HomeMy WebLinkAbout2023-11-21 Response to Peer Review WSP Sullivan Engineering Group, LLC Civil Engineers&Land Development Consultants November 20, 2023 Ms. Jean Enright, Planning Director North Andover Planning Board 120 Main Street North Andover, MA 01845 Re; 173 Johnson Street, North Andover Response to Peer Review letter dated 11/16/2023 Ms. Enright; The following is a written response to the peer review performed by Horsley Witten Group in a comment letter dated 11/16/2023. An updated Site flan is provided as well with a revision date on 11/20/2023. Items requiring comment are numbered in the same numbering sequence in the 11/16/23 peer review fetter for ease in cross referencing. 2b, Summary of Impervious Area (Existing&Proposed) &Land Area to be disturbed Total Land Disturbance: 1,110 s.f (Permanent Disturbance: 272 s.f.,Temp. Disturbance: 838 s,f.) Impervious Areas: Item: Existing: Proposed: House 1,480 1,480 Shed 160 160 Paved Driveway 1,720 1,720 Other Pavement Areas 98 98 Retaining Wall 18 18 Slate Walk 300 300 Paver Patio 396 396 Bulkhead 30 30 Addition n/a 272 Total: 4,202 sf 4,474 sf 8a. A separate LOW line was added to the plan for the construction entrance and tree protection. 8b. A note was to the design plan that the developer shall clearly mark limits of no land disturbance prior to any land disturbance. 8c. One tree is to be protected during construction. A tree protection construction detail was added to the plan with a note. 9. A standalone, signed O&M Plan has been prepared per the reviewer recommendations. P.O. Box 2004 Woburn, MA 01888 (781) 854-8644 e-mail:jaeksull53@comeast.net i I believe this address s all concerns and comments per the peer review letter and planning Board comments. If you have any qu , Lions please email or call me. Very' =u1 Yo r; J4tlF1 0-1 ; Jac S ll�van P.E. . No. 4t;�G Attachments: '+, 57, 1) Standalone,signed O&M plan and sketch of BMP's. 2) Plot Platt of Land— 173 Johnson Street,North Andover, revised 11/20/23, scale: 1"=20' P.O. Box 2004 Woburn, MA 01888 (781) 854-8644 e-inail:jacksuII53@comeast.net 1 Sullivan Engineering Group, LLC Civil Engineers Land Development Consultants Long-Term Stormwater Operation & Maintenance Plan 173 Johnson Street, North Andover Current Owners: Christopher and Katherine Hughes Reponsible Parties for O&M: Christopher and Katherine Hughes Beginning with the construction of the drainage system, and continuing in perpetuity thereafter, the owner(s) of the site shall maintain in accordance with the following schedule: a. Pavement and walkways shall be swept in the early spring immediately after snow melt b. Roof drain inlets, downspouts, and roof drain pipes - All components of the roof drain collection system shall be inspected at least 2 times per year. Sediments and debris shall be removed and disposed of in accordance with all applicable federal, state, and local laws. Any components that become damaged shall be repaired or replaced immediately upon discovery to assure proper conveyance of stormwater runoff into the drywell systems. Leaves shall be removed from gutters. c. Infiltration Chambers—The level of water in the infiltration chambers shall be monitored during and after heavy rain storms at least 2 times per year during the first year of operation and at least twice annually thereafter for evidence of clogging or other problems. If water does not leave the chambers within 72 hours after the storm, or if water breaks out on the surface above the system, or if the roof collection system begins to overflow frequently (for the 10 year storm intensity or less intense storms), the infiltration bed is likely clogged. The infiltration bed shall be cleaned and repaired or replaced as needed to maintain proper functioning. d. Vegetation shall be maintained in healthy condition to prevent erosion and sedimentation in the drainage system and wetland resource areas. e. Infiltration Chamber Inspection Port--The inspection port should be opened to complete the water level inspection and general inspection within the chambers (see item "c" above) 11/20/2023 Owner: Date Katherine Hughes Estimated Operation and Maintenance Cost. $0 if performed by owner; $5001yr if