HomeMy WebLinkAbout260402_3rd_SWPeerReview_Zero_Prescott - Horsley Witten - Consultant Review - 0 Prescott Street 4/2/2026 April 2, 2026 Ms. Jean Enright, Planning Director Planning Department Town of North Andover 120 Main Street North Andover, Massachusetts 01845 Re: ThirdTechnical Peer Review–Comprehensive Permit Application Zero PrescottStreet North Andover, Massachusetts Dear Ms. Enright and Board Members: The Horsley Witten Group, Inc. (HW) is pleased to provide the North Andover ZoningBoardof Appeals (ZBA) with this report summarizing ourthirdreview of theComprehensivePermit Applicationfor Zero PrescottStreet.The plans and calculations were prepared by Civil Design Group, LLC, dated October 2025, revised March2026, on behalf of RCG,LLC (Applicant).The project proposes to replace the existing garage at 10 Prescott Street with two new buildings housing 296 rental units and a multi-story parking garage on a 6.13-acre parcel.The Applicant is proposing catch basins, hydrodynamic separators, and a subsurface infiltration system to capture and mitigate the stormwater from the proposedincrease inimpervious areas. The project is located within the Downtown Overlay Historic Mill Area:Subdistrict A with underlying zoning districts Industrial S (IS)and Residential 4(R4).The proposed improvements do not appear to be withinthe 100-foot buffer zone of a wetland resource area therefore arenot within the jurisdiction of the North Andover Conservation Commission. The following additional documents and plans were receivedby HWin response to our second review letter dated March 3, 2026: Response to Comments letter, issued to Jean Enright, prepared by Civil Design Group, LLC, dated April 1, 2026 (4 pages); Grading & Drainage Plan, Avalon North Andover Mills, prepared by Civil Design Group, LLC,revised throughJuly 28, 2021(2Sheets); Comprehensive Permit, Site Development Plans, for Zero Prescott, Residential Development,0 Prescott Street, North Andover, MA,prepared byCivil Design Group, LLC,dated October 21, 2025, revised March 30, 2026 (2sheets), which includes: o Grading &Drainage Plan5 o Photometric CalculationL3.0 horsleywitten.com Town of North Andover April 2,2026 Page 2of 15 Stormwater Management Design Peer Review HW offers the following comments concerning the stormwater management design as per the Massachusetts Stormwater Handbook (MSH) dated February 2008, and the North Andover Chapter 165 Stormwater Management and Erosion Control Bylaw (Bylaw), and the Chapter 250 Stormwater Management and Erosion Control regulations (Stormwater Regulations) adopted June 21, 2022. The following comments correlate to our secondpeer review letter dated March 3, 2026. Follow up comments are provided in boldunderlinedfontwhere applicable. 1.Standard 1: No new stormwater conveyances (e.g., outfalls) may discharge untreated stormwater directly to or cause erosion in wetlands or waters of the Commonwealth. a.The Applicant has analyzed the pre-and post-development stormwater runoff to four pointsof analysis(POA). (1)POA-1 is an existing 18-inch culvert that carries stormwater from the existing garage roof and a portion of the existing parking lot (EX-1) under the western driveway and discharges into the existing municipal drainage system in High Street (POA-2). The culvert will remain under proposed conditions.The proposed catchment area (PR-1) is reduced significantly from the existing catchment area because it does not include the proposed building. March 3, 2026: No further action is requested. (2)POA-2 is the existing municipal drainage system in High Street. The stormwater from a large portion of the existing and proposed site is directed into the municipal system(EX-2).Under proposed conditions a portion of the development is directed towards a subsurface chamber system (SIS-1) and a portion of the building is piped directly towards the closed drainage system.The catchment areas directed towards POA-2 include most of the proposed development.HW notesthat the stormwater from a portion of the southern parking lot within EX-2 and PR-2 appears to flow offsite via the center driveway. It is not obvious how this runoff is directed into the drainage system defined by POA-2. March 3,2026: The Applicant has clarifiedthat the proposed contourswill redirect flow in the drainage system defined by POA-2.The runoff from the area will flow down the center driveway and then in the westerlydirection towardsHigh Street. No further action is requested. (3)POA-3 is the portion of the project area onthe east side of the site that flows towards the east and the adjacent Meadow View Condominium property(EX-3). Under proposed conditionsthis area is reduced slightly(PR-3). March 3, 2026: No further action is requested. (4)POA-4 is the portion of the project area that flows southeast onto the southern parking lot(EX-4).Under proposed conditions this catchment area is reduced slightly (PR-4). HW notes that the narrative and Figure 3 describeEX-4as consisting of 0.24 acres. However, it is approximately 0.39 acres as listedin the HydroCAD