Loading...
HomeMy WebLinkAboutCorrespondence - 1077 OSGOOD STREET 3/6/1985 „ a + w w, > wr lu ANDOVER Ww DEPAR"T"MENT w � w""" w ....... CENTRAL. HEADQUARTERS w.w:. FIRE 124 hay Street Norffi Andover, Plass. 818 WILIJAM V. DOLAN Tel. (617) Chief ea6Department Date: March 6, 1985 MAR To: No. Andover Planning Board From: Fire Chief Dolan Re: Special Permit Angus Realty PLANNING The proposed building is required to have a full sprinkler system with a fire department connection in accordance with MGL Chapter 148 Section 26G. This building shall also be connected to the municipal fire alarm system by means of a fire alarm box installed on the building activated from both a sprinkler flow switch and from any other internal fire warning systems . In addition to the fire hydrant at the right front of the existing building, an additional fire hydrant should be installed at the left rear of the proposed building to provide adequate water supply for fire purposes . Access to the area from Route 125 should be of the same standard width as similar entrances in the town. I ejjL-,, William V. Dolan, Chief "SMOKE DETECTORS SAVE UVES”