performed by contractor Attached: • Inspection Log • Sketch Plan of Stormwater Inspection Components • Cultec Operation and Maintenance Guidelines P.O. Box 2004 Woburn, MA 01888 (781) 854-8644 e-mail:jacksul153@comcast.net I 173 Johnson Street—Inspection Log Inspection and Maintenance Report Form To be completed per the Operation and Maintenance schedule Inspector: Date: Inspection Cheddist Item: Pavement and Walkways Accumulated sand, sediment, leaves Yes or No (circle one) Sweeping took place Yes or No (circle one) Roof drains inlets and downspouts Any signs of sediment or debris at outlets Yes or No (circle one) Condition of drain inlets/downspouts Good or Poor (circle one) Any piping need replacement Yes or No (circle one) Remove leaves from gutters Yes or No (circle one) Infiltration Chambers Any signs of water breakout Yes or No (circle one) Any water in chambers Yes or No (circle one) If water in chamber, is it empy after 72 hrs Yes or No (circle one) Vegetation Does site vegetation, including grass look health Yes or No (circle one) Inspection Port Did inspection port open Yes or No (circle one) Is Inspection port in good condition Yes or No (circle one) Additional Notes or Corrective measures taken: P.O. Box 2004 Woburn, MA 01888 (781) 854-8644 e-mail:jacksu1153@comcast.net t SKE 'CH P ,AN OF 00 MAIN 'F-� � - , A4E tixu Z , j C. BUILDING ETBACK LINE TYP) j Item, a - 8 refer tO notation 3/ o f MAoi n tre n a n c o S c 6e dul- rop. Dralgage Field / / is W 7.5 x23;5y(See detail) on-'Pa�,e� l - '� HDPE 86XI / ' ' �' Inspection Po t y to Grade. Gross / Area / t;.ixa / Limit a Prop. ' /r i � n axr C Soil 95xn /t18x1 —} / Stockplle / 86.2 7/ / w _ Area I // / /Pa be Removed ore M'l 950 o � � 3 / r3p8 srxA WX" 2x Grass / Area / 92x;s J6x8 1 Cgs 9tSxR / E WS / xn Q � � � tv � � 9ca/o 26" s2� 91xi 1 p 98x7 950 N� Grass Area G ass N , k <� 1 1 1 1 1 N a ��rea , �� 4 s.'x4 n 11 1 \ t1x2 / Q SS Secondary Limit of 950 1 or Ex. Slate i mar 1 Work Yne depicting Walkway / 1 y ; const ction access O" egr ss route. 41 /xa / 970 / Q 95A 1 brass / I Area / 98x 9:,x3 V 10-* /1 I / 97 97xT 92x1 C%� x1 f� .1 9t7x� pr. �ne 3.9.9, Jo'��a� / 97x8 ~ 26"0 43,47 95x8 —DH S20 34'29"E 1)/xt3 FND / `�7a R= 5.00 r / / 141.29' < W30 L=4.67' S15 0,09------------ „E \ SS .7fxG t-/0HN . yap S ti p ham ; rr ^ Y OB e' i ` d 1 r F a rf� � t } H m15. OPERATIONS AND MAINTENANCE 1 Published by CULTEC P.O. Box 280 878 Federal Road Brookfield, Connecticut 06804 USA www,cultec.com Copyright Notice © 2023 CULTEC All rights reserved. Printed In the USA. This document and any accompanying CULTEC products are copyrighted by CULTEC. Any reproduction and/or distribution without prior written consent from CULTEC is strictly prohibited. :disclaimers. The drawings, photographs and illustrations shown in this document are for illustrative purposes only and are not necessarily to scale. Actual designs may vary. CULTEC reserves the right to make design and/or specification changes at any time without notice at CULTEC's sole discretion. CULTEC, the CULTEC logo, RECHARGER, CONTACTOR, HVLV, PAC, STORMFILTER, STORMGENIE and The Chamber with The Stripe are registered trademarks of CULTEC. Chamber of Choice, HD, 100, 125, 150, 150XL, 180, 280, 330, 330XL, 360, V8, 902, Field Drain Panel, C-1, C-2, C-3, C-4, EZ-24, Landscape Series are trademarks of CULTEC. cQ Copyright on all drawings, illustrations, photos, charts - CULTEC. All rights reserved. Protected by one or rnore of the following patents owned by Cultec: U.S. Patents 6,129,482; 6,322,288; 6,854,925; 7,226,241; 7,806,627; 8,366,346; 8,425,148; U.S. Designs D613,819; D638,095; D668,318; Canadian Patent 2,450,565; 2,591,255; Canadian Designs 129144; 135983; 159073; 160977; and/or other U.S. or Foreign Patent(s) or Patent(s) Pending. Contact Information: For general information on our other products and services, please contact our offices within the United States at (800)428-5832, (203)775-4416 ext. 202, or e-mail us at CT-Customer5ervice@cultec.com. For technical support, please call (203)775-4416 ext. 203 or e-mail CT Tech@cultec.com. Visit www.cultec.com/downloads.html for Product Downloads and CAD details. Doc ID; CLT057 11-23 November 2023 These instructions are for single-layer traffic applications only. For multi-layer applications, contact CULTEC. All Illustrations and photos shown herein are examples of typical situations. Be sure to follow the engineer's drawings. Actual designs may vary. . , , .For more information, contact CULTEC at (203) 775-4416 or visit Owww.cultec.co . mm .