model.HW further notes that it appears that the western side of EX-4 H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 3of 15 and PR-4 flows towards an 18-inch corrugated metal pipe (CMP)that is directed into EX-1 and PR-1. HW recommends that the Applicant revisit the catchment areas to POA-4under existing and proposed conditions. March 3, 2026: The Applicant has revised the EX-4 and PR-4 subcatchment areas. No further action is requested. b.Theclosest resource area is Mill Pond to the southeast of the project area. The proposed development is greater than 100 feet from this pond. HW recommends that the Applicant clarify where the closed drainage system modeled as POA-2 discharges to. HW further recommends that the Applicant confirm that the final discharge point is not currently causing erosion in wetlands or waters of the Commonwealth. March 3,2026: The Applicant has clarifiedthat the closed drainage system modeled as POA-2 travels south down High Street and connects into the large culvert that conveys runoff to West Mill Ponds. No further action is requested. 2.Standard 2: Stormwater management systems shall be designed so that post- development peak discharge rates do not exceed pre-development peak discharge rates. a.The Applicant has included a Peak Flow Rate ComparisonTable in Section 7.0of the Stormwater Management Narrative. ThePost-developmentpeak flows do not exceed the pre-developmentvalues. HW recommends that the Applicant update the Table,if applicable,after responding to the other comments in this letter. March 3,2026: The Applicant has updated the Tableas suggested. No further action is requested. b.Per §250-22 B. (5)(b) and §250-23 A. (1) of the North Andover Stormwater Regulations, Low-Impact development (LID) site planning and design strategies must be implemented to the maximum extent feasible. The Applicant has incorporated onesubsurface infiltration chambersystemas an LID technique. HW recommends that the Applicant document other LID options it considered withinthe Project Area. March 3,2026: The Applicant has stated that theLID measures utilized include reusing the existing swale to capture and convey runoff and matchingthe existing impervious area in the proposed condition.The Applicant is also maintaining most of the wooded area on the north side of the building. c.In accordance with §250-22 B. (5)(c),HW recommends that the Applicant identify the watershed basin and the downgradient water body that stormwater from the project site discharges into. March 3,2026: The Applicant has stated that the watershed basin associated with this site is the Merrimack River. Runoff from this site drains in a westerly direction to Osgood Pond behind the West Mill Campus. Runoffthen continues to Sutton Pond and eventually into the Merrimack River. No further action is requested. d.In accordance with §250-22 C. (4)(c),HW recommends that the Applicant delineate any existing or proposed slopes between 15% and 25% and over 25%. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 4of 15 March 3, 2026: The Applicant has stated that the existing and proposed developed portions of the site are less than 5% and the sloped area to the rear is less than 10%. The 3:1 side slope of the existing swale willremain. No further action is requested. e.In accordance with §250-22 C. (4)(g),HW recommends that the Applicant call out any significant or unique trees or tree clusters. March 3, 2026: The Applicant has requested a waiver from the local Stormwater Bylaw. During the ZBA hearing on February 25, 2026, the Applicant stated that it will be removing approximately 0.5 acres of trees.The HydroCAD model indicates that there are approximately 1.22 acres of woods under pre-development conditions and 1.85 acres of grass cover. Under post-development conditions the Applicant has modeled 2.34 acres of grass and 0.70 acres of woods. HW defers the granting of this waiver to the ZBA. April 2, 2026: Waiver requested. f.In accordance with §250-22 C. (5)(b),HW recommends that the Applicant includes profiles of the drainage truck lines. March 3, 2026: The Applicant has requested a waiver from the local Stormwater Bylaw. The Applicant has not included profiles of the drainage truck lines,butit hasreviewed thepotential conflictswith other utilities. HW defers the granting of this waiver to the ZBA. April 2, 2026: Waiver requested. g.In accordance with §250-22 D. (1 and 4),the calculations provided should include peak flow rates and volumes. HW has confirmed that the peak volumes have been reduced over existing conditions. However, werecommend that the Applicant includesa table with the pre-and post-peak volumes of stormwater runofffor documentation purposes. March 3, 2026: The Applicant has added a volume mitigation table to the Stormwater Reportas suggested. The peak stormwater volume will decrease at each point of analysis. No further action is requested. h.HW notes that the Applicant has used a direct entry of 6 minutes for the times of concentration (Tc) values for all Pre-development and Post-development catchment areas.HW recommends that the Applicant revisit the Tc values for catchment areas EX- 2 and PR-2in accordance with §250-23 E. (18)and provide the flow paths on Figures 3 and 4. March 3, 2026: The Applicant has revised the Tc values in the HydroCAD model andadded the flow pathtothe planas suggested. No further action is requested. i.In accordance with §250-23 E. (19),the Applicant must utilize the 24-hour rainfall data taken from National Oceanic and Atmospheric Administration (NOAA) Atlas 14 for the rainfall precipitation depths. The Applicanthas used theNortheast Regional Climate Center(NRCC)values,which are similar. