOD ()C'BOD ()TSS ()TKN ()Nitrate ()Nitrite ()Total Nitrogen()Phosphorus()Spec.Cond. ()Ammonia ()Alkalinity
()Oil/Grease OVOC ()Fecal Coliform
Description of any maintenance performed since previous inspection&during this inspection: Cleaned Filter,Checked Splash Recycle,Pump(s)
Inspected,Float(s)Inspected
Notes and Comments: Pumps and floats have been inspected and are operational.
Distal Pressure: DPRI: 12, DPR2: 12
CERTIFIED OPERATOR NAME CERTIFICATION NUMBER SERVICE DATE
Brendan Pires 19033 8/25/22