�.w a m• 0 CULTEC CLT057 11-23 CULTEC STORMWATER CHAMBERS CULTEV This manual contains guidelines recommended by CULTEC and may be used In conjunction with, but not to supersede, local regulations or regulatory authorities. OSHA Guidelines must be followed when lnspecting or cleaning any structure. Introduction The CULTEC Subsurface Stormwater Management System is a high-density polyethylene (HDPE) chamber system arranged in parallel rows surrounded by washed stone. The CULTEC chambers create arch-shaped voids within the washed stone to provide stormwater detention, retention, infiltration, and reclamation. Filter fabric is placed between the native soil and stone interface to prevent the Intrusion of fines into the system. In order to minimize the amount of sediment which may enter the CULTEC system, a sediment collection device (stormwater pretreat- ment device) is recommended upstream from the CULTEC chamber system. Examples of pretreatment devices Include, but are not limited to, an appropriately sized catch basin with sump, pretreatment catchment device, oil grit separator, or baffled distribution box. Manufactured pretreatment devices may also be used in accordance with CULTEC chambers. Installation, operation, and maintenance of these devices shall be in accordance with manufacturer's recommendations. Almost all of the sediment entering the stormwater management system will be collected within the pretreatment device. Best Management Practices allow for the maintenance of the preliminary collection systems prior to feeding the CULTEC chambers. The pretreatment structures shall be Inspected for any debris that will restrict Inlet flow rates. Outfall structures, If any, such as outlet control must also be inspected for any obstructions that would restrict outlet Flow rates. OSHA Guidelines must be followed when Inspecting or cleaning any structure. Operation and Maintenance Requirements I. Operation CULTEC stormwater management systems shall be operated to receive only stormwater run-off In accordance with applicable local regulations. CULTEC subsurface stormwater management chambers operate at peak performance when installed in series with pretreatment. Pretreatment of suspended solids is superior to treatment of solids once they have been introduced into the system. The use of pretreatment is adequate as long as the structure is maintained and the site remains stable with finished impervious surfaces such as parking lots, walkways, and pervious areas are properly maintained. If there Is to be an unstable condition, such as improvements to buildings or parking areas, all proper silt control measures shall be Implemented according to local regulations. 11. Inspection and Maintenance Options A. The CULTEC system may be equipped with an Inspection port located on the Inlet row. The inspection port is a circular cast box placed in a rectangular concrete collar. When the lid Is removed, a 6-inch (150 mm) pipe with a screw-in plug will be exposed. Remove the plug. This will provide access to the CULTEC Chamber row below. From the surface, through this access, the sediment may be measured at this location. A stadia rod may be used to measure the depth of sediment if any in this row. If the depth of sediment is in excess of 3 inches (76 mm), then this row should be cleaned with high pressure water through a culvert cleaning nozzle. This would be carried out through an upstream manhole or through the CULTEC StormFilter Unit (or other pre- treatment device). CCTV Inspection of this row can be deployed through this access port to deter mine If any sediment has accumulated In the Inlet row. B. If the CULTEC bed Is not equipped with an inspection port, then access to the inlet row will be through an upstream manhole or the CULTEC StormFllter. 