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 5of 15 YearNRCCValuesNOAA Atlas 14 Values 2-year3.15 inches3.15 inches 10-year4.83 inches5.00 inches 25-year6.16 inches6.15 inches 100-year8.94 inches7.93 inches March 3, 2026: No further action is requested. j.In accordance with §250-23 E. (22),HW recommends that the Applicant providespipe sizing calculationsusing Mannings Equation and confirmsthat the drainage pipes can accommodate a 25-year storm event. March 3, 2026: The Applicant has requested a waiver from the local Stormwater Bylaw. The Applicant has stated that the drainage connection in High Street consistsof 12-inchpipesand increasing the pipe sizes based on onsite pipe capacity would be ineffective. The Applicant has stated that itwill continue its conversation with the Department of Public Works(DPW) regarding the regional flood management study and to explore alternatives to maximize runoff conveyance through the campus. HW recommends that the ZBA request updates on the conversations between the Applicant and the DPW. April 2, 2026: The Applicant has stated that it has been coordinating with the North Andover DPW. It has proposed an alternative drainage plan that includes the installation of an 18-inch pipe crossing High Street at the end of Prescott Street from proposed DMH-6. The 18-inch pipe will discharge stormwater via an existing 18-inch drain line that increases to a 36-inch drain lineat DMH-3D on the AVB West Mill property andthen crosses through the AVB West Mill property.The 18-inch pipe directed west from DMH-6is 1.65 feet lower than the 12-inch pipe directed south, therefore able to redirectmost of the stormwater from the proposed development.An 18-inch pipe with a slope of 3%can manage approximately 18 cfs.It appears that the alternative design will redirect the proposed building and patio area from storm events up to and including a 25-year event.HW agrees that the alternative design will reduce the peak flows and volumesdirected towards the High Street municipal system. HW recommends that the ZBA confirm that the DPW is in agreement with the alternative design plan. k.HW notes that the existing pipe configuration at the intersection with High Street and the driveway access drive is confusing. HW requests that the Applicant clarify how the various catch basins and manholes are connected. Furthermore, the Applicant is connecting anew18-inch drainpipeto the existing drainage system at an existing catch basin, it is not clear the size of the existing drainpipes and if the existing system can manage the proposed runoff.HW recommends that the Applicant providesadditional documentation on the existing drainpipes.If feasible,HW recommends that the Applicant tie into the existing system at a manhole. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 6of 15 March 3, 2026: The Applicant has reducedthe proposed 18-inchpipe to a 12-inch pipe. Since the watershed to the swale has been reduced by 2 acres, the existing 18-inchpipe is oversized as compared to the contributing flow. The discharge to the municipal stormwater system should be part of the ongoing discussions with the DPW. April 2, 2026: The Applicant has been in discussions with the DPW. No further action is requested. l.In accordance with §250-23 E. (30),all drainpipes are to be reinforced concrete pipe (RCP)with a minimum diameter of 12 inches.HW notes that the Applicant is proposing high-density polyethylene (HDPE) pipes. March 3, 2026: The Applicant has requested a waiver from the local Stormwater Bylaw. HW notes that HDPE pipes are frequently used in Massachusetts municipalities.HW defers the granting of this waiver to the ZBA. April 2, 2026: Waiver requested. 