Loading...
HomeMy WebLinkAbout1986-06-16 Department Review SPR WITHDRAWN NORTH ANDOVER FIRE DEPARTMENT m CENTRAL FIRE HEADQUARTERS 124 Main Street ARAYSlJ hP�`~rc�J I �,3Ac +us North Andover, Mass. 01845 WIL.L.IAM V, ©OL.AN Tel. (617) 66-3812 Chief of Department To: No. Andover Planning Board From: Fire Chief Dolan Re: Special Permit Holt Road ;t, Date: April 8 , 1986 I have reviewed the plans submitted and have the following comments : 1 . I disagree with the total floor space of 5998. 5 . The building is over the 7500 sq. ft. requirement of MGL Chapter 148 Section 26G and will, require an automatic sprinkler system with fire department connection. A copy of 26G is attached, 2. A fire detection system must be installed as required by the Fire Chief and these systems must be connected to the municipal fire alarm system through the installation of a fire alarm box 3 . The developer must contact the Fire Chief regarding both fire detection and suppression systems. 4 . Any underground storage must meet state requirements of February 1 , 1986 William V. Dolan, Fire Chief "SMOKE DETECTORS SAVE LIVES" Section 26G. Installation of Automatic Sprinkler Systems; Enforc•e.- ment. In any city or town which accepts the provisions of this section, every building or addition of more than seven thousand five hundred gross square feet in floor area shall be protected throughout with an adequate system of automatic sprinklers in accordance with the provi- sions of the state building code. No such sprinkler system shall be required unless sufficient water and water pressure exists. For purposes of this section, the gross square feet of a building or. addition shall include the sum total of the floor areas for all. floor levels, . basements and subbasements, measured from *outs.ide walls, irrespective of the existence of interior fire resistive walls, floors and ceilings. In such buildings or additions, or in certain areas of such buildings or additions, where the discharge of water would be an actual danger in the evezit of fire, the head of the fire department shall permit the in- stallation of such other fire suppressant systems as. are prescribed by the state building code in lieu of automatic sprinklers. Automatic suppressant or sprinkler systems shall not be required..'i,n rodms. or areas of a telephone central office equipment building when such. rooms or areas are protected with an automatic fire alarm ,system: ,:Spri.nkler systems shall not be required in a one story building having.la, fire resistance rating as prescribed in the state building code. that is used solely for offices provided -the building is protected ,by: an­automatic fire. alarm system. This section shall not apply to buildings or additions used..-for residential purposes. The head.of the fire department shall enforce the provisions of ' i9'hia eeat vn shall apply to construction of buf.ld`l"g`i ' r gdditions or "mAjor 'alterations' commenced after July first,, nineteetV huhdred and t �oRry O£tt,eo �6q'`'A Fes- A BOARD OF HEALTH 120 MAIN STREET ��ssaCHuSti NORTH ANDOVER, MASS, 01845 TEL. 682-6400 April 23 , 1986 North Andover Planning Board North Andover Re : Lot 2 Holt Rd . Mass . Gentlemen: This lot has not yet passed a percolation test . Ground water and soil testing has been completed and conditions were encouraging. Very truly yours , Michael Graf Health Inspector mg;mj C3PP= or C"'ONSERVATION COMMISSION o 3,£P rb TELEPHONE 683-7105 DATE: May 5, 1986 TO: Planning Board RE: Comments for H O L_T ROAD {:1 f f i. E e 4., r.;tu r-,;,g e 1.-;u J. }. d i n,,: 1 . No SSD S is shown on they plan. 2. No wetlands a r-e shown an the plan. however. extensive grading has been done on the lot and the front left CC]h-ller h '.'B t::C-'`..t2r'-Ed the drain 01 ORT" I i µ 6° OFFICE OF MG AY SURVEYOR i = * 384 OSGOOD STREET TOWN OF NORTH ANDOVER MASSACHUSETTS 01845 csause� i WILLIAM A.CYR TELEPHONE 685-0950 Highway Surveyor May 12, 1986 Michael Roberts, Chairman. Planning Board 120 Main St. North :Andover, Ma. Re: Bolt Rd. Site Plan Review - Cristaldi Dear Mike: I have reviewed plans and make the following recommendations: Any roof or site drainage is to be tied into the street drainage as specified and approved by the Highway Dept. Written permission and street opening permit required. Driveway Entry Permits will be required by this department. °very truly yours, L i G C' YV� Ct William A. Cyr Highway Surveyor WAC/m