1. Manhole Access This inspection should only be carried out by persons trained In confined space entry and sewer Inspection services. After the manhole cover has been removed a gas detector must be lowered Into the manhole to ensure that there are not high concentrations of toxic gases present. The Inspector should be lowered into the manhole with the proper safety equipment as per OSHA requirements. The inspector may be able to observe sediment from this location. If this Is not possible, the inspector will need to deploy a CCTV robot to permit viewing of the sediment. For more informations, contact CULTEC at (203) 775-4416 or visit www.cultec.com. ©CULTEC CLT057 11-23 OPERATIONS r MAINTENANCE CULTEC 2. StormFilter Access Remove the manhole cover to allow access to the unit. Typically a 30-inch (750 mm) pipe is used as a riser from the StormFilter to the surface. As in the case with manhole access, this access point requires a technician trained in confined space entry with proper gas detection equipment. This individual must be equipped with the proper safety equipment for entry into the StormFilter. The technician will be lowered onto the StormFilter unit. The hatch on the unit must be removed. Inside the unit are two filters which may be removed according to StormFilter maintenance guidelines. Once these filters are removed the Inspector can enter the StormFilter unit to launch the CCTV camera robot. C. The inlet row of the CULTEC system is placed on a polyethylene liner to prevent scouring of the washed stone beneath this row. This also facilitates the flushing of this row with high pressure water through a culvert cleaning nozzle. The nozzle Is deployed through a manhole or the StormFllter and extended to the end of the row. The water is turned on and the Inlet row is back-flushed Into the manhole or StormFllter. This water is to be removed from the manhole or StormFllter using a vacuum truck. III. Maintenance Guidelines The following guidelines shall be adhered to for the operation and maintenance of the CULTEC stormwater management system: A. The owner shall keep a maintenance log which shall include details of any events which would have an effect on the system's operational capacity. B. The operation and maintenance procedure shall be reviewed periodically and changed to meet site conditions. C. Maintenance of the stormwater management system shall be performed by qualified workers and shall follow applicable occupational health and safety requirements. D. Debris removed from the stormwater management system shall be disposed of In accordance with applicable laws and regulations. IV. Suggested Maintenance Schedules A. Minor Maintenance The following suggested schedule shall be followed for routine maintenance during the regular operation of the stormwater system: Monthly in first year Check inlets and outlets for clogging and remove any debris, as required. Spring and Fall Check Inlets and outlets for clogging and remove any debris, as required. One year after commissioning and every third Check Inlets and outlets for clogging and remove any debris, as required. year following B. Major Maintenance The following suggested maintenance schedule shall be followed to maintain the performance of the CULTEC stormwater management chambers. Additional work may be necessary due to Insufficient performance and other Issues that might be found during the Inspection of the stormwater management chambers. (See table on next page) i 9 For more information, contact CULTEC at (203) 775-4416 or visit www.cultec.com. q CULTEC CLT057 11-23 I CULTEC • CHAMBERSC ' CULTEC I E p Inlets and Outlets Every 3 years Obtain documentation that the inlets,outlets and vents have been cleaned and will function as intended. Spring and Fall Check inlet and outlets for clogging and remove any debris as re- quired. CULTEC Stormwater 2 years after commis- • Inspect the interior of the stormwater management chambers Chambers sioning through inspection port for deficiencies using CCTV or comparable technique. • Obtain documentation that the stormwater management chambers and feed connectors will function as anticipated. 