3.Standard 3 requires that the annual recharge from post-development shall approximate annual recharge from pre-development conditions. a.The Applicant has provided a Natural Resources Conservation Service (NRCS) Soils map which documented that the soils on site are classified as Urban Land and Woodbridge. The Applicant conductedsoil test pits within the footprint of the infiltration system to confirm the Estimated Seasonal High Ground Water (ESHGW)and the exfiltration rate used in the HydroCAD model.The soil in the test holes was listed as sand and the Applicant has used an exfiltration rate of 2.41 inches per hour (iph) in the HydroCAD model. HW finds the exfiltration rate to be reasonable. March 3, 2026: No further action is requested. b.HW notes that bottom of the infiltration system is set at elevation 95.0 and the ESHGW in test pit T-1indicates thatESHGW is at approximately elevation 91.0 providing the required four feet of separation.No further action is requested. March 3, 2026: No further action is requested. c.The Applicant has provided drawdown calculations in Section 9.0 of the Stormwater Management Narrative.HW notes that the Applicant has stated that the increase in impervious area is approximately 0.03+acres. The HydroCAD calculations indicate the increase is 0.041 acres. HW could notconfirm the volume of stormwater being retained in the subsurface infiltration system with the information provided. HW recommends that the Applicant provide the stage storage area printout from the HydroCAD model for confirmation. March 3, 2026: The Applicant has provided the subsurface infiltration system stage storage table. There is a 0.04 acre increase in impervious area, requiring 50 CF of storage, the Applicant has demonstrated that approximately 588 CF of storage is provided,exceedingthe requirement. No further action is requested. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 7of 15 4.Standard 4 requires that the stormwater system be designed to remove 80% Total Suspended Solids (TSS) and to treat 1-inch of volume from the impervious area for water quality. a.The Applicant has provided waterquality calculationsto confirm that the treatment trains exceed the 80% TSS removal requirement per the MSHand §250-23 C. (1) of the North Andover Stormwater Regulations.HW recommends that the Applicant provides documentation confirming the TSS removal provided by the proposed proprietary devices.HW notes that the Applicant has provided a detail of a Hydroworks HS4. However, we could not locate where this device is proposed. March 3, 2026: The Applicant has clarified the location of the water qualityunitin front of the garage portion of the buildingat drain manhole (DMH)9and provided documentation confirming the TSS removal provided. HW recommends that a second water quality unit be provided for the closed drainage system on the east side of the parcel,possibly at DMH2. April 2, 2026: The Applicant has provided a water quality unit to manage the driveway runoff collected by the trench drain. No further action is requested. b.In accordance with §250-23 B. (1)(b),HW recommends that the Applicant provides calculations to verify that the proposed stormwater chamber systemscan captureand retainthe volume of runoff generated by 1-inch times the increase in impervious area of the site.HW could notconfirm the volume of stormwater retained with the documentation provided. March 3, 2026: The proposedinfiltration system will need to capture and retaina minimum of149 CF of stormwater runoff generated from the 0.041 acres of increased impervious area. The infiltration system is designed to retain588 CF of stormwater runoff.No further action is requested. c.HW recommends that the Applicant address the Phosphorous removal calculations in accordance with §250-23 C. (1) of the North Andover Stormwater Regulations. March 3, 2026: The proposed infiltration system is designed to capture the 1-inch volume from the proposed increase in impervious area. No further action is requested. 5.Standard 5 is related to projects with a Land Use of Higher Potential Pollutant Loads (LUHPPL). a.Theproposed projectis not considered a LUHPPL. Standard 5 is not applicable. March 3, 2026: No further action is requested. 6.Standard 6 is related to projects with stormwater discharging into a critical area, a Zone II, or an Interim Wellhead Protection Area of a public water supply. a.The proposed development is not discharging near or into a critical area, Zone II or an IWPA area. Standard 6 is not applicable. March 3, 2026: No further action is requested. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 8of 15 7.Standard 7 is related to projects considered Redevelopment.A redevelopment project is required to meet the following Stormwater Management Standards only to the maximum extent practicable: Standard 2, Standard 3, and the pretreatment and structural best management practice requirements of Standards 4, 5, and 6. Existing stormwater discharges shall comply with Standard 1 only to the maximum extent practicable. A redevelopment project shall also comply with all other requirements of the Stormwater Management Standards and improve existing conditions. a.This project is considered a mix of new development and redevelopment. The Applicant is required to comply with the new development standards for the increase in impervious areas as described under Standards 3 and 4 above. The Applicant is required to meet the standards for the remainder of the site to the maximum extent practicable and improve existing conditions.HW recommends that the Applicant describe how it is improving existing conditions. March 3, 2026: The proposed development will improveexisting conditions by reducing the impervious areaof the top-level parking deck and providing water quality.The