Loading...
HomeMy WebLinkAbout1984-10-02 1984 Willows Prof Park - South Complex Dept Review Correspondence 09/17/84 MUM HUI .-_.T._O-W N OF NORTH A.N_D O V-R-R--- __._.. MASSACIaUSETTS r1oRY1, � y f i � ss/lCHUS October 2, 1984 Mr. Charles Foster Building Department 120 Main Street North Andover, MA. 01845 RE: Willows South Complex - Site Plan Review Dear Charlie: The purpose of this letter is to inform you of the Plann1ng.3Qard's review of the above referenced site plan. In general the board did not have any problems with granting the go ahead for issuing building permits. However, we requested a few days to review the drainage calculations submitted last night at the. meeting. Therefore, we ask you to hold off on issuing occupancy permits until that time (which I am sure Mr. Grasso will not be' needing them for some time) . l will get back to you on this matter by weeks end. , Sincerely, Karen H, Pomroy-Nelson kp cc: Mr. V. Gkasso pyC1i��"F-p CJ��.yo r5 410� _ _ °_ _ !� W. d F DEPARTMENT CENTRAL FIRE HEADQUARTERS 124 Main Street North Andover, Mass, 01845 Tel. 666-3812 September 17, 1984 To : No . Andover Planning Board From: Fire Chief Dolan Re : Willows Professional Park South Complex T have reviewed the site plan for the proposed South Complex at the Willows industrial Park and have the following comments : 1 . The developer should contact the Fire Chief prior to developing sprinkler design plans . Buildings must comply with Mass . General Law Chapter 148 Sec. 26G Installation of Automatic. 2 . The 2" water line shown on the plan would be inadequate to supply water for fire protection needs . 8 . An access to the "courtyard", created by the four buildings, for Fire Department access should be created and maintained in a serviceable condition throughout the year . William V. Dolan, Chief No . Andover Fire Dept . I CENTRAL FIRE HEADQUARTERS U" 124 Main Street North Aiiclover, Mass. 01845 I.tl,l Vy3)OL.F�IV {4 17) tst3ii-3612 r r).1;1,irt,?w1d April 30, 1986 Mr. John Grasso Grasso Construction 865 Turnpike Street No. Andover, Mass. 01845 Dear Mr. Grasso, I am writing concerning the Willow Professional Park South Complex. During the construction of these buildings, the fire hydrant on the corner of Flagship Drive and Willow Street was disabled by an accident. In addition, a hydrant was to be placed within the complex for fire protection. At the present time, these hydrants have not been replaced. I have discussed this with Mr. Joseph Borgesi. and Mr. Hmurciak of the Public Works Department, who informed me that they had discussed this matter with you and that you were to replace these hydrants . I also have discussed this matter with Mr. Charles Faster, the Building Inspector, and have informed him that without these hydrants there is no water supply for fire protection. Unless this situation is corrected, it would be unwise of the town to issue occupancy permits for these buildings. Please contact me if you have any questions concerning this matter , Respectfully, William V. Dolan, Fire Chief cc: Karen Nelson Charles Foster Joseph Borgesi "'iMO I-' DEIEC"I URS SAVC UVLS"