9 years after commis- • Clean stormwater management chambers and feed connectors of sioning every 9 years any debris. following • Inspect the Interior of the stormwater management structures for deficiencies using CCTV or comparable technique. • Obtain documentation that the stormwater management chambers and feed connectors have been cleaned and will function as intend- ed. 45 years after com- 0 Clean stormwater management chambers and feed connectors of missioning any debris. • Determine the remaining life expectancy of the stormwater man- agement chambers and recommended schedule and actions to reha- bilitate the stormwater management chambers as required. • Inspect the interior of the stormwater management chambers for deficiencies using CCTV or comparable technique. • Replace or restore the stormwater management chambers in accor- dance with the schedule determined at the 45-year Inspection. • Attain the appropriate approvals as required. • Establish a new operation and maintenance schedule. Surrounding Site Monthly In 161year Check for depressions In areas over and surrounding the stormwater management system. Spring and Fall • Check for depressions in areas over and surrounding the stormwater management system. Yearly • Confirm that no unauthorized modifications have been performed to the site. For additional Information concerning the maintenance of CULTEC Subsurface Stormwater Management Chambers, please contact CULTEC at 1-800-428-5832. For more information, contact CULTEC at (203) 775w4416 or visit www.cultec.com. ©CULTEC CLT057 11-23 II OPERATIONS AND MAINTENANCE I CULTEC WQMPi Operation & Maintenance (O&M ) Plan Project Name: Prepared for: Project Name: Address: City, State Zip: Prepared on.- Date: For more information, contact CULTEC at(203) 775-4416 or visit www.cuitec.com. p CULTEC CLT057 11-23 Ei I STORMWATER i • CULTEC i 1 This O&M Plan describes the designated responsible party for implementation of this WQMP, including: operation and maintenance of all the structural BMP(s), conducting the training/educational program and duties, and any other necessary activities. The O&M Plan includes detailed inspection and maintenance requirements for all struc- tural BMPs, including copies of any maintenance contract agreements, manufacturer's maintenance requirements, permits, etc, 8.1.1 Project Information Project name Address City, State Zip Site size List of structural BMPs, number of each Other notes 8.1.2 Responsible Party The responsible party for implementation of this WQMP is: Name of Person or HOA Property Manager Address City, State Zip Phone number 24-Hour Emergency Contact number Email 8.1.3 Record Keeping Parties responsible for the O&M plan shall retain records for at least S years. All training and educational activities and BMP operation and maintenance shall be documented to verify compli- ance with this O&M Plan. A sample Training Log and Inspection and Maintenance Log are Included in this docu- ment. 8.1.4 Electronic Data Submittal This document along with the Site Plan and Attachments shall be provided in PDF format. AutoCAD files and/or GIS coordinates of BMPs shall also be submitted to the City. more in �, n contact www.cultec.com. For m farmatia t CULTEC at (203) 7'75-4416 or visit c.com. ©CULTEC CLT057 1i-23 1 OPERATIONS AND MAINTENANCE GUIDELINES CULFEC Appendix BMP SITE PLAN Site plan is preferred on minimum 11" by 17" colored sheets, as long as legible. mry.pFor more information, contact CULTEC at µ(203) 775-4416 or visit www.cultec.com, ©CULTEC CLT057 11-23 ■ ■ CHAMBERS CULTEC BMP OPERATION & MAINTENANCE LOG Project Name: Today's Date: Name of Person Performing Activity (Printed): Signature: mrrm r.urxvnw.msamu:rnn¢evrxndnn�nnnww—�,'tr.�u'xnsro �mru nw�.rw�rxwrrmmurcux�xmrvmmrmmmni�wmoomniacwirirw.wn'yi�la�a � anwmoirrnm�mrnmia�.imama¢rmmmrvmuimrrcaa�.rmmmnuwttwrwaFa�wx�frtvm+rm�mwrmmeuiem� i,nuomeivcm�m..mmueniwnw.wam�mramurirvmmavu�mxumurtivxrnrvrixmmmrry ma„ a.