open garage parking area has been reduced from 2 acres to 0.60 acres. The infiltration system captures the 1-inch volume from the increased impervious area.The proposed stormwater system will include measures to improve water quality prior to discharging from the site. 8.Standard 8 requires a plan to control construction related impacts including erosion, sedimentation, or other pollutant sources. a.The Applicant has provided a Site Demolition & Erosion Control Plan. HW recommends that the Applicant clarify the type of erosion control barrier proposed. The plans call for a wattle, and the detail references a silt sock with a silt fence. It is HW’s opinion that the silt sock with a silt fenceis the preferred method. March 3, 2026: The Applicant has updated the planas suggested, a 12-inchsilt sock with a silt fence is proposed. No further action is requested. b.HW recommends that the Applicant includesa detail of the construction fence that is proposed on the northern limit of work. March 3, 2026: The Applicant has added a construction fence detailas suggested. No further action is requested. c.HW recommends that the Applicant includesinlet protectionin allexisting catch basins within 100 feet ofthe construction entrance. March 3, 2026: The Applicant has added a noteto include inlet protection in all existing catch basins within 100 feet of the construction entrance.No further action is requested. d.The limit of disturbance will be greater than 1 acre therefore aConstruction General Permit (CGP) and a Stormwater Pollution Prevention Plan (SWPPP) is required by EPA. TheZBAmay choose to require a final signed SWPPP a minimum of 14 days prior to land disturbance. March 3, 2026: Suggested condition of approval. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 9of 15 9.Standard 9 requires a Long-Term Operation and Maintenance (O & M) Plan to be provided. a.The Applicant has provided anOperation and Maintenance Planwithin the Stormwater Management Report. The plan liststhe property ownerand site engineer. The ZBAmay choose to require receipt of a signed O&M Plan prior to occupancy as a condition of approval. March 3, 2026: The Owner’s signature has been added to the O&M plan. The ZBA may still choose to require receipt of the final O&M Plan as a condition of approval. b.The O&M Plan indicates that solid waste materials will be stored in dumpsters provided on site. It is not obvious onthe Site Plan where the dumpsters are located. March 3, 2026: The Applicant has stated that the dumpsters will be located inside the garage building. The ZBA may choose to require this as a condition of approval. c.HW notes that the O&M Plan states that Pet Waste is not anticipated based on the proposed use of the site. HW recommends that the Applicant clarify if dogs will be prohibited from the residential units. March 3, 2026: The Applicant has stated pets are not prohibited and that pet waste baskets are to be provided. The Operation and Maintenance Plan has been updated. The ZBA may choose to require this as a condition of approval. d.Section 3 of the O&M Plan references yard drains. However,it is not clear how these should be maintained. March 3, 2026: The maintenance of the yard drains has been added to the O&M Plan. No further action is requested. e.The Applicant has noted that the Hydrodynamic Separator should be cleaned per the manufacturer’s recommendation. HW recommends that the Applicant includes the manufacturer’s recommendations with the O&M Plan. March 3, 2026: The Applicant has added the manufacture’srecommendations to the O&M plan. No further action is requested. f.The Applicant has included a Quarterly Stormwater Inspection Report. HW recommends that the Applicant include the catch basins,the yard drains, and the deep sump drain manholesas part of this Report. March 3, 2026: The Applicant has updatedthe Quarterly StormwaterInspection Report as suggested. No further action is requested. g.HW recommends that the Applicant includesthesnow storage locations on the Figure-1 BMP Location Plan. March 3, 2026: The Applicant has included snow storage locations on Figure-1. HW recommends that the Applicant include the snow storage location for the roof deck of the proposed garage. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 10of 15 April 2, 2026: The Applicant has noted that the snow on the roof deck will be removed by hand and allowed to melt. HW assumes that there will be no stockpiling of snow on the garage roof deck. h.HW recommends that the Applicant providesthe O&M Plan as a standalone document that can be provided to theproperty owner(s). March 3, 2026: The O&M Plan is a standalone document and can be extracted from the Stormwater Report as needed. No further action is requested. 10.Standard 10 requires an Illicit Discharge Compliance Statement be provided. a.The Applicant has provided a signed Illicit Discharge Compliance statement.No further action is requested. March 3, 2026: No further action is requested. Site Plan Review: A multifamily dwelling unit having seven or more units is allowed by Special Permit by the Planning Board in Subdistrict A.The Comprehensive Permit application proposes two new buildings housing 296 rental units connected by a multi-story parking garage.HW has the following comments regarding the site plans. 11.Parking: a.There are 100 surface level parking spaces,in the south side yardof the proposed building. The typical size is 9-feet wide by 18-feet long with a 25-foot-wide aisle. These spaces are in the same location as the existing parking spaces. Two of the proposed surface spaces will be striped as van accessible. March 3, 2026: No further action is requested. b.There are 77 parking spaces on the first floor of the garage, 10 are marked for electric vehicles (EV), and three are marked as accessible. HW notes that the Applicant has listed 79 spaces, we recommend that the Applicant clarify the number of spaces provided on the first floor. March 3, 2026: The Applicant has clarified that there is a total of 80 parking spaces on the first floor, 41 spaces on Level 1 and 39 spaces on Level 1.5.Nine spaces are designated for electric vehicles (EV), and three are designated as accessible parking spaces, including one van-accessible space. No further action is requested. c.There are 80 parking spaces on the second, third, fourth and fifth floors of the garage, 22 on each floor are marked for EV for a total of 88 spaces on the four floors, and two spaces are marked as accessible. The Applicant has noted on the Site Plan,Sheet 4, that 9 accessible parking spaces are provided. HW notes that per 521 CMR 23.2.1,497 spaces require a minimum of nineaccessible spaces. We only counted sevenand recommend that the Applicant revisit the number of spaces marked as accessible. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 11of 15 March 3, 2026: The Applicant has updatedthe submission to depict seven accessible parking spaces in the garage, twoadditional accessible spaces are provided at surface level. There isa total of nine accessible parking spaces, two spaces are designated as van accessible. No further action is requested. d.The Applicant has proposed a total of 497 parking spaces, 7 of which are marked as accessible, and 98 are marked for electric vehicles (19.7%). HW agrees that thetotal number of spaces proposed complies with Section 195-8.4 of the North Andover Zoning Code. HW recommends that the Applicant confirm the sizes of the parking spaces and aisles inside the garage. March 3, 2026: The Applicant has updated the parking layout to include typical parking space and aisle dimensions in the garage. No further action is requested. 12.Grading: a.On the northwest corner of the garage there is a walkway that provides the pedestrian connection from the garage to Prescott Street. The proposed grading in this area directs the runoff from thelargearea on the north side of the site over this walkway and along the north side of the west wing. HW recommends that the Applicant review this corner and confirm that ponding and/or icing in this area will not be an issue. March 3, 2026: The walkway has been removed from the proposed project. No further action is requested. b.The Applicant appears to have graded the walkways to be ADA compliant. Note 5 of the Grading & Drainage Notes on Sheet 1 states the maximum slopes allowed. March 3, 2026: No further action is requested. 13.Retaining Walls: a.Proposed Retaining Wall #1 is approximately 164feet long and is located on the north side of the amenity space for Building 1.Sections of this wall are greater than 10 feet high and the wall will need to be designedby a structural engineer.HW recommends that the Applicant includesRetaining Wall #1 incross section C-C provided on Sheet A5.01. March 3, 2026: The Applicant has included Wall #1 in the sectionC-C as suggested. No further action is requested. b.Proposed Retaining Wall #2is approximately 114feetlong and is locatedon the northwest side of the proposed building parallel to Prescott Street. The wall appears to be less than 4 feet high. Because of the length of the wall,HW recommends that a structural engineer be involved in the final design.HW recommends that the Applicant include Wall #2 on cross section B-B provided on Sheet A5.00. March 3, 2026: The Applicant has included Wall #2 in the sectionB-B as suggested. No further action is requested. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 12of 15 c.Proposed Retaining Wall #3is approximately 45 feet long and is located on the north side of the proposed garage adjacent to the proposed walkway and approximately 5 feet from the property boundary with 39 Prescott Street.The wall appears to be only 2 feet high.HW recommends that the Applicant include Wall #3 on cross section F-F provided on Sheet A5.02. March 3, 2026: The Applicant has stated that Wall #3 has been removed from the project. No further action is requested. d.Proposed Retaining Wall #4 is approximately265 feet long and is located on the east side of the parcelapproximately 5 feet from the property line. Sections of the wall are between 6 and 10 feet high, though the portion of the wall that runs parallel tothe property line is less than 3 feet high. March 3, 2026: No further action is requested. e.Proposed Retaining Wall #5 is approximately 112 feet long and located to the east of Building 2, across the driveway from Wall #4. The entire wallappears to be only 1 foot high. March 3, 2026: No further action is requested. f.HW recommends that the Applicant confirmsour description of the walls and documents any modifications it makes. March 3, 2026: No further action is requested. 