-nvxnrrrnrr svuwnweimm�.'rer-s For more information, contact CULTEC at(203) 775-4416 or visit www.cultec.com. ©CULTEC CLT057 11-23 i OPERATIONSAND ► ► GUIDELINES 1 Minor Maintenance Monthly in first year Check inlets and outlets for clogging and remove any debris, as required. Notes ` . .. ❑ Month 1 Date: ❑ Month 2 Date: ❑ Month 3 Date: ❑ Month 4 Date ❑Month 5 Date: ❑ Month 6 Date: a Month 7 Date: ❑ Month 8 Date: ❑ Month 9 Date: ❑ Month 10 Date: ❑ Month 11 Date: ❑ Month 12 Date: Spring and Fall Check inlets and outlets for clogging and remove any debris, as required. Notes ❑ Spring Date: ❑ Fall Date. n Spring Date: T1 Fall Date: a Spring Date: ❑ Fall Date: •Spring Date: ❑ Fall Date: ❑Spring Date: ❑ Fall Date: •Spring Date: ❑ Fall Date: One year after commissioning Check inlets and outlets for clogging and remove any debris,as required. and every third year following Notes ❑Year i Date: ❑Year 4 Date: a Year 7 Date: ❑Year 10 Date: ❑Year 13 Date: ❑Year 16 Date: ❑Year 19 Date: n Year 22 Date: 0 .For more information, contact CIiLTIEC at(203)�775-4416 or visit www.cultec.com „ � � ,rvr,m ©CULTEC CLT057 11-23 i CULTEC N r y r CHAMBERS jI CULTEC Major Maintenance IRON Every 3 years Obtain documentation that the inlets, outlets and vents have been cleaned and will function as intended. Notes a Year 1 Date: ❑Year 4 Date: ❑Year 7 Date: n Year 10 Date: ❑Year 13 Date: n Year 16 Date: y ❑Year 19 Date: ©Year 22 Date: O 13 Spring and Fall Check inlet and outlets for clogging and remove any debris, as required. 44 Notes C n Spring Date: N ❑Fall Date: ❑Spring Date: ❑ Fall Date: ❑Spring Date: n Fall Date: a Spring Date: ❑ Fall Date: u Spring Date: a Fall Date: a Spring Date: a Fall Date: 2 years after commissioning ❑Inspect the Interior of the stormwater management chambers through inspection port for deficiencies using s1 CCTV or comparable technique. M ❑Obtain documentation that the stormwater manage- .0 ment chambers and feed connectors will function as U anticipated, x. Gl Notes 3 n Year 2 Date: E 0 U iu J U For more information, contact CULTEC at(203) 775-4416 or visit www.cultec.com. O CULTEC CLT057 11.-23 I OPERATIONS AND M + + I I Major Maintenance t 9 years after commissioning n Clean stormwater management chambers and feed every 9 years following connectors of any debris. ❑Inspect the Interior of the stormwater management structures for deficiencies using CCTV or comparable technique. ❑obtain documentation that the stormwater man- agement chambers and feed connectors have been cleaned and will function as intended. Notes ❑Year 9 Date: Ei Year 18 Date: ❑Year 27 Date: W ❑Year 36 Date: L. M45 years after commissioning a Clean stormwater management chambers and feed .0 connectors of any debris. U ❑Determine the remaining life expectancy of the +�+ stormwater management chambers and recommended schedule and actions to rehabilitate the stormwater management chambers as required, p o Inspect the interior of the stormwater management chambers for deficiencies using CCTV or comparable U technique. LU D Replace or restore the stormwater management chambers in accordance with the schedule determined U at the 45-year Inspection. ❑Attain the appropriate approvals as required. ❑ Establish a new operation and maintenance sched- ule, Notes o Year 45 Date: 1 For more Information,contact� C at CULTE (203) 775-4416 or visit www.cultee.com. ©CULTEC CLT057 11-23 i i CULTEC . r A r CHAMBERS CULTEc Major Maintenance R Monthly in 151 year ❑Check for depressions in areas over and surrounding the stormwater management system. Notes ❑Month 1 Date: ❑ Month 2 Date: ❑ Month 3 Date: ❑ Month 4 Date: ❑ Month 5 Date: ❑ Month 6 Date: ❑ Month 7 Date: ❑ Month 8 Date: ❑ Month 9 Date: ❑ Month 10 Date: ❑ Month 11 Date: ❑ Month 12 Date: Spring and Fall ❑ Check for depressions in areas over and surrounding the stormwater management system. iU Notes ++ ❑ Spring Date: i71 ❑ Fall Date: C ❑ Spring Date: O ❑ Fall Date: L ❑Spring Date: ❑ Fall Date: ❑Spring Date: ❑ Fall Date: ❑Spring Date: ❑ Fall Date: ❑Spring Date: ❑ Fall Date: Yearly ❑Confirm that no unauthorized modifications have been performed to the site. Notes ❑Year 1 Date: ❑Year 2 Date: •Year 3 Date: ❑Year 4 Date: ❑Year 5 Date: ❑Year 6 Date: ❑Year 7 Date: 13 For more information, contact CULTEC at (203) 775-4416 or visit www.cultec.com. cultec.com. ©CULTEC CLT057 11-23 � � � � � � � � � CULTEC 878 Federal Road ° RO. 8oxZ8D ° Brookfield, CTO68O4USA � P. (203) 775'4418 ^ TbU Free- 1(800) 4'CU[TEC ° www.cu|tno.corn � CULTGCRETENTION DETENTION INFILTRATION WATER QUALITY | |