14.Building Setbacks: The Applicant has included a Zoning Information table on the Site Plan, Sheet 4. a.In accordance with Section 195-18.12 of the North Andover Zoning Code, an application for a proposed project located within Subdistrict A may either use the standards in the underlying zoning district in their entirety, or those standards contained within Part 2 in their entirety.The Applicant has listed the three zoning districts it resides in and the zoning waivers requested per district. As a Comprehensive Permit is not required to fully comply with the local zoning requirements the ZBA may choose to consider the intent of Subdistrict A: Historic Mill Area and whether the proposed project is inline with the originalintent. March 3, 2026: Suggested discussion by the ZBA. b.Building 1 is located 18.8 feet from the western property boundary along Prescott Street. This appears to be the closest front yard setback. The Applicant has listed the front yard setback as 20.2 feet and has requested a waiverfrom the 30-foot requirement in a Residential 4(R4)zoning district.HW recommendsthat the Applicant confirmsthe minimum provided front yard setback. March 3, 2026: The Applicant has stated that the property is bisected by both the R-4 and Industrial-S Districts on Prescott Street which serves as a front setback for the Property. The Zoning Information Table on the Site Plan has been updated, and the waiver list will also be updated. As discussed during the ZBA hearing, HW recommends that the waiver list includesthe specific sections that the Applicant is requesting a waiver for and not theblanket waiver requestcurrently provided. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 13of 15 April 2, 2026: HW suggests that a waiver list be provided that includes the specific sectionsof the bylaws that waivers are being requested for. c.Building 1 is located 16.5 from the southeast corner of 39 Prescott Street.A four-foot- high black metal picket fence is proposed along the property boundary. The existing East MillGarage is located approximately 45 feet from this same corner. This appears to be the closest point to a residential property.It would be beneficial for the Applicant to add the adjacent buildings including the residential garages to the plan set.The Applicant has requesteda waiver from the35-footside yard setbackrequired for anew building in Subdistrict A when the Subdistrict Aline abuts a residential zoning district located outside Subdistrict A.The Applicant is also requesting a waiver from the 30-foot front yardsetback required in a R4district. March 3, 2026: The Applicant has added a locus plan on Sheet 13 to depictthe adjacent buildings. Building 1 is very close to the garage of the abutter at 39 Prescott St. HW notes that the Applicant has proposed a 5-foot-high black picket fence with plantingsalong the property line. d.Building 2 is located 34.6 feet from the eastern property line adjacent to Meadow View Condominiumwhich is in a residential 5 zoning district.This areamay be defined as the rear yardrequiring 30 feet of setback from the R4 and the IS districtsand 35 feet from Subdistrict A. Or it may be considered a side yardrequiring a 35-foot setback for a new building in Subdistrict A when the Subdistrict A line abuts a residential zoning district located outside Subdistrict A. The Applicant has not requested a waiver from the rear yardsetback line but has requested a waiver from the sideyardsetback line. HW recommends that a determination be made regarding thearea between the building and theeastern property line. March 3, 2026: The Applicant has stated that the Building Commissioner has determined that the eastern property line is a rear yard setback requiringa 30-foot setback withinthe R-4 District and the Industrial-S District.A34-foot 6-inch setback has been proposed.A 35-foot setback is required for a new building in Subdistrict A, therefore a waiver may be necessary to allow the34-foot 6-inch setback within this district. e.Thehighest proposed building height is approximately 54 feet 7 inchesfeetfrom the average finish grade. The Applicant is requesting a waiver from the maximum height of 35 feet within an R4 district.The IS district and Subdistrict A appear to allow a maximum height of 55 feet by right. March 3, 2026: No further action is requested. f.The maximum lot coverage calculated by the Applicant is 34%. The maximum allowable lot coverage within the IS district is 35%. The Applicant has requesteda waiver. However,it is not apparent that one is needed. March 3, 2026: The Applicant intends to update the waiver list. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 14of 15 g.The Applicant is requesting a waiver from the Maximum Floor Area Ratio(FAR) and is proposing a FAR of 1.70:1. A ratio of 1:1 is allowed by right in Subdistrict A. A ratio of 0.5:1 is allowed by right in an IS district. A FARof up to 2:1 is allowed by Special Permit in Subdistrict A. March 3,2026: The Applicant has requested a waiverfrom the allowable FAR. 15.Design Criteria: a.The Applicant is using the same curb cuts as exists for the existing parking garage with a 25-foot-wide driveway. March 3, 2026: No further action is requested. b.It is not obvious if bike racks are proposed. HW recommends that the Applicant includes an interior storage location for bicycle accommodation in accordance with Section 195- 18.18 C. March 3, 2026: The Applicant has stated that thebike racks will be located inside the garage portion of the building. No further action is requested. c.HW recommends that the Applicant consider a solid five-foot-high fence along the property of 39 Prescott Street or additional trees for screening. March 3, 2026: The Applicant has added a five-foot-high fence along the property of 39 Prescott Street. d.The Applicant has proposed two generators, one for each building that are located near the surface parking spaces. The size of the generators looks small for the size of the building. HW recommends that the Applicant confirm the size and determine if additional screening or enclosureis necessary. March 3, 2026: The Applicant has stated that the generator pads have been removed from the plans. No further action is requested. e.The Applicant has provided a Photometric Calculation Plan, Sheet L3.0. The light candles appear to spill over onto the Meadow View Condominiums and slightly ontothe property at39 Prescott. HW recommends that the Applicant confirm that the amount of spillover will not be a nuisance for any abutting residents. March 3, 2026: The Applicant has updated the light and landscape plan to prevent light trespass. There still appears to be some spillover. HW recommends that the Applicant confirm that the amount of spillover will not be a nuisance for any abutting residents. April 2, 2026: The Applicant has updated the lighting plan and has noted that it cannotavoid light spillover along the southern lot unless a fence is installed. The Applicant would prefer to request a waiver for the lighting. HW defers the granting of the waiver to the ZBA. f.HW recommendsthat the Applicant includesa locus plan showing the names of abutters, land uses, and locations and width of all adjacent streets. March 3, 2026: The Applicant has provided a locus plan onSheet 13of the plan set. No further action is requested. H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx Town of North Andover April 2,2026 Page 15of 15 g.The Applicant is proposing one new fire hydrant. There is an existing hydrant on Prescott Street near 139 Prescottand an existing hydrant on High Street at the intersection with Prescott Street. It appears that fire apparatus can reach three sides of the proposed building. HW recommends that the Applicant coordinatewith the fire department to confirm thatthe hydrant locations are adequate and that they canaccess, circulate, and egressthe site and building safely. March 3, 2026: The Applicant is in the process of coordinating with the Fire Department. The ZBA may choose to request confirmation that the Fire Department is satisfied. h.HW recommends that the Applicant confirmwith the North Andover Department of Public Works (DPW) that the municipal sewer and water systems have adequate capacity to accommodate an additional296 residential units. March 3, 2026: The Applicant is in the process of coordinating with the DPW.The ZBA may choose to request confirmation that the DPWis satisfied. i.HW recommends that the Applicant add the depth of gravel subbase tothe Typical Bituminous PavementDetail, on Sheet 8. March 3, 2026: The Applicant has added the gravel subbase depth to the Typical Bituminous Pavement Detailon Sheet 8. No further action is requested. j.HW recommend that the Applicant confirmshow trash and recycling operations will be performed by the residents. March 3, 2026: The Applicant has stated that the trash and recycling will be stored within the garage and will be wheeled out to the driveway on trash and recycle pick up day. The ZBA may choose to make this process a condition of approval. Conclusions HW is satisfied that the Applicant has adequately addressed our comments. TheZBAmay choose to require that the Applicant providesa clear list of requested waivers as part of the Board’s review process. Please contact Janet Bernardo at 508-833-6600 or at jbernardo@horsleywitten.com if you have any questions regarding these comments. Sincerely, HORSLEY WITTEN GROUP, INC. Janet Carter Bernardo, PE Principal H:\\Projects\\2024\\24018 Town of North Andover\\24018P Zero Prescott Street\\Reports\\260402_3rd_SWPeerReview_Zero_Prescott.docx